| 2006-01-30 00:00:00 | *********** UNSAT2ND REVIEW ********* |
| | |
| | ** PLEASE SEE MANY NOTES FROM PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE ADDRESSED. |
| | ** PLEASE ALSO SEE NEW NOTES DUE TO |
| | CHANGES ON PLANS. |
| | |
| | |
| | |
| | ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| | SUBMITTED FOR"PLAN REVIEW"AND NOT |
| | FOR PERMIT. |
| | PLEASE KNOW, AS OF OCT 1ST, 2005 THE FBC |
| | HAS CHANGED TO THE 2004. PLANS MUST |
| | CHANGE TO THE 2004 FBC WHEN SUBMITTED |
| | FOR PERMIT. THIS WILL AFFECT MANY AREAS |
| | OF PLANS. |
| | PLEASE ALSO KNOW A NEW PERMIT PROCESSING |
| | NUMBER MAY BE GIVEN. |
| | |
| | |
| | |
| | 1)NOTE: NOTE #1, NO, PLEASE SEE RESPONSE |
| | LTR MENTIONS THIS WAS SUBMITTED, HOWEVER |
| | THIS COULD NOT BE LOCATED ON PLANS. |
| | |
| | **PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: NOTE #2 OK, HOWEVER PLEASE SEE |
| | NOTE #12. |
| | |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE NEW |
| | COMMENT FOR CIRCUITING ON PLANS. |
| | PLEASE SEE THE REQUIRED DEDICATED BATH |
| | CIRCUIT IS SHOWN ON WITH OTHER RECEPTS |
| | ETC IN OTHER AREAS WHICH IS NOT |
| | PERMITTED. |
| | |
| | ** PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | APPEAR TO BE SHOWN AS 20A'S HOWEVER NO |
| | CONDUCTORS SIZES ARE SHOWN? |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S |
| | WERE ADDED, HOWEVER PLEASE STILL SE |
| | MISSING SD'S AS REDLINED. THESE MUST BE |
| | INSIDE AND OUTSIDE ALL SLEEEPING RMS. |
| | PLEASE ALSO SEE SD'S ARE REQUIRED TO BE |
| | WIRED INLINEETC , HOWEVER PLEASE SEE |
| | SD'S ARE BEING SHOWN TO AT LEAST 6 |
| | SEPARATE CIRCUITS???? |
| | |
| | ** SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER: NFPA-72 11.5.1.1 |
| | PLEASE SEE REDLINED PLANS, MANY ARE |
| | MISSING. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE CWP IS |
| | NOT SHOWN AS PART OF THE MAIN GROUNDING |
| | ELETRODE SYSTEM AS REQUIRED PER 250.50, |
| | 250.64C |
| | |
| | **PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. SIZE ALL PER 250.66 |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE REDLINED |
| | PLANS FOR MISSING RECEPTS. |
| | |
| | ** PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE PLANS, THERE ARE NUMEROUS |
| | MISSING. |
| | PLEASE ALSO SEE "RAIL AREA" ON SECOND |
| | FLR IS CONSIDERED WALL SPACE AND WILL |
| | REQUIRED RECEPT(S). (FLR OUTLET) |
| | |
| | 7)NOTE: NOTE #7 OK. |
| | |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | HOWEVER PLEASE SEE NEW COMMENT FOR POOL |
| | PANEL. |
| | |
| | |
| | 9)NOTE: NOTE #9 NO, PLEASE SEE THIS IS |
| | STILL BEING SHOWN?? |
| | |
| | **PLEASE SEE 250.6,250.24, NO |
| | EQUIPMENT GROUNDING SHALL BE INSTALLED |
| | FROM METER TO MAIN. |
| | |
| | 10)NOTE: NOTE #10 NO, PLEASE SEE MISSING |
| | IN HALL AS REDLINED ON PLANS. |
| | |
| | ** PLEASE 210.52H FOR MISSING |
| | REQUIRED HALL RECEPTS. MORE THAN ONE |
| | LOCATION. |
| | |
| | 11)NOTE: NOTE #11 NO, PLEASE SEE AREAS |
| | WHERE ONLY A FAN IS BEING SHOWN FOR THE |
| | MIN OF EITHER A SWITCHED RECEPT OR LIGHT |
| | FIXTURE OF SOME SORT. |
| | |
| | **PLEASE SEE 210.70 FOR MISSING |
| | EGRESS LIGHTING CONTROL(S) IN MORE THAN |
| | ONE LOCATION. PLEASE ALSO SEE MISSING |
| | LIGHTING FOR GRADE LEVEL ACCES STAIRS. |
| | |
| | 12)NOTE: NOTE #12 NO, PLEASE SEE MISSING |
| | GFI RECEPT PENINSULAR. |
| | |
| | ** PLEASE SEE 210.52C-1-5 FOR |
| | RECEPTS REQUIRED IN KITCHENS ALONG |
| | COUNTERSPACES ETC. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16 OK. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18 NO, PLEASE SHOW |
| | CALCUALTIONS PER NEC. |
| | |
| | ** PLEASE SEE NEC FOR LOAD |
| | CALCULATIONS. |
| | PLEASE SUBMIT LOAD CALCULATIONS BASED ON |
| | MIN REQUIREMENTS UNDER 220.31 ETC. |
| | |
| | 19)NOTE: NOTE #19 OK, HOWEVER SEE NEW |
| | NOTE FOR POOL PANEL. |
| | |
| | |
| | 20)NOTE: NOTE #20, OK, HOWEVER PLEASE |
| | SEE NEW NOTE FOR MIN LOAD. |
| | |
| | ** PLEASE SEE MISSING |
| | LAUNDRY/WASHER CIRCUIT REQUIRED PER |
| | 220.16, 210.11C2 |
| | |
| | 21)NOTE: NOTE #21 OK. |
| | |
| | 22)NOTE: NOTE #22 OK, WALL ADDED. |
| | |
| | |
| | 23)NOTE: NOTE #23 NO, PLEASE SEE THIS |
| | COMMENT IS THE SAME AS BEFORE. PLEASE |
| | ALSO SEE NEW NOTES FOR SAID PLANS AND |
| | SET BEING RETAINED FOR POSSIBLE REVIEW |
| | BY THE STATE'S LEGAL COUNSEL. PLEASE SEE |
| | BOTH COMPANIES AS SHOWN DOES SEEM TO BE |
| | LICENSED AS REQUIRED AND NOTED ON |
| | PREVIOUS REVIEW AS REQUIRED UNDER |
| | FLORIDA STATUES. |
| | PLANS ARE NOW SIGNED. |
| | THIS COMMENT REMAINS FOR ALL TRADES AND |
| | ALL REVIEWER(S) WHETHER OR NOT COMMENT |
| | IS MADE BY OTHER(S). |
| | |
| | ** PLEASE SEE TITLE BLOCKS ARE |
| | MISSING LICENSE INFORMATION AS REQUIRED |
| | UNDER FAC 61G1-16.004 AND FS 481.219 |
| | PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM |
| | PAGE TO PAGE WITH DIFFERENT COMPANY NAME |
| | AND FIRMS SHOWN. |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | TRADES AND FOR ALL SHEETS WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | ** NEW NOTES** |
| | |
| | 1)NOTE: PLEASE CORRELAT EFLOORS WITH |
| | OTHER SHEETS. PLEASE SEE THE FIRST FLOOR |
| | IS NOTED AS THE "2ND FLR" THIS FLR |
| | CONTAINS THE GARAGE, POOL ETC. |
| | PLEASE ALSO ADJUST 2ND FLR, AS IT IS |
| | SHOWN AS FIRST FLR. |
| | |
| | 2)NOTE: PLEASE SEE ITEM(S) IN LOAD |
| | CALCUALTIONS AND NOT ON SCHEDULE OR |
| | PLANS. |
| | PLEASE SEE JACUZZI, ? PLEASE ALSO SEE |
| | 680.71 FOR GFI PROTECTION REQUIRED TO BE |
| | INDICATED. |
| | |
| | 3)NOTE: PLEASE SEE WASHER IS NOW LISTED, |
| | HOWEVER THE MIN KW RATING FOR |
| | WASHER/LAUNDRY CIRCUIT IS 1.5 KW. |
| | 220.16 |
| | |
| | 4)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH PANEL SCHEDULE. |
| | PLEASE SEE SMALL APPLIANCE CIRCUITS |
| | SHOWN WITH RECEPTS OUTSIDE, BATHS ETC. |
| | PLEASE SEE BATHS CIRCUITS SHOWN ON |
| | OTHERS AS PREVIOUSLY NOTED. |
| | PLEASE SEE SOME CIRCUIT(S) MISSING, |
| | PLEASE SEE SD'S ETC ETC. |
| | 215.5 |
| | MANY OF THESE ARE REDLINED ON PLANS. |
| | |
| | 5)NOTE: PLEASE REMOVE POOL PANEL OR |
| | LABLE AS "FUTURE". PLEASE KNOW, IF POOL |
| | IS PERMITTED DURING CONSTRUCTION OF MAIN |
| | HOUSE , THE PLANS WILL BE REQUIRED TO BE |
| | REVISED TO INCLUDE THIS. |
| | 215.5 |
| | |
| | 6)NOTE: PLEASE SEE FLORIDA STATUES |
| | SECTION 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONAL AND CODE COMPLIANT |
| | COMMENTS THREE OR MORE TIMES AND |
| | POSSIBLE 4X FEE ACCESSED TO DESIGN |
| | PROFESSIONALS. PLEASE KNOW THIS IS GIVEN |
| | ONLY A NOTICE ON THIS REVIEW. |
| | ** PLEASE KNOW, ONE SET OF PLANS ARE |
| | BEING RETAINED FOR FILE AS MENTIONED |
| | ABOVE. |
| | |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | PLEASE SEE DUE TO THE AMOUNT OF COMMENTS |
| | ,CODE CORRECTIONS NEEDED, AND MISSING |
| | INFORMATION FURTHER COMMENTS MAY BE |
| | POSSIBLE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |