Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-31 00:00:00DENIED;
 1. FBC-2004 TO BE USED.
 2.THE 1/2 BATHROOMS ON 1 ST FLOOR DO NOT
 APPEAR TO HAVE THE CLEARANCES REQUIRED
 BY FBC-2004 PLUMBING SEC.405.3.1.
 3.SANIRARY RISER DIAGRAM, SIZE ALL
 PIPES, VENTING VIOLATIONS, FIXTURES MISS
 NAMED, DOES NOT FOLLOW FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;