2007-02-27 14:16:40** UNSAT ***
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW DATED
 6/12/06 , 1/16/07 AND "PROVISO" DATED JULY OF 05. THE
 SAME COMMENTS APPLY.
  
 2) NOTE: PLEASE SEE THERE ARE MISSING CIRCUITS ON PLANS
 FOR SOME DEVICES. PLEASE SEE THERE ARE CIRCUITS ON
 PLANS WHICH ARE SHOWN AS "BLANK" ON PANEL SCHEDULE.
 PLEASE SEE NO CONDUCTOR SIZES ARE BEIGN SHOWN ON PANEL
 SCHEDULE. PLEASE SEE NO BREAKER/OCP SIZES ARE SHOWN ON
 PANEL SCHEDULE ETC.
 PLEASE SEE 240.4, 310.16, 408.4.
 SEE EXERPT TAKEN FROM COMMENTARY OF CODE.
 * REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANELBOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  