Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop M
Sequence Number 2
Notes
Date Text
2006-01-31 00:00:00*** DENIED ***
 1) MACHANICAL PLAN (DUCT LAY-OUT) IS
 DIFFICULT TO READ DUE TO SIZE.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
  
 2) NO RETURN AIR PROVIDED FOR. BALANCED
 RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 4) WHEN APPLYING FOR PERMIT PLANS WILL
 NEED TO COMPLY WITH 2004 BUILDING CODES,
 AND ENERGY CALCULATIONS WILL NEEN TO BE
 ON FORM 600A-2004.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.