2006-02-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ***PLAN CHECK ONLY***
  
 GOVERNING CODE IS FBC2004 EFFECTIVE
 OCTOBER 1, 2005.NO PERMIT WAS APPLIED
 FOR PRIOR TO THIS DATE.REVISE ALL
 INCORRECT CODE REFERENCES.
  
 COMMENTS FROM THE PREVIOUS REVIEW;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 5.)THE ARCHITECT FIRM IS TO HAVE A CA
 NUMBER.TITLE BLOCK TO BE IN
 CONFORMANCE WITH FAC61G1-16.003,004.
  
 NOT ADDRESSED.NO CA NUMBER PROVIDED
 FOR FLORIDA KEY WEST DESIGN OR FLORIDA
 DESIGN ARCHITECTS.A COPY OF THE TITLE
 BLOCKS HAVE BEEN SENT TO THE ATTORNEY
 FOR THE FLORIDA BOARD OF ARCHITECTS.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
  
 ENERGY CALCS WERE SUBMITTED.THE
 CEILING/FLOOR ASSEMBLY BETWEEN THE
 UNCONDITIONED GARAGE AREA AND THE
 CONDITIONED SECOND FLOOR IS NOT ON THE
 ENERGY CALCS, FIRST PAGE.SECOND PAGE
 SHOWS RAISED WOOD FLOOR ADJACENT, PLANS
 SHOW CONCRETE FLOOR.THE PLAN DOES NOT
 SHOW INSULATION BETWEEN THE LAUNDRY AREA
 IN THE GARAGE AND THE UTILITY ROOM.
 INSULATION IS SHOWN GRAPHICALLY ON A2.0
 BETWEEN FIRST AND SECOND FLOOR.
 INSULATION SHOWN GRAPHICALLY BETWEEN
 GARAGE AND ENTRY.PLEASE SPECIFY.THE
 WOOD FRAME WALL IS NOT INCLUDED IN THE
 ENERGY CALCS.
  
 7.)THE WIND RESISTANCE NOTES ON T1
 WERE PREPARED BY ANOTHER DESIGN
 PROFESSIONAL, MAKES REFERENCE TO A
 COMMERCIAL STRUCTURE, AND STATE THAT
 THIS IS A PARTIALLY ENCLOSED BUILDING
 WHICH IS NOT TO BE SHUTTERED.OTHER
 SHEETS SPECIFY IMPACT GLASS.PLEASE
 CLARIFY.
  
 SHEET T1 STILL STATES THAT THIS IS A
 PARTIALLY ENCLOSED STRUCTURE.SEE
 FBC1609.2.
  
 8.)ADDRESSED.
  
 9.)ADDRESSED.
  
 10.)ADDRESSED.
  
 11.)LOCAL OR STATE PRODUCT APPROVAL
 REQUIRED FOR:
 SHINGLE OR METAL ROOF
 WINDOWS
 MULLIONS
 FIXED GLASS WINDOWS
 FRENCH DOORS
 CASEMENT WINDOW
 OVERHEAD DOOR
 SKYLIGHTS
 IMPACT PROTECTION IF REQUIRED
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS REQUIRED IN ADDITION TO THE
 FLORIDA OR LOCAL PRODUCT APPROVAL.
  
 SEPARATE PERMITS WILL BE REQUIRED FOR
 ANY PRODUCT APPROVALS NOT PROPERLY
 SUBMITTED AND REVIEWED PRIOR TO
 ISSUANCE.
  
 NONE SUBMITTED.PRODUCT APPROVALS TO BE
 REVIEWED BY DESIGNER OF RECORD
 FBC*106.3.3.
  
 12.)PLEASE READ FBC35 IN REGARDS TO
 STANDARDS.YOU MAKE REFERENCE TO
 ACI318-63 ON SHEET A3.(ALSO SPECIFIES
 300PSI CONCRETE.)THAT REFERENCE IS
 VERY OUTDATED.CHECK ALL REFERENCES.
  
 NOT ADDRESSED.PLANS STILL STATE
 ACI318-63.CHECK ALL REFERENCES.
  
 13.)ADDRESSED.
  
 14.)PROVIDE DESIGN CRITERIA REQUIRED
 BY FBC1606.1.7.NO DESIGN PRESSURES FOR
 ROOF OR COMPONENTS AND CLADDING WERE
 PROVIDED.
  
 NOT ADDRESSED.WIND SPEED AND EXPOSURE
 PROVIDED, NO COMPONENTS AND CLADDING
 DESIGN PRESSURES AND PLANS STILL STATE
 THAT THIS IS A PARTIALLY ENCLOSED
 STRUCTURE.
  
 15.)A7.0 SPECIFIES HUGHES CONNECTORS.
 THEY HAVE BEEN OUT OF BUSINESS FOR MANY
 YEARS.SPECIFY AVAILABLE, CODE
 COMPLIANT PRODUCTS ONLY.
  
 SWITCHED TO SIMPSON, BUT I AM UNABLE TO
 FIND TA STRAPS IN THE SIMPSON CATALOG.
  
 16.)A7.0 MAKES REFERENCE TO BOCA 1996.
 GOVERNING CODE IS FBC2001.
  
 NOT ADDRESSED.BOCA CODE REFERENCE
 STILL ON THE PLAN.GOVERNING CODE IS
 NOW FBC2004.
  
 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING
 NOTES, ITEM 2 (NAILING PATTERN 6IN
 EDGES,
 6IN FIELD) IS NON COMPLIANT, SEE
 FBC*TABLE 2306.1.THE RESPONSE LETTER
 STATES THAT THE SHEATHING NAILING WAS
 CORRECTED TO 6IN OC EDGES AND 12IN OC
 FIELD.
  
 NOT ADDRESSED.STILL STATES 6/6.6/12
 WAS SPECIFIED IN THE RESPONSE LETTER.
 THIS IS ALSO NOT CODE COMPLIANT.SEE
 FBC TABLE 2304.9.1.
  
 18.)PROVIDE A WALL SECTION CONTINUOUS
 FOUNDATION THROUGH ROOF, INCLUDING GRADE
 IN RELATION TO FINISH FLOOR AND BOTTOM
 OF FOOTER, FBC*104.3.1.1, FBC*1804.1.7.
  
 NOT ADDRESSED.NO INFORMATION GIVEN IN
 REGARDS TO THE FIRST FLOOR BEAM.
  
 19.)WATERSTOP REQUIRED FBC2111.1.9,
 FIRST AND SECOND FLOOR.
  
 NOT ADDRESSED.THIS SHOULD BE SHOWN ON
 THE WALL SECTION WHICH WAS NOT PROVIDED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL.
  
 21.)PROVIDE A STRUCTURAL DETAIL FOR
 THE BAY WINDOWS.
  
 NOT ADDRESSED.A CROSS SECTION WAS
 PROVIDED SHOWING THE STAIR AND BAY
 WINDOW.THIS IS NOT A STRUCTURAL DETAIL
 AS SPACING, FASTENING, DESIGN LOADS WERE
 NOT PROVIDED.
  
 22.)ADDRESSED.
  
 23.) PROVIDE CALCULATIONS FOR THE FILLED
 CELLS SET AT EVERY 10FT.
  
 RESPONSE LETTER STATES THAT THEY WILL BE
 EVERY 8FT, BUT THE NOTE ON A3 STATES
 10FT.2ND FLOOR, BEDROOM 3 HAS A
 DISTANCE OF OVER 12FT.
  
 24.)ADDRESSED.
  
 25.)PROVIDE WINDOW AND DOOR BUCK
 DETAILS.
  
 NOT ADDRESSED.
  
 26.)ADDRESSED.
 26.)ADDRESSED.
  
 27.)SPECIFY INSULATION FOR THE
 ADJACENT WALL (BETWEEN GARAGE AND ENTRY
 HALL).
  
 NOT ADDRESSED.SHOWN GRAPHICALLY BUT
 NOT SPECIFIED.ALSO NEEDS INSULATION
 BETWEEN THE GARAGE AND UTILITY ROOM.
  
 28.)ADDRESSED.
  
 29.)ADDRESSED.
  
 30.)APPARENTLY ADDRESSED.
  
 31.)ADDRESSED.
  
 32.)DETAILS SHOWN ON A6.0 ARE NOT
 CLEAR.COMPLETE DIMENSIONS AND
 MATERIALS ARE NOT SHOWN.
  
 AS OLD SHEETS NOT SUBMITTED, UNSURE AS
 TO WHAT THIS COMMENT REFERRED TO.
  
 31.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, WITH ALL DIMENSIONS,
 INCLUDING THE LANDING AND FIREBLOCKING
 FBC2305.1.4(3).
  
 NOT ADDRESSED.
  
 32.)SHOW ATTIC ACCESS LOCATIONS AND
 SIZE FBC2309.
  
 SPECIFY SIZE.
  
 33.)SAFETY GLASS REQUIRED AT TUBS AND
 SHOWER, FBC2405.1.
  
 ADDRESSED IF IMPACT WINDOWS ARE USED AS
 PER PLAN.
  
 34.)THE CANTILEVERED BALCONY DETAIL A6
 DOES NOT HAVE A SLAB DIMENSION.
  
 NOT ADDRESSED.
  
 35.)SPECIFY SOFFIT VENTING AND SHOW
 COMPLIANCE FBC2309.7.
  
 NOT ADDRESSED.
  
 36.)SPECIFY REACTION LOADS ON THE ROOF
 FRAMING PLAN A7.0.
  
 NOT ADDRESSED.
  
 37.)PROVIDE CALCULATIONS FOR THE BOND
 BEAM, ONE 8X8 WITH TWO #4S.
  
 NOT ADDRESSED.STILL SHOWS ONE 8X8 WITH
 TWO #4S.
  
 38.)PROVIDE DESIGN CRITERIA FOR
 HANDRAILS AND GUARDRAILS, FBC1608.2,
 FBC1007, FBC1015.STAIR DETAIL
 DIFFICULT TO READ.THE RAILING CANNOT
 BE 34", FBC1015, FBC1026.5.
  
 PROVIDE A DETAIL FOR THE RAILINGS.NOT
 ADDRESSED.
  
 39.)PROPERTY APPRAISER'S WEBSITE SHOW
 TWO LOTS WITH THIS ADDRESS, EACH WITH A
 STRUCTURE ON IT.PLEASE CLARIFY.
  
 THE PLANS SHOW TWO ADDRESSES.ADDRESS
 ON THE PLAN IS TO BE ONE ADDRESS ONLY
 WHICH SHOULD MATCH THE APPLICATION.
  
 40.) REINFORCEMENT ABOVE OPENINGS HAS
 NOT BEEN SPECIFIED.PROVIDE A SCHEDULE.
  
 ADDRESSED BY STATING THAT LINTELS WILL
 BE INSTALLED.SEE COMMENT 46 BELOW.
  
 41.) A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 ***NEW COMMENTS***
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 43.)PLANS SHOW AN ADDRESS OF 425 AND
 423 WILDER.APPLICATION IS FOR 423
 WILDER.
  
 44.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY INDICATED WITH A CLOUD AND
 REVISION NUMBER.AS NONE OF THE CHANGES
 WERE CLOUDED AND OLD SHEETS WERE NOT
 SUBMITTED, THIS REQUIRED A COMPLETELY
 NEW PLAN REVIEW.TO AVOID DELAYS,
 CLEARLY INDICATE ALL CHANGES AND SUBMIT
 OLD SHEETS AS IS STANDARD INDUSTRY
 PRACTICE.
  
 45.)A WOOD LOUVER IS SHOWN ON THE LEFT
 SIDE ELEVATION, HAND WRITTEN ON THE
 PLAN.PROVIDE A STRUCTURAL DETAIL AS TO
 HOW THIS WILL BE BUILT AND COMPLY WITH
 THE WIND PROVISIONS OF FBC16.
  
 46.)PROVIDE INFORMATION IN REGARDS TO
 THE BEAM ABOVE THE GARAGE DOOR.YOU
 HAVE A 16? SPAN SUPPORTING CONCRETE
 FLOOR JOISTS, A CONCRETE BALCONY AND A
 CONCRETE BLOCK 2ND FLOOR WITH NO
 STRUCTURAL INFORMATION AS TO HOW THIS
 WILL BE ACCOMPLISHED.THERE IS A NOTE
 STATING THAT LINTELS WILL GO OVER ALL
 OPENINGS.PROVIDE MORE INFORMATION.
  
 47.)PROVIDE A DETAIL FOR THE BEARING
 WALL, INTERIOR NON BEARING WALLS, AND
 THE CABANA WALL.
  
  