Plan Review Notes
Plan Review Notes For Permit 05041991
Permit Number 05041991
Review Stop E
Sequence Number 4
Notes
Date Text
2006-02-21 00:00:00****** UNSAT ******
  
 1)NOTE: PLEASE SEE REVISION INDICATES TO
 INCLUDE FIRST FLR AREAS.
 PLEASE KNOW, PERMITTING WAS FOR
 RENOVATION OF ROOMS.
 PLEASE SEE VALUATION FOR COMPLETE SCOPE
 OF WORK AND CONTRACT OF JOB NEEDS TO BE
 UPDATED AS ORIGINAL SCOPE OF SEEMS TO
 PASSED ORIGINAL VALUE APPLIED FOR.
 FBC ADMINISTRATICE CODE 108.3 AS ADOPTED
 TO THE CITY OF WEST PALM BEACH.
 VALUE APPLIED FOR IS LOW.
  
 2)NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICLA PLANS FOR SCOPE OF WORK.
 PLEASE SEE PLANS DO NOT INDICATE
 ELECTRICAL FOR REMODEL OF FIRST FLR
 ARES.
 ROOMS ARE SHOWN ON ONE SHEET, BUT IT IS
 UNCLEAR WHAT IS BEING DONE.
 PLEASE SUBMIT COMPLETE ELECTRICLA PLANS
 FOR ALL WORK AND REMODEL WHICH IS TAKING
 PLACE AT HOTEL. ORIG SCOPE FOR REPAIR OF
 EXISTING.
 PLEASE INCLUDE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH PANEL SCHEDULES TO BE
 SUBMITTED.
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]