2005-05-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE LOCATION OF PANEL "B".
  
 2} INDICATE LOCATION OF OVERCURRENT
 PROTECTION FOR PANELS "A" & "B".
  
 3} THE OCP FOR CIRCUITS 12,13 PANEL "A",
 12,13,14,15 PANEL "B" IS TOO LARGE FOR
 THE CONDUCTORS PER 210.16.
  
 4} THE POWDER ROOM REQUIRES A GFI
 RECEPTACLE PER 210.8(A) & 210.52(D).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  