| 2006-06-02 00:00:00 | ******** UNSAT ******** |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | 1)NOTE: PLEASE SEE MISSING RECEPTS PER |
| | 210.52 |
| | |
| | ** PLEASE SEE THE RECEPTS WERE NOT |
| | ADDED. |
| | |
| | 2)NOTE: PLEASE SEE MISSING EGRESS LT AND |
| | CONTROL FOR DOOR EXITING FROM KITCHEN TO |
| | OUTSIDE. |
| | |
| | ** THIS WAS NOT DONE. |
| | |
| | 3)NOTE: PLEASE SEE NEW NOTE ON PLAN NOW |
| | MENTIONS FOR SD'S TO BE WIED AHEAD OF |
| | KITCHEN/BATH LIGHTING CIRCUIT?? |
| | PLEASE KNOW, THIS IS OK AND CAN BE DONE, |
| | HOWEVER,PLEAS EKNOW, KIT/BATH CIRCUIT |
| | WOULD ALSO THEN REQUIRE ARC FAULT |
| | PROTECTION. |
| | |
| | ** PLEASE SEE NOW PANEL SCHEDULE LIST |
| | THE SD'S ON A SEPARATE CIRCUIT, YET NOT |
| | ON PLANS, MENTIONS TO WIRE TO BATH/ |
| | KITCHEN LIGHTING CIRCUIT. |
| | ** PLEASE KNOW, THE SD'S WILL BE |
| | REQUIRED TO WIRED TO "A" LIGHTING |
| | CIRCUIT AND NOT ON THEIR OWN CIRCUIT. |
| | PLEASE KNOW, IF THESE ARE WIRED TO A |
| | KITCHEN OR BATH LIGHTING CIRCUIT, THEN |
| | ARC FAULT PROTECTION WILL BE REQUIRED. |
| | 210.12B. |
| | |
| | |
| | 4)NOTE: PLEASE SEE THAT PLANS MUST |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS AND |
| | DESIGN. |
| | 104.2.1 |
| | |
| | ** NOT DONE. |
| | PLEASE ALSO SEE BUILDING REVIEW COMMENTS |
| | , AS ALL SHEETS NOW HAVE THE TITLE |
| | BLOCKS REMOVED FROM THE PREVIOUS DESIGN |
| | PROFESSIONAL.?? |
| | PLANS NOW CONTAIN THE PRINTED NAME OF |
| | THE O/B. |
| | |
| | |
| | ** NEW NOTE** |
| | |
| | 1) NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) IS NOW ATTACHED WITH |
| | RESPECT TO THE DESIGN PROFESSIONAL AND |
| | REPEAT COMMENTS. |
| | |
| | 2) NOTE: PLEASE SEE THE NOTICE OF |
| | COMMENCMENT SUBMITTED IS NOW EXPIRED PER |
| | FS 713.13(2). |
| | WHEN WORK HAS NOT COMMENCED WITH IN 90 |
| | DAYS OF RECORDING SUCH NOC, THE NOC |
| | SHALL BECOME VOID. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |