| 2006-02-10 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ***PLAN CHECK ONLY*** |
| | |
| | GOVERNING CODE IS FBC2004 EFFECTIVE |
| | OCTOBER 1, 2005.NO PERMIT WAS APPLIED |
| | FOR PRIOR TO THIS DATE.REVISE ALL |
| | INCORRECT CODE REFERENCES. |
| | |
| | COMMENTS FROM THE PREVIOUS REVIEW; |
| | NUMBERING TO REMAIN THE SAME FOR |
| | CONSISTENCY.NOTE THAT CODE REFERENCE |
| | NUMBERS HAVE CHANGED AS THE FIRST REVIEW |
| | WAS DONE ON FBC2001, SECOND REVIEW ON |
| | FBC2004. |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)ADDRESSED. |
| | |
| | 5.)THE ARCHITECT FIRM IS TO HAVE A CA |
| | NUMBER.TITLE BLOCK TO BE IN |
| | CONFORMANCE WITH FAC61G1-16.003,004. |
| | |
| | NOT ADDRESSED.NO CA NUMBER PROVIDED |
| | FOR FLORIDA KEY WEST DESIGN OR FLORIDA |
| | DESIGN ARCHITECTS.A COPY OF THE TITLE |
| | BLOCKS HAVE BEEN SENT TO THE ATTORNEY |
| | FOR THE FLORIDA BOARD OF ARCHITECTS. |
| | |
| | 6.)ENERGY CALCS REQUIRED, FBC11-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC, FBC11-103.1.2. |
| | |
| | |
| | ENERGY CALCS WERE SUBMITTED.THE |
| | CEILING/FLOOR ASSEMBLY BETWEEN THE |
| | UNCONDITIONED GARAGE AREA AND THE |
| | CONDITIONED SECOND FLOOR IS NOT ON THE |
| | ENERGY CALCS, FIRST PAGE.SECOND PAGE |
| | SHOWS RAISED WOOD FLOOR ADJACENT, PLANS |
| | SHOW CONCRETE FLOOR.THE PLAN DOES NOT |
| | SHOW INSULATION BETWEEN THE LAUNDRY AREA |
| | IN THE GARAGE AND THE UTILITY ROOM. |
| | INSULATION IS SHOWN GRAPHICALLY ON A2.0 |
| | BETWEEN FIRST AND SECOND FLOOR. |
| | INSULATION SHOWN GRAPHICALLY BETWEEN |
| | GARAGE AND ENTRY.PLEASE SPECIFY.THE |
| | WOOD FRAME WALL IS NOT INCLUDED IN THE |
| | ENERGY CALCS. |
| | |
| | 7.)THE WIND RESISTANCE NOTES ON T1 |
| | WERE PREPARED BY ANOTHER DESIGN |
| | PROFESSIONAL, MAKES REFERENCE TO A |
| | COMMERCIAL STRUCTURE, AND STATE THAT |
| | THIS IS A PARTIALLY ENCLOSED BUILDING |
| | WHICH IS NOT TO BE SHUTTERED.OTHER |
| | SHEETS SPECIFY IMPACT GLASS.PLEASE |
| | CLARIFY. |
| | |
| | SHEET T1 STILL STATES THAT THIS IS A |
| | PARTIALLY ENCLOSED STRUCTURE.SEE |
| | FBC1609.2. |
| | |
| | 8.)ADDRESSED. |
| | |
| | 9.)ADDRESSED. |
| | |
| | 10.)ADDRESSED. |
| | |
| | 11.)LOCAL OR STATE PRODUCT APPROVAL |
| | REQUIRED FOR: |
| | SHINGLE OR METAL ROOF |
| | WINDOWS |
| | MULLIONS |
| | FIXED GLASS WINDOWS |
| | FRENCH DOORS |
| | CASEMENT WINDOW |
| | OVERHEAD DOOR |
| | SKYLIGHTS |
| | IMPACT PROTECTION IF REQUIRED |
| | TEST REPORT AND INSTALLATION |
| | INSTRUCTIONS REQUIRED IN ADDITION TO THE |
| | FLORIDA OR LOCAL PRODUCT APPROVAL. |
| | |
| | SEPARATE PERMITS WILL BE REQUIRED FOR |
| | ANY PRODUCT APPROVALS NOT PROPERLY |
| | SUBMITTED AND REVIEWED PRIOR TO |
| | ISSUANCE. |
| | |
| | NONE SUBMITTED.PRODUCT APPROVALS TO BE |
| | REVIEWED BY DESIGNER OF RECORD |
| | FBC*106.3.3. |
| | |
| | 12.)PLEASE READ FBC35 IN REGARDS TO |
| | STANDARDS.YOU MAKE REFERENCE TO |
| | ACI318-63 ON SHEET A3.(ALSO SPECIFIES |
| | 300PSI CONCRETE.)THAT REFERENCE IS |
| | VERY OUTDATED.CHECK ALL REFERENCES. |
| | |
| | NOT ADDRESSED.PLANS STILL STATE |
| | ACI318-63.CHECK ALL REFERENCES. |
| | |
| | 13.)ADDRESSED. |
| | |
| | 14.)PROVIDE DESIGN CRITERIA REQUIRED |
| | BY FBC1606.1.7.NO DESIGN PRESSURES FOR |
| | ROOF OR COMPONENTS AND CLADDING WERE |
| | PROVIDED. |
| | |
| | NOT ADDRESSED.WIND SPEED AND EXPOSURE |
| | PROVIDED, NO COMPONENTS AND CLADDING |
| | DESIGN PRESSURES AND PLANS STILL STATE |
| | THAT THIS IS A PARTIALLY ENCLOSED |
| | STRUCTURE. |
| | |
| | 15.)A7.0 SPECIFIES HUGHES CONNECTORS. |
| | THEY HAVE BEEN OUT OF BUSINESS FOR MANY |
| | YEARS.SPECIFY AVAILABLE, CODE |
| | COMPLIANT PRODUCTS ONLY. |
| | |
| | SWITCHED TO SIMPSON, BUT I AM UNABLE TO |
| | FIND TA STRAPS IN THE SIMPSON CATALOG. |
| | |
| | 16.)A7.0 MAKES REFERENCE TO BOCA 1996. |
| | GOVERNING CODE IS FBC2001. |
| | |
| | NOT ADDRESSED.BOCA CODE REFERENCE |
| | STILL ON THE PLAN.GOVERNING CODE IS |
| | NOW FBC2004. |
| | |
| | 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING |
| | NOTES, ITEM 2 (NAILING PATTERN 6IN |
| | EDGES, |
| | 6IN FIELD) IS NON COMPLIANT, SEE |
| | FBC*TABLE 2306.1.THE RESPONSE LETTER |
| | STATES THAT THE SHEATHING NAILING WAS |
| | CORRECTED TO 6IN OC EDGES AND 12IN OC |
| | FIELD. |
| | |
| | NOT ADDRESSED.STILL STATES 6/6.6/12 |
| | WAS SPECIFIED IN THE RESPONSE LETTER. |
| | THIS IS ALSO NOT CODE COMPLIANT.SEE |
| | FBC TABLE 2304.9.1. |
| | |
| | 18.)PROVIDE A WALL SECTION CONTINUOUS |
| | FOUNDATION THROUGH ROOF, INCLUDING GRADE |
| | IN RELATION TO FINISH FLOOR AND BOTTOM |
| | OF FOOTER, FBC*104.3.1.1, FBC*1804.1.7. |
| | |
| | NOT ADDRESSED.NO INFORMATION GIVEN IN |
| | REGARDS TO THE FIRST FLOOR BEAM. |
| | |
| | 19.)WATERSTOP REQUIRED FBC2111.1.9, |
| | FIRST AND SECOND FLOOR. |
| | |
| | NOT ADDRESSED.THIS SHOULD BE SHOWN ON |
| | THE WALL SECTION WHICH WAS NOT PROVIDED. |
| | |
| | 20.)WHAT IS THE CONSTRUCTION OF THE |
| | CABANA WALLS?IT DOES NOT APPEAR TO BE |
| | BLOCK.PROVIDE A DETAIL. |
| | |
| | 21.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE BAY WINDOWS. |
| | |
| | NOT ADDRESSED.A CROSS SECTION WAS |
| | PROVIDED SHOWING THE STAIR AND BAY |
| | WINDOW.THIS IS NOT A STRUCTURAL DETAIL |
| | AS SPACING, FASTENING, DESIGN LOADS WERE |
| | NOT PROVIDED. |
| | |
| | 22.)ADDRESSED. |
| | |
| | 23.) PROVIDE CALCULATIONS FOR THE FILLED |
| | CELLS SET AT EVERY 10FT. |
| | |
| | RESPONSE LETTER STATES THAT THEY WILL BE |
| | EVERY 8FT, BUT THE NOTE ON A3 STATES |
| | 10FT.2ND FLOOR, BEDROOM 3 HAS A |
| | DISTANCE OF OVER 12FT. |
| | |
| | 24.)ADDRESSED. |
| | |
| | 25.)PROVIDE WINDOW AND DOOR BUCK |
| | DETAILS. |
| | |
| | NOT ADDRESSED. |
| | |
| | 26.)ADDRESSED. |
| | 26.)ADDRESSED. |
| | |
| | 27.)SPECIFY INSULATION FOR THE |
| | ADJACENT WALL (BETWEEN GARAGE AND ENTRY |
| | HALL). |
| | |
| | NOT ADDRESSED.SHOWN GRAPHICALLY BUT |
| | NOT SPECIFIED.ALSO NEEDS INSULATION |
| | BETWEEN THE GARAGE AND UTILITY ROOM. |
| | |
| | 28.)ADDRESSED. |
| | |
| | 29.)ADDRESSED. |
| | |
| | 30.)APPARENTLY ADDRESSED. |
| | |
| | 31.)ADDRESSED. |
| | |
| | 32.)DETAILS SHOWN ON A6.0 ARE NOT |
| | CLEAR.COMPLETE DIMENSIONS AND |
| | MATERIALS ARE NOT SHOWN. |
| | |
| | AS OLD SHEETS NOT SUBMITTED, UNSURE AS |
| | TO WHAT THIS COMMENT REFERRED TO. |
| | |
| | 31.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS, WITH ALL DIMENSIONS, |
| | INCLUDING THE LANDING AND FIREBLOCKING |
| | FBC2305.1.4(3). |
| | |
| | NOT ADDRESSED. |
| | |
| | 32.)SHOW ATTIC ACCESS LOCATIONS AND |
| | SIZE FBC2309. |
| | |
| | SPECIFY SIZE. |
| | |
| | 33.)SAFETY GLASS REQUIRED AT TUBS AND |
| | SHOWER, FBC2405.1. |
| | |
| | ADDRESSED IF IMPACT WINDOWS ARE USED AS |
| | PER PLAN. |
| | |
| | 34.)THE CANTILEVERED BALCONY DETAIL A6 |
| | DOES NOT HAVE A SLAB DIMENSION. |
| | |
| | NOT ADDRESSED. |
| | |
| | 35.)SPECIFY SOFFIT VENTING AND SHOW |
| | COMPLIANCE FBC2309.7. |
| | |
| | NOT ADDRESSED. |
| | |
| | 36.)SPECIFY REACTION LOADS ON THE ROOF |
| | FRAMING PLAN A7.0. |
| | |
| | NOT ADDRESSED. |
| | |
| | 37.)PROVIDE CALCULATIONS FOR THE BOND |
| | BEAM, ONE 8X8 WITH TWO #4S. |
| | |
| | NOT ADDRESSED.STILL SHOWS ONE 8X8 WITH |
| | TWO #4S. |
| | |
| | 38.)PROVIDE DESIGN CRITERIA FOR |
| | HANDRAILS AND GUARDRAILS, FBC1608.2, |
| | FBC1007, FBC1015.STAIR DETAIL |
| | DIFFICULT TO READ.THE RAILING CANNOT |
| | BE 34", FBC1015, FBC1026.5. |
| | |
| | PROVIDE A DETAIL FOR THE RAILINGS.NOT |
| | ADDRESSED. |
| | |
| | 39.)PROPERTY APPRAISER'S WEBSITE SHOW |
| | TWO LOTS WITH THIS ADDRESS, EACH WITH A |
| | STRUCTURE ON IT.PLEASE CLARIFY. |
| | |
| | THE PLANS SHOW TWO ADDRESSES.ADDRESS |
| | ON THE PLAN IS TO BE ONE ADDRESS ONLY |
| | WHICH SHOULD MATCH THE APPLICATION. |
| | |
| | 40.) REINFORCEMENT ABOVE OPENINGS HAS |
| | NOT BEEN SPECIFIED.PROVIDE A SCHEDULE. |
| | |
| | ADDRESSED BY STATING THAT LINTELS WILL |
| | BE INSTALLED.SEE COMMENT 46 BELOW. |
| | |
| | 41.) A COPY OF THE PLANS HAS BEEN |
| | RETAINED. |
| | |
| | ***NEW COMMENTS*** |
| | |
| | 42.)SHOW POSITIVE DRAINAGE FBC R401.3, |
| | FBC*109.3.10. |
| | |
| | 43.)PLANS SHOW AN ADDRESS OF 425 AND |
| | 423 WILDER.APPLICATION IS FOR 423 |
| | WILDER. |
| | |
| | 44.)ALL CHANGES TO THE PLAN ARE TO BE |
| | CLEARLY INDICATED WITH A CLOUD AND |
| | REVISION NUMBER.AS NONE OF THE CHANGES |
| | WERE CLOUDED AND OLD SHEETS WERE NOT |
| | SUBMITTED, THIS REQUIRED A COMPLETELY |
| | NEW PLAN REVIEW.TO AVOID DELAYS, |
| | CLEARLY INDICATE ALL CHANGES AND SUBMIT |
| | OLD SHEETS AS IS STANDARD INDUSTRY |
| | PRACTICE. |
| | |
| | 45.)A WOOD LOUVER IS SHOWN ON THE LEFT |
| | SIDE ELEVATION, HAND WRITTEN ON THE |
| | PLAN.PROVIDE A STRUCTURAL DETAIL AS TO |
| | HOW THIS WILL BE BUILT AND COMPLY WITH |
| | THE WIND PROVISIONS OF FBC16. |
| | |
| | 46.)PROVIDE INFORMATION IN REGARDS TO |
| | THE BEAM ABOVE THE GARAGE DOOR.YOU |
| | HAVE A 16? SPAN SUPPORTING CONCRETE |
| | FLOOR JOISTS, A CONCRETE BALCONY AND A |
| | CONCRETE BLOCK 2ND FLOOR WITH NO |
| | STRUCTURAL INFORMATION AS TO HOW THIS |
| | WILL BE ACCOMPLISHED.THERE IS A NOTE |
| | STATING THAT LINTELS WILL GO OVER ALL |
| | OPENINGS.PROVIDE MORE INFORMATION. |
| | |
| | 47.)PROVIDE A DETAIL FOR THE BEARING |
| | WALL, INTERIOR NON BEARING WALLS, AND |
| | THE CABANA WALL. |
| | |
| | |