| Date |
Text |
| 2006-05-31 00:00:00 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | |
| | 2} 250.6 OBJECTIONABLE CURRENT OVER |
| | GROUNDING CONDUCTORS. |
| | (A) ARRANGEMENT TO PREVENT OBJECTIONABLE |
| | CURRENT. THE GROUNDING OF ELECTRICAL |
| | SYSTEMS, CIRCUIT CONDUCTORS, SURGE |
| | ARRESTERS, AND CONDUCTIVE |
| | NON?CURRENT-CARRYING MATERIALS AND |
| | EQUIPMENT SHALL BE INSTALLED AND |
| | ARRANGED IN A MANNER THAT WILL PREVENT |
| | OBJECTIONABLE CURRENT OVER THE GROUNDING |
| | CONDUCTORS OR GROUNDING PATHS. |
| | DISCONTINUE ONE OR MORE BUT NOT ALL OF |
| | SUCH GROUNDING CONNECTIONS.PREFERABLY |
| | AT PANEL "A". |
| | |
| | 3} 220.17 APPLIANCE LOAD DWELLING |
| | UNIT(S). |
| | IT SHALL BE PERMISSIBLE TO APPLY A |
| | DEMAND FACTOR OF 75 PERCENT TO THE |
| | NAMEPLATE RATING LOAD OF FOUR OR MORE |
| | APPLIANCES FASTENED IN PLACE, OTHER THAN |
| | ELECTRIC RANGES, CLOTHES DRYERS, |
| | SPACE-HEATING EQUIPMENT, OR |
| | AIR-CONDITIONING EQUIPMENT, THAT ARE |
| | SERVED BY THE SAME FEEDER OR SERVICE IN |
| | A ONE-FAMILY, TWO-FAMILY, OR MULTIFAMILY |
| | DWELLING. RECALCULATE THE SERVICE LOAD |
| | PER 220 PART II, OR OPTIONAL |
| | CALCULATIONS PER 220 PART III. INDICATE |
| | CALCULATION USED. |
| | |
| | 4} THE RANGE IS LISTED AT 8KW IN THE |
| | CALC'S BUT AT 25 AMPS ON A 40 AMP |
| | BREAKER ON THE SCHEDULE. |
| | |
| | 5} 11.8.3.5 NFPA-72 WHERE STAIRS LEAD TO |
| | OTHER OCCUPIED LEVELS, A SMOKE ALARM OR |
| | SMOKE DETECTOR SHALL BE LOCATED SO THAT |
| | SMOKE RISING IN THE STAIRWAY CANNOT BE |
| | PREVENTED FROM REACHING THE SMOKE ALARM |
| | OR SMOKE DETECTOR BY AN INTERVENING DOOR |
| | OR OBSTRUCTION.ADD ONE INSIDE THE STAIR |
| | HALL. AFTER REVIEWING PREVIOUS NOTES, |
| | IREALIZED THE ARTICLES FROM THAT REVIEW |
| | WERE CURRENT. SEE NOTE #4, SAME INTENT, |
| | DIFFERENT NUMBER. |
| | |
| | 6} SMOKE DETECTORS TARE REQUIRED TO BE |
| | INTERCONNECTED PER R313.1 FBC, 11.8.2 |
| | NFPA-72. PLEASE SUPPLY SPECIFICATIONS |
| | INDICATING COMPLIANCE WITH THESE |
| | ARTICLES WHILE THE DETECTORS ARE BEING |
| | FED WITH MORE THAN ONE CIRCUIT. |
| | |
| | 7} PLEASE SEE 210.11(C)(3) BATHROOM |
| | BRANCH CIRCUITS. IN ADDITION TO THE |
| | NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST |
| | ONE 20-AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY THE BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS |
| | SHALL HAVE NO OTHER OUTLETS. |
| | EXCEPTION: WHERE THE 20-AMPERE CIRCUIT |
| | SUPPLIES A SINGLE BATHROOM, OUTLETS FOR |
| | OTHER EQUIPMENT WITHIN THE SAME BATHROOM |
| | SHALL BE PERMITTED TO BE SUPPLIED IN |
| | ACCORDANCE WITH 210.23(A). ALL BATHS ARE |
| | IN VIOLATION EXCEPT 35 AND 38. |
| | |
| | 8} 210.11(C)(1) SMALL-APPLIANCE BRANCH |
| | CIRCUITS. IN ADDITION TO THE NUMBER OF |
| | BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| | OF THIS SECTION, TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE |
| | PROVIDED FOR ALL RECEPTACLE OUTLETS |
| | SPECIFIED BY 210.52(B). ONLY ONE |
| | CIRCUIT, #34 APPEARS TO BE A "SMALL |
| | APPLIANCE" CIRCUIT. IT SHOULD BE |
| | DESIGNATED SUCH ON THE PANEL SCHEDULE, |
| | ALONG WITH THE REQUIRED SECOND CIRCUIT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |