Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop B
Sequence Number 3
Notes
Date Text
2006-06-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ***PLAN CHECK ONLY***
  
 GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.NO PERMIT WAS APPLIED
 FOR PRIOR TO THIS DATE.REVISE ALL
 INCORRECT CODE REFERENCES.
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 (2ND REVIEW) ENERGY CALCS WERE
 SUBMITTED.THE
 CEILING/FLOOR ASSEMBLY BETWEEN THE
 UNCONDITIONED GARAGE AREA AND THE
 CONDITIONED SECOND FLOOR IS NOT ON THE
 ENERGY CALCS, FIRST PAGE.SECOND PAGE
 SHOWS RAISED WOOD FLOOR ADJACENT, PLANS
 SHOW CONCRETE FLOOR.THE PLAN DOES NOT
 SHOW INSULATION BETWEEN THE LAUNDRY AREA
 IN THE GARAGE AND THE UTILITY ROOM.
 INSULATION IS SHOWN GRAPHICALLY ON A2.0
 BETWEEN FIRST AND SECOND FLOOR.
 INSULATION SHOWN GRAPHICALLY BETWEEN
 GARAGE AND ENTRY.PLEASE SPECIFY.THE
 WOOD FRAME WALL IS NOT INCLUDED IN THE
 ENERGY CALCS.
  
 (3RD REVIEW) ENERGY CALCS NO LONGER IN
 THE PACKAGE.REQUIRED FOR PERMITTING.
  
 7.)THE WIND RESISTANCE NOTES ON T1
 WERE PREPARED BY ANOTHER DESIGN
 PROFESSIONAL, MAKES REFERENCE TO A
 COMMERCIAL STRUCTURE, AND STATE THAT
 THIS IS A PARTIALLY ENCLOSED BUILDING
 WHICH IS NOT TO BE SHUTTERED.OTHER
 SHEETS SPECIFY IMPACT GLASS.PLEASE
 CLARIFY.
  
 (2ND REVIEW) SHEET T1 STILL STATES THAT
 THIS IS A PARTIALLY ENCLOSED STRUCTURE.
 SEE FBC1609.2.
  
 (3RD REVIEW) REFERS TO 1606; WIND
 PROVISIONS ARE 1609.REVISE OR
 ELIMINATE INCORRECT CODE REFERENCES.
 ALSO ON A7.0.
  
 8.-10.)ADDRESSED.
  
 11.)LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FOR:
 SHINGLE OR METAL ROOF
 WINDOWS
 MULLIONS
 FIXED GLASS WINDOWS
 FRENCH DOORS
 CASEMENT WINDOW
 OVERHEAD DOOR
 SKYLIGHTS
 IMPACT PROTECTION IF REQUIRED
 GARAGE DOOR
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS REQUIRED IN ADDITION TO THE
 FLORIDA OR LOCAL PRODUCT APPROVAL.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED AND REVIEWED PRIOR TO
 ISSUANCE.
  
 (2ND REVIEW) NONE SUBMITTED.PRODUCT
 APPROVALS TO BE REVIEWED BY DESIGNER OF
 RECORD FBC*106.3.3.
  
 (3RD REVIEW) TWO COPIES REQUIRED OF ALL
 DOCUMENTS.ONLY ONE ROOF PRODUCT
 APPROVAL SUBMITTED.
  
 FIVE DIFFERENT TYPES OF WINDOWS ARE
 SHOWN ON THE PLAN; ONLY ONE PRODUCT
 APPROVAL SUBMITTED.PLANS NOT CLEAR,
 SEE OTHER COMMENT REGARDING WINDOWS.
 IMPACT S/H, IMPACT FIXED, IMPACT
 CASEMENT, S/H, CASEMENT.
  
 THE PB COUNTY PRODUCT APPROVAL CHECKLIST
 IS AN ACCEPTABLE METHOD OF SHOWING
 COMPLIANCE WITH FBC*106.3.3, ARCHITECT
 REVIEW.PROVIDE ORIGINAL SIGNATURES ON
 THE FORM OR PROVIDE A REVIEW STAMP FOR
 ALL PRODUCT APPROVALS.IF ADDING
 PRODUCT APPROVALS, PLEASE REVISE THE
 PRODUCT APPROVAL LIST.
  
 COMPLETE THE ATTACHED HURRICANE SHUTTER
 INSTALLATION SCHEDULE, OR PROVIDE ALL
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.
  
 12-13.)ADDRESSED.
  
 14.) ADDRESSED.
  
 15-16.)ADDRESSED.
  
 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING
 NOTES, ITEM 2 (NAILING PATTERN 6IN
 EDGES, 6IN FIELD) IS NON COMPLIANT, SEE
 FBC*TABLE 2306.1.THE RESPONSE LETTER
 STATES THAT THE SHEATHING NAILING WAS
 CORRECTED TO 6IN OC EDGES AND 12IN OC
 FIELD.
  
 (2ND REVIEW) NOT ADDRESSED.STILL
 STATES 6/6.6/12 WAS SPECIFIED IN THE
 RESPONSE LETTER. THIS IS ALSO NOT CODE
 COMPLIANT.SEE FBC TABLE 2304.9.1.
  
 (3RD REVIEW) NOT ADDRESSED, PLANS STILL
 SHOW 6/12.SUBFLOOR NAILING ALSO NOT
 COMPLIANT WITH FBC TABLE 2304.9.1.
  
 18.-19.)NOT ADDRESSED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL.
  
 21.)PROVIDE A STRUCTURAL DETAIL FOR
 THE BAY WINDOWS.
  
 (2ND REVIEW) NOT ADDRESSED.A CROSS
 SECTION WAS PROVIDED SHOWING THE STAIR
 AND BAY WINDOW.THIS IS NOT A
 STRUCTURAL DETAIL AS SPACING, FASTENING,
 DESIGN LOADS WERE NOT PROVIDED.
  
 (3RD REVIEW) NOT ADDRESSED.PROVIDE
 DIMENSIONS, NONE SHOWN ON PLAN.SHOW
 COMPLIANCE WITH FBC R302.1,302.2 (MUST
 BE OVER 3' FROM PROPERTY LINE).
  
 22-26.)ADDRESSED.
  
 27.)SPECIFY INSULATION FOR THE
 ADJACENT WALL (BETWEEN GARAGE AND ENTRY
 HALL).
  
 (2ND REVIEW) NOT ADDRESSED.SHOWN
 GRAPHICALLY BUT NOT SPECIFIED.ALSO
 NEEDS INSULATION BETWEEN THE GARAGE AND
 UTILITY ROOM.
  
 (3RD REVIEW) NOT ADDRESSED.THE FRAME
 WALL WAS CHANGED TO BLOCK, STILL NEEDS
 INSULATION.THE FRAME WALL SHOWS "SOUND
 INSULATION", MUST HAVE R VALUE SPECIFIED
 FBC13-602.
  
 28.-32.)ADDRESSED.
  
 31.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH ALL DIMENSIONS,
 INCLUDING THE LANDING AND FIREBLOCKING
 FBC2305.1.4(3).
  
 (2ND REVIEW) NOT ADDRESSED.
  
 (3RD REVIEW) NOT ADDRESSED.
  
 32.)ADDRESSED.
  
 33.)SAFETY GLASS REQUIRED AT TUBS AND
 SHOWER, FBC2405.1.
  
 (2ND REVIEW) ADDRESSED IF IMPACT WINDOWS
 ARE USED AS PER PLAN.
  
 (3RD REVIEW) UNSURE AS TO COMPLIANCE.
 CONFLICTING NOTES REGARDING IMPACT
 PROTECTION ON THE PLAN.
  
 34.)THE CANTILEVERED BALCONY DETAIL A6
 DOES NOT HAVE A SLAB DIMENSION.
  
 (2ND & 3RD REVIEWS) NOT ADDRESSED.
  
 35.)SPECIFY SOFFIT VENTING AND SHOW
 COMPLIANCE FBC2309.7.
  
 (2ND & 3RD REVIEWS) NOT ADDRESSED.
  
 36.)SPECIFY REACTION LOADS ON THE ROOF
 FRAMING PLAN A7.0.
  
 NOT ADDRESSED.
  
 37-39.) ADDRESSED.
  
 40.) REINFORCEMENT ABOVE OPENINGS HAS
 NOT BEEN SPECIFIED.PROVIDE A SCHEDULE.
  
 ADDRESSED BY STATING THAT LINTELS WILL
 BE INSTALLED.SEE COMMENT 46 BELOW.
  
 PROVIDE A LINTEL SCHEDULE.
  
 41.) A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 ***NEW COMMENTS***
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 NOT ADDRESSED.
  
 43.)ADDRESSED.
  
 44.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY INDICATED WITH A CLOUD AND
 REVISION NUMBER.AS NONE OF THE CHANGES
 WERE CLOUDED AND OLD SHEETS WERE NOT
 SUBMITTED, THIS REQUIRED A COMPLETELY
 NEW PLAN REVIEW.TO AVOID DELAYS,
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS AS IS STANDARD INDUSTRY
 PRACTICE.
  
 45.)ADDRESSED.
  
 46.)PROVIDE INFORMATION IN REGARDS TO
 THE BEAM ABOVE THE GARAGE DOOR.YOU
 HAVE A 16? SPAN SUPPORTING CONCRETE
 FLOOR JOISTS, A CONCRETE BALCONY AND A
 CONCRETE BLOCK 2ND FLOOR WITH NO
 STRUCTURAL INFORMATION AS TO HOW THIS
 WILL BE ACCOMPLISHED.THERE IS A NOTE
 STATING THAT LINTELS WILL GO OVER ALL
 OPENINGS.PROVIDE MORE INFORMATION.
  
 (2ND REVIEW) BEAM HAS BEEN CHANGED TO
 8X20 W/2#6.PROVIDE CALCULATIONS; IT IS
 NOT CLEAR HOW YOU ARE MAKING THESE
 CHANGES TO ACCOMODATE THE 16' SPAN
 SUPPORTING A SECOND STORY WHICH IS
 BLOCK.
  
 47.)PROVIDE A DETAIL FOR THE BEARING
 WALL, INTERIOR NON BEARING WALLS, AND
 THE CABANA WALL.
  
 NOT ADDRESSED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 48.)A7.0 REFERS TO ASCE7-98, CORRECT
 REFERENCE IS ASCE7-02, FBC35.
  
 49.)THE PLANS STATE THAT ALL WINDOWS
 WILL BE IMPACT CASEMENT, SCHEDULE SHOWS
 FIXED AND SINGLE HUNG, IMPACT 2ND
 FLOOR,SHUTTERS 1ST FLOOR, AND SHUTTER
 PRODUCT APPROVALS AND S/H NON IMPACT
 WINDOW PRODUCT APPROVALS SUBMITTED.
 ADDRESS.
  
 50.)PROVIDE A SURVEY AND SOILS
 INVESTIGATION REPORT FOR THIS JOB, TWO
 ORIGINALS.I BELIEVE THAT THEY WERE IN
 THE PACKAGE AT ONE TIME.
  
 51.)THE ATTIC LIVE LOAD IS TO COMPLY
 WITH FBC TABLE 1607.1 (MIN 10PSF ATTICS
 WITHOUT STORAGE, 20 W/STORAGE).
  
 52.)NOTE THAT THIS IS A PLAN CHECK
 ONLY, PERMIT APPLICATION REQUIRED.
  
 53.)PROVIDE ONE SET OF THE OLD PLANS
 WHEN RESUBMITTING FOR REFERENCE.