Plan Review Notes
Plan Review Notes For Permit 05041961
Permit Number 05041961
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00************* UNSAT ******************
  
 PLANS SUBMITTED FOR "PLAN REVIEW ONLY
 AND NOT SUBMITTED FOR PERMIT.
 REVIEW FOR A NEW SFR.
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 APPEAR TO BE SHOWN AS 20A'S HOWEVER NO
 CONDUCTORS SIZES ARE SHOWN?
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE REDLINED PLANS, MANY ARE
 MISSING.
  
 5)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE PLANS, THERE ARE NUMEROUS
 MISSING.
 PLEASE ALSO SEE "RAIL AREA" ON SECOND
 FLR IS CONSIDERED WALL SPACE AND WILL
 REQUIRED RECEPT(S). (FLR OUTLET)
  
 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 8)NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S) AND PLANS.
 PLANS INDICATE MULTIPLE PANELS A&B AND
 MSB. PLEASE SEE NO PANEL SCHEDULE
 SUBMITTED FOR PANEL "C". PLEASE SEE
 THERE ARE NUMEROUS ITEMS THAT DO NOT
 CORRELATE SERVICE AND PLANS.
  
 9)NOTE: PLEASE SEE 250.6,250.24, NO
 EQUIPMENT GROUNDING SHALL BE INSTALLED
 FROM METER TO MAIN.
  
 10)NOTE: PLEASE 210.52H FOR MISSING
 REQUIRED HALL RECEPTS. MORE THAN ONE
 LOCATION.
  
 11)NOTE: PLEASE SEE 210.70 FOR MISSING
 EGRESS LIGHTING CONTROL(S) IN MORE THAN
 ONE LOCATION. PLEASE ALSO SEE MISSING
 LIGHTING FOR GRADE LEVEL ACCES STAIRS.
  
 12)NOTE: PLEASE SEE 210.52C-1-5 FOR
 RECEPTS REQUIRED IN KITCHENS ALONG
 COUNTERSPACES ETC.
  
 13)NOTE: PLEASE SHOW ALL OUTSIDE, GARAGE
 RECEPTS ETC AS GFI/ GFI PROTECTED.
 210.8B3
  
 14)NOTE: PLEASE SEE MISSING ISCONNECTS
 FOR A/C EQUIPMENT.440.11
  
 15)NOTE: PLEASE CORRELATE LOAD
 CALCAULTIONS AND PANEL SCHEDULES FOR A/C
 EQUIPMENT. SHOWN AT 5KW. 7.5 KW, 10 KW
 ??
 ETC ETC.
  
 16)NOTE: PLEASE INCLUDE ALL CONDUCTOR
 SIZES ON PANEL SCHEDULES AND CORRELATE
 WITH THE OCP SHOWN.
 310.16,240.4
  
 17)NOTE: PLEASE SEE 210.11C1 FOR MISSING
 REQUIRED SMALL APPLIANCE CIRCUITS.
 PLEASE SEE LOAD CALCS INDICATE TWO,
 HOWEVERONE SHOWN AT 1.5KW AND THE
 OTHER AT 1.2? PLEASE SEE MIN OF 1.5KW IS
 REQUIRED PER 220.16, 210.11C1 PLEASE
 ALSO SEE PANEL SCHEDULES DO NOT INDICATE
 SMALL APPLIANCE CIRCUITS??
  
 18)NOTE: PLEASE SEE NEC FOR LOAD
 CALCULATIONS.
 PLEASE SUBMIT LOAD CALCULATIONS BASED ON
 MIN REQUIREMENTS UNDER 220.31 ETC.
  
 19)NOTE: PLEASE SEE POOL HEATER MAY NOT
 BE DERATED AT 65% AS THIS LOAD IS A
 CONTINUOUS LOAD (3 OR MORE) HOURS AND
 MUST BE SHOWN AT 125% ALONG WITH LARGEST
 MPTORS LOADS. POOL PUMP IS ALSO 125% FOR
 A CONT LOAD.215.3, 230.42 ETC.
  
 20)NOTE: PLEASE SEE MISSING
 LAUNDRY/WASHER CIRCUIT REQUIRED PER
 220.16, 210.11C2
  
 21)NOTE: PLEASE SEE THERE ARE THREE A/C
 SYSTEMS SHOWN ON PANEL SCHEDULE,
 HOWEVER, LOAD CALCS ONLY SHOWN 2???
 PLEASE CORRELATE.
 215.5
  
 22)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES REQUIRED FOR A/C, AHU DISC'S.
 PLEASE ALSO SEE OCP IS NOT PERMITTED IN
 CLOTHES/ STORAGE CLOSETS.240.24D ETC
  
 23)NOTE: PLEASE SEE TITLE BLOCKS ARE
 MISSING LICENSE INFORMATION AS REQUIRED
 UNDER FAC 61G1-16.004 AND FS 481.219
 PLEASE ALSO SEE TITLE BLOCKS CHANGE FROM
 PAGE TO PAGE WITH DIFFERENT COMPANY NAME
 AND FIRMS SHOWN.
 PLEASE SEE PLANS ALSO APPEAR TO BE
 "SIGNED" WITH INITIALS WHICH ARE NOT
 ACCEPTABLE. IF INDEED THIS IS THE "LEGAL
 SIGNATURE" OF ARCH, PLEASE SUBMIT A
 SIGNED, DATED SEALED AND NOTORTIZED
 LETTER STATING LEGAL SIGNATURE.
 FS 481.221
 PLEASE SEE THIS COMMENT IS FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 PLEASE SEE DUE TO THE AMOUNT OF COMMENTS
 ,CODE CORRECTIONS NEEDED, AND MISSING
 INFORMATION FURTHER COMMENTS MAY BE
 POSSIBLE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  