Plan Review Notes
Plan Review Notes For Permit 05041991
Permit Number 05041991
Review Stop P
Sequence Number 3
Notes
Date Text
2006-03-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. ORIGINAL PERMIT APPLICATION INDICATES
 THAT FIRST FLOOR WILL BE ADDRESSED IN
 FUTURE PERMIT. THE VALUE OF THE FIRST
 FLOOR SHALL BE ADDED TO THE PERMIT COST.
 2. PER SECTION 11-4.1.6(2) 20% OF COST
 OF ALTERATIONS SHALL BE FOR ACCESSIBLITY
 UPGRADES AND ARE REQUIRED. SEE SECTIONS
 11-9.1.2, 11-9.1.3, 11-9.1.4 AND
 11-9.2.3. INDICATE HOW THESE CODE
 SECTIONS ARE IN COMPLIANCE.
 3. SHT A.05 DETAILS 1 & 2 SHOW THE CLEAR
 FLOOR SPACE FOR THE SHOWER 11-4.21.2 AND
 FOR THE TUB 11-4.20.2.
 4. SHT A.06 ALL WATER CLOSETS INSTALLED
 ADJACENT TO A WALL SHALL BE 1'6" TO THE
 CENTERLINE OF THE FIXTURE OFF THE WALL.
 PLEASE INDICATE ON DETAILS. TOILET PAPER
 DISPENSERS SHALL BE LOCATED 19" MINIMUM
 OFF THE FLOOR. SECTION 11-4.16.6.
 5. SHT A.06 ALL LAVS SHALL COMPLY WITH
 THE FOLLOWING:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 PLEASE INDICATE ON DETAILS.
 6. SHT A.06 SHOW MEASUREMENTS FOR THE
 CONTROLS FOR THE TUB 11-4.20.5 (DETAILS
 4.3 & 6.1), AND FOR THE SHOWER 11-4.21.5
 (DETAILS 3.1 & 5.1).
 7. SUBMIT A SANITARY RISER ISOMETRIC
 DIAGRAM FOR ALL NEW WORK SHOWING ALL
 PIPE SIZES, TRAPS, AND VENTING PER
 SECTION 104.3.1.1.
 8. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 AND, IF REQUIRED BY SECTION 604.9, (W/M)
 WATER HAMMER ARRESTORS LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. SECTION 104.3.1.1.
  