| Date |
Text |
| 2006-06-12 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ***PLAN CHECK ONLY*** |
| | |
| | GOVERNING CODE IS FBC2004 EFFECTIVE |
| | OCTOBER 1, 2005.NO PERMIT WAS APPLIED |
| | FOR PRIOR TO THIS DATE.REVISE ALL |
| | INCORRECT CODE REFERENCES. |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEWS; |
| | NUMBERING TO REMAIN THE SAME FOR |
| | CONSISTENCY.NOTE THAT CODE REFERENCE |
| | NUMBERS HAVE CHANGED AS THE FIRST REVIEW |
| | WAS DONE ON FBC2001, SECOND REVIEW ON |
| | FBC2004. |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.-5.)ADDRESSED. |
| | |
| | 6.)ENERGY CALCS REQUIRED, FBC11-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC, FBC11-103.1.2. |
| | |
| | (2ND REVIEW) ENERGY CALCS WERE |
| | SUBMITTED.THE |
| | CEILING/FLOOR ASSEMBLY BETWEEN THE |
| | UNCONDITIONED GARAGE AREA AND THE |
| | CONDITIONED SECOND FLOOR IS NOT ON THE |
| | ENERGY CALCS, FIRST PAGE.SECOND PAGE |
| | SHOWS RAISED WOOD FLOOR ADJACENT, PLANS |
| | SHOW CONCRETE FLOOR.THE PLAN DOES NOT |
| | SHOW INSULATION BETWEEN THE LAUNDRY AREA |
| | IN THE GARAGE AND THE UTILITY ROOM. |
| | INSULATION IS SHOWN GRAPHICALLY ON A2.0 |
| | BETWEEN FIRST AND SECOND FLOOR. |
| | INSULATION SHOWN GRAPHICALLY BETWEEN |
| | GARAGE AND ENTRY.PLEASE SPECIFY.THE |
| | WOOD FRAME WALL IS NOT INCLUDED IN THE |
| | ENERGY CALCS. |
| | |
| | (3RD REVIEW) ENERGY CALCS NO LONGER IN |
| | THE PACKAGE.REQUIRED FOR PERMITTING. |
| | |
| | 7.)THE WIND RESISTANCE NOTES ON T1 |
| | WERE PREPARED BY ANOTHER DESIGN |
| | PROFESSIONAL, MAKES REFERENCE TO A |
| | COMMERCIAL STRUCTURE, AND STATE THAT |
| | THIS IS A PARTIALLY ENCLOSED BUILDING |
| | WHICH IS NOT TO BE SHUTTERED.OTHER |
| | SHEETS SPECIFY IMPACT GLASS.PLEASE |
| | CLARIFY. |
| | |
| | (2ND REVIEW) SHEET T1 STILL STATES THAT |
| | THIS IS A PARTIALLY ENCLOSED STRUCTURE. |
| | SEE FBC1609.2. |
| | |
| | (3RD REVIEW) REFERS TO 1606; WIND |
| | PROVISIONS ARE 1609.REVISE OR |
| | ELIMINATE INCORRECT CODE REFERENCES. |
| | ALSO ON A7.0. |
| | |
| | 8.-10.)ADDRESSED. |
| | |
| | 11.)LOCAL OR STATE PRODUCT APPROVAL |
| | REQUIRED FOR: |
| | SHINGLE OR METAL ROOF |
| | WINDOWS |
| | MULLIONS |
| | FIXED GLASS WINDOWS |
| | FRENCH DOORS |
| | CASEMENT WINDOW |
| | OVERHEAD DOOR |
| | SKYLIGHTS |
| | IMPACT PROTECTION IF REQUIRED |
| | GARAGE DOOR |
| | TEST REPORT AND INSTALLATION |
| | INSTRUCTIONS REQUIRED IN ADDITION TO THE |
| | FLORIDA OR LOCAL PRODUCT APPROVAL. |
| | |
| | SEPARATE PERMITS WILL BE REQUIRED FOR |
| | ANY PRODUCT APPROVALS NOT PROPERLY |
| | SUBMITTED AND REVIEWED PRIOR TO |
| | ISSUANCE. |
| | |
| | (2ND REVIEW) NONE SUBMITTED.PRODUCT |
| | APPROVALS TO BE REVIEWED BY DESIGNER OF |
| | RECORD FBC*106.3.3. |
| | |
| | (3RD REVIEW) TWO COPIES REQUIRED OF ALL |
| | DOCUMENTS.ONLY ONE ROOF PRODUCT |
| | APPROVAL SUBMITTED. |
| | |
| | FIVE DIFFERENT TYPES OF WINDOWS ARE |
| | SHOWN ON THE PLAN; ONLY ONE PRODUCT |
| | APPROVAL SUBMITTED.PLANS NOT CLEAR, |
| | SEE OTHER COMMENT REGARDING WINDOWS. |
| | IMPACT S/H, IMPACT FIXED, IMPACT |
| | CASEMENT, S/H, CASEMENT. |
| | |
| | THE PB COUNTY PRODUCT APPROVAL CHECKLIST |
| | IS AN ACCEPTABLE METHOD OF SHOWING |
| | COMPLIANCE WITH FBC*106.3.3, ARCHITECT |
| | REVIEW.PROVIDE ORIGINAL SIGNATURES ON |
| | THE FORM OR PROVIDE A REVIEW STAMP FOR |
| | ALL PRODUCT APPROVALS.IF ADDING |
| | PRODUCT APPROVALS, PLEASE REVISE THE |
| | PRODUCT APPROVAL LIST. |
| | |
| | COMPLETE THE ATTACHED HURRICANE SHUTTER |
| | INSTALLATION SCHEDULE, OR PROVIDE ALL |
| | REQUIRED INFORMATION IN A SIMILAR |
| | FORMAT. |
| | |
| | 12-13.)ADDRESSED. |
| | |
| | 14.) ADDRESSED. |
| | |
| | 15-16.)ADDRESSED. |
| | |
| | 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING |
| | NOTES, ITEM 2 (NAILING PATTERN 6IN |
| | EDGES, 6IN FIELD) IS NON COMPLIANT, SEE |
| | FBC*TABLE 2306.1.THE RESPONSE LETTER |
| | STATES THAT THE SHEATHING NAILING WAS |
| | CORRECTED TO 6IN OC EDGES AND 12IN OC |
| | FIELD. |
| | |
| | (2ND REVIEW) NOT ADDRESSED.STILL |
| | STATES 6/6.6/12 WAS SPECIFIED IN THE |
| | RESPONSE LETTER. THIS IS ALSO NOT CODE |
| | COMPLIANT.SEE FBC TABLE 2304.9.1. |
| | |
| | (3RD REVIEW) NOT ADDRESSED, PLANS STILL |
| | SHOW 6/12.SUBFLOOR NAILING ALSO NOT |
| | COMPLIANT WITH FBC TABLE 2304.9.1. |
| | |
| | 18.-19.)NOT ADDRESSED. |
| | |
| | 20.)WHAT IS THE CONSTRUCTION OF THE |
| | CABANA WALLS?IT DOES NOT APPEAR TO BE |
| | BLOCK.PROVIDE A DETAIL. |
| | |
| | 21.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE BAY WINDOWS. |
| | |
| | (2ND REVIEW) NOT ADDRESSED.A CROSS |
| | SECTION WAS PROVIDED SHOWING THE STAIR |
| | AND BAY WINDOW.THIS IS NOT A |
| | STRUCTURAL DETAIL AS SPACING, FASTENING, |
| | DESIGN LOADS WERE NOT PROVIDED. |
| | |
| | (3RD REVIEW) NOT ADDRESSED.PROVIDE |
| | DIMENSIONS, NONE SHOWN ON PLAN.SHOW |
| | COMPLIANCE WITH FBC R302.1,302.2 (MUST |
| | BE OVER 3' FROM PROPERTY LINE). |
| | |
| | 22-26.)ADDRESSED. |
| | |
| | 27.)SPECIFY INSULATION FOR THE |
| | ADJACENT WALL (BETWEEN GARAGE AND ENTRY |
| | HALL). |
| | |
| | (2ND REVIEW) NOT ADDRESSED.SHOWN |
| | GRAPHICALLY BUT NOT SPECIFIED.ALSO |
| | NEEDS INSULATION BETWEEN THE GARAGE AND |
| | UTILITY ROOM. |
| | |
| | (3RD REVIEW) NOT ADDRESSED.THE FRAME |
| | WALL WAS CHANGED TO BLOCK, STILL NEEDS |
| | INSULATION.THE FRAME WALL SHOWS "SOUND |
| | INSULATION", MUST HAVE R VALUE SPECIFIED |
| | FBC13-602. |
| | |
| | 28.-32.)ADDRESSED. |
| | |
| | 31.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS, WITH ALL DIMENSIONS, |
| | INCLUDING THE LANDING AND FIREBLOCKING |
| | FBC2305.1.4(3). |
| | |
| | (2ND REVIEW) NOT ADDRESSED. |
| | |
| | (3RD REVIEW) NOT ADDRESSED. |
| | |
| | 32.)ADDRESSED. |
| | |
| | 33.)SAFETY GLASS REQUIRED AT TUBS AND |
| | SHOWER, FBC2405.1. |
| | |
| | (2ND REVIEW) ADDRESSED IF IMPACT WINDOWS |
| | ARE USED AS PER PLAN. |
| | |
| | (3RD REVIEW) UNSURE AS TO COMPLIANCE. |
| | CONFLICTING NOTES REGARDING IMPACT |
| | PROTECTION ON THE PLAN. |
| | |
| | 34.)THE CANTILEVERED BALCONY DETAIL A6 |
| | DOES NOT HAVE A SLAB DIMENSION. |
| | |
| | (2ND & 3RD REVIEWS) NOT ADDRESSED. |
| | |
| | 35.)SPECIFY SOFFIT VENTING AND SHOW |
| | COMPLIANCE FBC2309.7. |
| | |
| | (2ND & 3RD REVIEWS) NOT ADDRESSED. |
| | |
| | 36.)SPECIFY REACTION LOADS ON THE ROOF |
| | FRAMING PLAN A7.0. |
| | |
| | NOT ADDRESSED. |
| | |
| | 37-39.) ADDRESSED. |
| | |
| | 40.) REINFORCEMENT ABOVE OPENINGS HAS |
| | NOT BEEN SPECIFIED.PROVIDE A SCHEDULE. |
| | |
| | ADDRESSED BY STATING THAT LINTELS WILL |
| | BE INSTALLED.SEE COMMENT 46 BELOW. |
| | |
| | PROVIDE A LINTEL SCHEDULE. |
| | |
| | 41.) A COPY OF THE PLANS HAS BEEN |
| | RETAINED. |
| | |
| | ***NEW COMMENTS*** |
| | |
| | 42.)SHOW POSITIVE DRAINAGE FBC R401.3, |
| | FBC*109.3.10. |
| | |
| | NOT ADDRESSED. |
| | |
| | 43.)ADDRESSED. |
| | |
| | 44.)ALL CHANGES TO THE PLAN ARE TO BE |
| | CLEARLY INDICATED WITH A CLOUD AND |
| | REVISION NUMBER.AS NONE OF THE CHANGES |
| | WERE CLOUDED AND OLD SHEETS WERE NOT |
| | SUBMITTED, THIS REQUIRED A COMPLETELY |
| | NEW PLAN REVIEW.TO AVOID DELAYS, |
| | CLEARLY INDICATE ALL CHANGES AND SUBMIT |
| | OLD SHEETS AS IS STANDARD INDUSTRY |
| | PRACTICE. |
| | |
| | 45.)ADDRESSED. |
| | |
| | 46.)PROVIDE INFORMATION IN REGARDS TO |
| | THE BEAM ABOVE THE GARAGE DOOR.YOU |
| | HAVE A 16? SPAN SUPPORTING CONCRETE |
| | FLOOR JOISTS, A CONCRETE BALCONY AND A |
| | CONCRETE BLOCK 2ND FLOOR WITH NO |
| | STRUCTURAL INFORMATION AS TO HOW THIS |
| | WILL BE ACCOMPLISHED.THERE IS A NOTE |
| | STATING THAT LINTELS WILL GO OVER ALL |
| | OPENINGS.PROVIDE MORE INFORMATION. |
| | |
| | (2ND REVIEW) BEAM HAS BEEN CHANGED TO |
| | 8X20 W/2#6.PROVIDE CALCULATIONS; IT IS |
| | NOT CLEAR HOW YOU ARE MAKING THESE |
| | CHANGES TO ACCOMODATE THE 16' SPAN |
| | SUPPORTING A SECOND STORY WHICH IS |
| | BLOCK. |
| | |
| | 47.)PROVIDE A DETAIL FOR THE BEARING |
| | WALL, INTERIOR NON BEARING WALLS, AND |
| | THE CABANA WALL. |
| | |
| | NOT ADDRESSED. |
| | |
| | NEW COMMENTS, 3RD REVIEW: |
| | |
| | 48.)A7.0 REFERS TO ASCE7-98, CORRECT |
| | REFERENCE IS ASCE7-02, FBC35. |
| | |
| | 49.)THE PLANS STATE THAT ALL WINDOWS |
| | WILL BE IMPACT CASEMENT, SCHEDULE SHOWS |
| | FIXED AND SINGLE HUNG, IMPACT 2ND |
| | FLOOR,SHUTTERS 1ST FLOOR, AND SHUTTER |
| | PRODUCT APPROVALS AND S/H NON IMPACT |
| | WINDOW PRODUCT APPROVALS SUBMITTED. |
| | ADDRESS. |
| | |
| | 50.)PROVIDE A SURVEY AND SOILS |
| | INVESTIGATION REPORT FOR THIS JOB, TWO |
| | ORIGINALS.I BELIEVE THAT THEY WERE IN |
| | THE PACKAGE AT ONE TIME. |
| | |
| | 51.)THE ATTIC LIVE LOAD IS TO COMPLY |
| | WITH FBC TABLE 1607.1 (MIN 10PSF ATTICS |
| | WITHOUT STORAGE, 20 W/STORAGE). |
| | |
| | 52.)NOTE THAT THIS IS A PLAN CHECK |
| | ONLY, PERMIT APPLICATION REQUIRED. |
| | |
| | 53.)PROVIDE ONE SET OF THE OLD PLANS |
| | WHEN RESUBMITTING FOR REFERENCE. |