Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-30 00:00:00*********** UNSAT2ND REVIEW *********
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
 ** PLEASE ALSO SEE NEW NOTES DUE TO
 CHANGES ON PLANS.
  
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR"PLAN REVIEW"AND NOT
 FOR PERMIT.
 PLEASE KNOW, AS OF OCT 1ST, 2005 THE FBC
 HAS CHANGED TO THE 2004. PLANS MUST
 CHANGE TO THE 2004 FBC WHEN SUBMITTED
 FOR PERMIT. THIS WILL AFFECT MANY AREAS
 OF PLANS.
 PLEASE ALSO KNOW A NEW PERMIT PROCESSING
 NUMBER MAY BE GIVEN.
  
  
  
 1)NOTE: NOTE #1, NO, PLEASE SEE RESPONSE
 LTR MENTIONS THIS WAS SUBMITTED, HOWEVER
 THIS COULD NOT BE LOCATED ON PLANS.
  
 **PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: NOTE #2 OK, HOWEVER PLEASE SEE
 NOTE #12.
  
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NEW
 COMMENT FOR CIRCUITING ON PLANS.
 PLEASE SEE THE REQUIRED DEDICATED BATH
 CIRCUIT IS SHOWN ON WITH OTHER RECEPTS
 ETC IN OTHER AREAS WHICH IS NOT
 PERMITTED.
  
 ** PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 APPEAR TO BE SHOWN AS 20A'S HOWEVER NO
 CONDUCTORS SIZES ARE SHOWN?
  
 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S
 WERE ADDED, HOWEVER PLEASE STILL SE
 MISSING SD'S AS REDLINED. THESE MUST BE
 INSIDE AND OUTSIDE ALL SLEEEPING RMS.
 PLEASE ALSO SEE SD'S ARE REQUIRED TO BE
 WIRED INLINEETC , HOWEVER PLEASE SEE
 SD'S ARE BEING SHOWN TO AT LEAST 6
 SEPARATE CIRCUITS????
  
 ** SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER: NFPA-72 11.5.1.1
 PLEASE SEE REDLINED PLANS, MANY ARE
 MISSING.
  
 5)NOTE: NOTE #5 NO, PLEASE SEE CWP IS
 NOT SHOWN AS PART OF THE MAIN GROUNDING
 ELETRODE SYSTEM AS REQUIRED PER 250.50,
 250.64C
  
 **PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: NOTE #6 NO, PLEASE SEE REDLINED
 PLANS FOR MISSING RECEPTS.
  
 ** PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE PLANS, THERE ARE NUMEROUS
 MISSING.
 PLEASE ALSO SEE "RAIL AREA" ON SECOND
 FLR IS CONSIDERED WALL SPACE AND WILL
 REQUIRED RECEPT(S). (FLR OUTLET)
  
 7)NOTE: NOTE #7 OK.
  
  
 8)NOTE: NOTE #8 OK.
 HOWEVER PLEASE SEE NEW COMMENT FOR POOL
 PANEL.
  
  
 9)NOTE: NOTE #9 NO, PLEASE SEE THIS IS
 STILL BEING SHOWN??
  
 **PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING SHALL BE INSTALLED
 FROM METER TO MAIN.
  
 10)NOTE: NOTE #10 NO, PLEASE SEE MISSING
 IN HALL AS REDLINED ON PLANS.
  
 ** PLEASE 210.52H FOR MISSING
 REQUIRED HALL RECEPTS. MORE THAN ONE
 LOCATION.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE AREAS
 WHERE ONLY A FAN IS BEING SHOWN FOR THE
 MIN OF EITHER A SWITCHED RECEPT OR LIGHT
 FIXTURE OF SOME SORT.
  
 **PLEASE SEE 210.70 FOR MISSING
 EGRESS LIGHTING CONTROL(S) IN MORE THAN
 ONE LOCATION. PLEASE ALSO SEE MISSING
 LIGHTING FOR GRADE LEVEL ACCES STAIRS.
  
 12)NOTE: NOTE #12 NO, PLEASE SEE MISSING
 GFI RECEPT PENINSULAR.
  
 ** PLEASE SEE 210.52C-1-5 FOR
 RECEPTS REQUIRED IN KITCHENS ALONG
 COUNTERSPACES ETC.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
 16)NOTE: NOTE #16 OK.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SHOW
 CALCUALTIONS PER NEC.
  
 ** PLEASE SEE NEC FOR LOAD
 CALCULATIONS.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON
 MIN REQUIREMENTS UNDER 220.31 ETC.
  
 19)NOTE: NOTE #19 OK, HOWEVER SEE NEW
 NOTE FOR POOL PANEL.
  
  
 20)NOTE: NOTE #20, OK, HOWEVER PLEASE
 SEE NEW NOTE FOR MIN LOAD.
  
 ** PLEASE SEE MISSING
 LAUNDRY/WASHER CIRCUIT REQUIRED PER
 220.16, 210.11C2
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK, WALL ADDED.
  
  
 23)NOTE: NOTE #23 NO, PLEASE SEE THIS
 COMMENT IS THE SAME AS BEFORE. PLEASE
 ALSO SEE NEW NOTES FOR SAID PLANS AND
 SET BEING RETAINED FOR POSSIBLE REVIEW
 BY THE STATE'S LEGAL COUNSEL. PLEASE SEE
 BOTH COMPANIES AS SHOWN DOES SEEM TO BE
 LICENSED AS REQUIRED AND NOTED ON
 PREVIOUS REVIEW AS REQUIRED UNDER
 FLORIDA STATUES.
 PLANS ARE NOW SIGNED.
 THIS COMMENT REMAINS FOR ALL TRADES AND
 ALL REVIEWER(S) WHETHER OR NOT COMMENT
 IS MADE BY OTHER(S).
  
 ** PLEASE SEE TITLE BLOCKS ARE
 MISSING LICENSE INFORMATION AS REQUIRED
 UNDER FAC 61G1-16.004 AND FS 481.219
 PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM
 PAGE TO PAGE WITH DIFFERENT COMPANY NAME
 AND FIRMS SHOWN.
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 ** NEW NOTES**
  
 1)NOTE: PLEASE CORRELAT EFLOORS WITH
 OTHER SHEETS. PLEASE SEE THE FIRST FLOOR
 IS NOTED AS THE "2ND FLR" THIS FLR
 CONTAINS THE GARAGE, POOL ETC.
 PLEASE ALSO ADJUST 2ND FLR, AS IT IS
 SHOWN AS FIRST FLR.
  
 2)NOTE: PLEASE SEE ITEM(S) IN LOAD
 CALCUALTIONS AND NOT ON SCHEDULE OR
 PLANS.
 PLEASE SEE JACUZZI, ? PLEASE ALSO SEE
 680.71 FOR GFI PROTECTION REQUIRED TO BE
 INDICATED.
  
 3)NOTE: PLEASE SEE WASHER IS NOW LISTED,
 HOWEVER THE MIN KW RATING FOR
 WASHER/LAUNDRY CIRCUIT IS 1.5 KW.
 220.16
  
 4)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULE.
 PLEASE SEE SMALL APPLIANCE CIRCUITS
 SHOWN WITH RECEPTS OUTSIDE, BATHS ETC.
 PLEASE SEE BATHS CIRCUITS SHOWN ON
 OTHERS AS PREVIOUSLY NOTED.
 PLEASE SEE SOME CIRCUIT(S) MISSING,
 PLEASE SEE SD'S ETC ETC.
 215.5
 MANY OF THESE ARE REDLINED ON PLANS.
  
 5)NOTE: PLEASE REMOVE POOL PANEL OR
 LABLE AS "FUTURE". PLEASE KNOW, IF POOL
 IS PERMITTED DURING CONSTRUCTION OF MAIN
 HOUSE , THE PLANS WILL BE REQUIRED TO BE
 REVISED TO INCLUDE THIS.
 215.5
  
 6)NOTE: PLEASE SEE FLORIDA STATUES
 SECTION 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONAL AND CODE COMPLIANT
 COMMENTS THREE OR MORE TIMES AND
 POSSIBLE 4X FEE ACCESSED TO DESIGN
 PROFESSIONALS. PLEASE KNOW THIS IS GIVEN
 ONLY A NOTICE ON THIS REVIEW.
 ** PLEASE KNOW, ONE SET OF PLANS ARE
 BEING RETAINED FOR FILE AS MENTIONED
 ABOVE.
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SEE DUE TO THE AMOUNT OF COMMENTS
 ,CODE CORRECTIONS NEEDED, AND MISSING
 INFORMATION FURTHER COMMENTS MAY BE
 POSSIBLE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW