Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop E
Sequence Number 3
Notes
Date Text
2006-05-31 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
  
 2} 250.6 OBJECTIONABLE CURRENT OVER
 GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE
 CURRENT. THE GROUNDING OF ELECTRICAL
 SYSTEMS, CIRCUIT CONDUCTORS, SURGE
 ARRESTERS, AND CONDUCTIVE
 NON?CURRENT-CARRYING MATERIALS AND
 EQUIPMENT SHALL BE INSTALLED AND
 ARRANGED IN A MANNER THAT WILL PREVENT
 OBJECTIONABLE CURRENT OVER THE GROUNDING
 CONDUCTORS OR GROUNDING PATHS.
 DISCONTINUE ONE OR MORE BUT NOT ALL OF
 SUCH GROUNDING CONNECTIONS.PREFERABLY
 AT PANEL "A".
  
 3} 220.17 APPLIANCE LOAD DWELLING
 UNIT(S).
 IT SHALL BE PERMISSIBLE TO APPLY A
 DEMAND FACTOR OF 75 PERCENT TO THE
 NAMEPLATE RATING LOAD OF FOUR OR MORE
 APPLIANCES FASTENED IN PLACE, OTHER THAN
 ELECTRIC RANGES, CLOTHES DRYERS,
 SPACE-HEATING EQUIPMENT, OR
 AIR-CONDITIONING EQUIPMENT, THAT ARE
 SERVED BY THE SAME FEEDER OR SERVICE IN
 A ONE-FAMILY, TWO-FAMILY, OR MULTIFAMILY
 DWELLING. RECALCULATE THE SERVICE LOAD
 PER 220 PART II, OR OPTIONAL
 CALCULATIONS PER 220 PART III. INDICATE
 CALCULATION USED.
  
 4} THE RANGE IS LISTED AT 8KW IN THE
 CALC'S BUT AT 25 AMPS ON A 40 AMP
 BREAKER ON THE SCHEDULE.
  
 5} 11.8.3.5 NFPA-72 WHERE STAIRS LEAD TO
 OTHER OCCUPIED LEVELS, A SMOKE ALARM OR
 SMOKE DETECTOR SHALL BE LOCATED SO THAT
 SMOKE RISING IN THE STAIRWAY CANNOT BE
 PREVENTED FROM REACHING THE SMOKE ALARM
 OR SMOKE DETECTOR BY AN INTERVENING DOOR
 OR OBSTRUCTION.ADD ONE INSIDE THE STAIR
 HALL. AFTER REVIEWING PREVIOUS NOTES,
 IREALIZED THE ARTICLES FROM THAT REVIEW
 WERE CURRENT. SEE NOTE #4, SAME INTENT,
 DIFFERENT NUMBER.
  
 6} SMOKE DETECTORS TARE REQUIRED TO BE
 INTERCONNECTED PER R313.1 FBC, 11.8.2
 NFPA-72. PLEASE SUPPLY SPECIFICATIONS
 INDICATING COMPLIANCE WITH THESE
 ARTICLES WHILE THE DETECTORS ARE BEING
 FED WITH MORE THAN ONE CIRCUIT.
  
 7} PLEASE SEE 210.11(C)(3) BATHROOM
 BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST
 ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY THE BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS
 SHALL HAVE NO OTHER OUTLETS.
 EXCEPTION: WHERE THE 20-AMPERE CIRCUIT
 SUPPLIES A SINGLE BATHROOM, OUTLETS FOR
 OTHER EQUIPMENT WITHIN THE SAME BATHROOM
 SHALL BE PERMITTED TO BE SUPPLIED IN
 ACCORDANCE WITH 210.23(A). ALL BATHS ARE
 IN VIOLATION EXCEPT 35 AND 38.
  
 8} 210.11(C)(1) SMALL-APPLIANCE BRANCH
 CIRCUITS. IN ADDITION TO THE NUMBER OF
 BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE
 PROVIDED FOR ALL RECEPTACLE OUTLETS
 SPECIFIED BY 210.52(B). ONLY ONE
 CIRCUIT, #34 APPEARS TO BE A "SMALL
 APPLIANCE" CIRCUIT. IT SHOULD BE
 DESIGNATED SUCH ON THE PANEL SCHEDULE,
 ALONG WITH THE REQUIRED SECOND CIRCUIT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  