| 2005-05-03 00:00:00 | ************* UNSAT ****************** |
| | |
| | PLANS SUBMITTED FOR "PLAN REVIEW ONLY |
| | AND NOT SUBMITTED FOR PERMIT. |
| | REVIEW FOR A NEW SFR. |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 3)NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | APPEAR TO BE SHOWN AS 20A'S HOWEVER NO |
| | CONDUCTORS SIZES ARE SHOWN? |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE REDLINED PLANS, MANY ARE |
| | MISSING. |
| | |
| | 5)NOTE: PLEASE SHOW GROUNDING ELETRODE |
| | SYSTEM PER 250.50. FOOTER STEEL/COLD |
| | WATER/ ETC. SIZE ALL PER 250.66 |
| | |
| | 6)NOTE: PLEASE SHOW OUTLET SPACING PER |
| | 210.52. 2',6`,12` RULE. |
| | PLEASE SEE PLANS, THERE ARE NUMEROUS |
| | MISSING. |
| | PLEASE ALSO SEE "RAIL AREA" ON SECOND |
| | FLR IS CONSIDERED WALL SPACE AND WILL |
| | REQUIRED RECEPT(S). (FLR OUTLET) |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 8)NOTE: PLEASE CORRELATE RISER DIGRAM(S |
| | WITH PANEL SCHEDULE(S) AND PLANS. |
| | PLANS INDICATE MULTIPLE PANELS A&B AND |
| | MSB. PLEASE SEE NO PANEL SCHEDULE |
| | SUBMITTED FOR PANEL "C". PLEASE SEE |
| | THERE ARE NUMEROUS ITEMS THAT DO NOT |
| | CORRELATE SERVICE AND PLANS. |
| | |
| | 9)NOTE: PLEASE SEE 250.6,250.24, NO |
| | EQUIPMENT GROUNDING SHALL BE INSTALLED |
| | FROM METER TO MAIN. |
| | |
| | 10)NOTE: PLEASE 210.52H FOR MISSING |
| | REQUIRED HALL RECEPTS. MORE THAN ONE |
| | LOCATION. |
| | |
| | 11)NOTE: PLEASE SEE 210.70 FOR MISSING |
| | EGRESS LIGHTING CONTROL(S) IN MORE THAN |
| | ONE LOCATION. PLEASE ALSO SEE MISSING |
| | LIGHTING FOR GRADE LEVEL ACCES STAIRS. |
| | |
| | 12)NOTE: PLEASE SEE 210.52C-1-5 FOR |
| | RECEPTS REQUIRED IN KITCHENS ALONG |
| | COUNTERSPACES ETC. |
| | |
| | 13)NOTE: PLEASE SHOW ALL OUTSIDE, GARAGE |
| | RECEPTS ETC AS GFI/ GFI PROTECTED. |
| | 210.8B3 |
| | |
| | 14)NOTE: PLEASE SEE MISSING ISCONNECTS |
| | FOR A/C EQUIPMENT.440.11 |
| | |
| | 15)NOTE: PLEASE CORRELATE LOAD |
| | CALCAULTIONS AND PANEL SCHEDULES FOR A/C |
| | EQUIPMENT. SHOWN AT 5KW. 7.5 KW, 10 KW |
| | ?? |
| | ETC ETC. |
| | |
| | 16)NOTE: PLEASE INCLUDE ALL CONDUCTOR |
| | SIZES ON PANEL SCHEDULES AND CORRELATE |
| | WITH THE OCP SHOWN. |
| | 310.16,240.4 |
| | |
| | 17)NOTE: PLEASE SEE 210.11C1 FOR MISSING |
| | REQUIRED SMALL APPLIANCE CIRCUITS. |
| | PLEASE SEE LOAD CALCS INDICATE TWO, |
| | HOWEVERONE SHOWN AT 1.5KW AND THE |
| | OTHER AT 1.2? PLEASE SEE MIN OF 1.5KW IS |
| | REQUIRED PER 220.16, 210.11C1 PLEASE |
| | ALSO SEE PANEL SCHEDULES DO NOT INDICATE |
| | SMALL APPLIANCE CIRCUITS?? |
| | |
| | 18)NOTE: PLEASE SEE NEC FOR LOAD |
| | CALCULATIONS. |
| | PLEASE SUBMIT LOAD CALCULATIONS BASED ON |
| | MIN REQUIREMENTS UNDER 220.31 ETC. |
| | |
| | 19)NOTE: PLEASE SEE POOL HEATER MAY NOT |
| | BE DERATED AT 65% AS THIS LOAD IS A |
| | CONTINUOUS LOAD (3 OR MORE) HOURS AND |
| | MUST BE SHOWN AT 125% ALONG WITH LARGEST |
| | MPTORS LOADS. POOL PUMP IS ALSO 125% FOR |
| | A CONT LOAD.215.3, 230.42 ETC. |
| | |
| | 20)NOTE: PLEASE SEE MISSING |
| | LAUNDRY/WASHER CIRCUIT REQUIRED PER |
| | 220.16, 210.11C2 |
| | |
| | 21)NOTE: PLEASE SEE THERE ARE THREE A/C |
| | SYSTEMS SHOWN ON PANEL SCHEDULE, |
| | HOWEVER, LOAD CALCS ONLY SHOWN 2??? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 22)NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARENCES REQUIRED FOR A/C, AHU DISC'S. |
| | PLEASE ALSO SEE OCP IS NOT PERMITTED IN |
| | CLOTHES/ STORAGE CLOSETS.240.24D ETC |
| | |
| | 23)NOTE: PLEASE SEE TITLE BLOCKS ARE |
| | MISSING LICENSE INFORMATION AS REQUIRED |
| | UNDER FAC 61G1-16.004 AND FS 481.219 |
| | PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM |
| | PAGE TO PAGE WITH DIFFERENT COMPANY NAME |
| | AND FIRMS SHOWN. |
| | PLEASE SEE PLANS ALSO APPEAR TO BE |
| | "SIGNED" WITH INITIALS WHICH ARE NOT |
| | ACCEPTABLE. IF INDEED THIS IS THE "LEGAL |
| | SIGNATURE" OF ARCH, PLEASE SUBMIT A |
| | SIGNED, DATED SEALED AND NOTORTIZED |
| | LETTER STATING LEGAL SIGNATURE. |
| | FS 481.221 |
| | PLEASE SEE THIS COMMENT IS FOR ALL |
| | TRADES AND FOR ALL SHEETS WHEATHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | PLEASE SEE DUE TO THE AMOUNT OF COMMENTS |
| | ,CODE CORRECTIONS NEEDED, AND MISSING |
| | INFORMATION FURTHER COMMENTS MAY BE |
| | POSSIBLE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |