| 2005-05-25 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY PRIOR TO PERMIT ISSUANCE. |
| | THE PLANS MUST BE STAMPED AND THE |
| | RECEIPT ATTACHED TO THE APPLICATION. |
| | 561-233-5025 |
| | |
| | 3.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | 4.)SOILS INVESTIGATION REPORT |
| | REQUIRED. |
| | |
| | 5.)THE ARCHITECT FIRM IS TO HAVE A CA |
| | NUMBER.TITLE BLOCK TO BE IN |
| | CONFORMANCE WITH FAC61G1-16.003,004. |
| | |
| | 6.)ENERGY CALCS REQUIRED, FBC11-101.2. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALC, FBC11-103.1.2. |
| | |
| | 7.)THE WIND RESISTANCE NOTES ON T1 |
| | WERE PREPARED BY ANOTHER DESIGN |
| | PROFESSIONAL, MAKES REFERENCE TO A |
| | COMMERCIAL STRUCTURE, AND STATE THAT |
| | THIS IS A PARTIALLY ENCLOSED BUILDING |
| | WHICH IS NOT TO BE SHUTTERED.OTHER |
| | SHEETS SPECIFY IMPACT GLASS.PLEASE |
| | CLARIFY. |
| | |
| | 8.)SHOW THE BAY WINDOWS ON THE SITE |
| | PLAN FOR ZONING REVIEW. |
| | |
| | 9.)INDICATE NORTH ON THE SITE PLAN AND |
| | THE FLOOR PLAN. |
| | |
| | 10.)REGARDING THE MITERED GLASS, SEE |
| | FBC2406 AND 1707.L.4.2, SHOW COMPLIANCE. |
| | ALSO, LOCAL OR STATE PRODUCT APPROVAL |
| | REQUIRED FAC9B72. |
| | |
| | 11.)LOCAL OR STATE PRODUCT APPROVAL |
| | REQUIRED FOR: |
| | SHINGLE OR METAL ROOF |
| | WINDOWS |
| | MULLIONS |
| | FIXED GLASS WINDOWS |
| | FRENCH DOORS |
| | CASEMENT WINDOW |
| | OVERHEAD DOOR |
| | SKYLIGHTS |
| | IMPACT PROTECTION IF REQUIRED |
| | TEST REPORT AND INSTALLATION |
| | INSTRUCTIONS REQUIRED IN ADDITION TO THE |
| | FLORIDA OR LOCAL PRODUCT APPROVAL. |
| | |
| | SEPARATE PERMITS WILL BE REQUIRED FOR |
| | ANY PRODUCT APPROVALS NOT PROPERLY |
| | SUBMITTED AND REVIEWED PRIOR TO |
| | ISSUANCE. |
| | |
| | 12.)PLEASE READ FBC35 IN REGARDS TO |
| | STANDARDS.YOU MAKE REFERENCE TO |
| | ACI318-63 ON SHEET A3.(ALSO SPECIFIES |
| | 300PSI CONCRETE.) THAT REFERENCE IS VERY |
| | OUTDATED.CHECK ALL REFERENCES. |
| | |
| | 13.)SHOW THE PLUMBING ON THE |
| | FOUNDATION PLAN. |
| | |
| | 14.)PROVIDE DESIGN CRITERIA REQUIRED |
| | BY FBC1606.1.7.NO DESIGN PRESSURES FOR |
| | ROOF OR COMPONENTS AND CLADDING WERE |
| | PROVIDED. |
| | |
| | 15.)A7.0 SPECIFIES HUGHES CONNECTORS. |
| | THEY HAVE BEEN OUT OF BUSINESS FOR MANY |
| | YEARS.SPECIFY AVAILABLE, CODE |
| | COMPLIANT PRODUCTS ONLY. |
| | |
| | 16.)A7.0 MAKES REFERENCE TO BOCA 1996. |
| | GOVERNING CODE IS FBC2001. |
| | |
| | 17.)A7.0, PLYWOOD/GYPBOARD SHEATHING |
| | NOTES, ITEM 2 (NAILING PATTERN 6? EDGES, |
| | 6? FIELD) IS NON COMPLIANT, SEE |
| | FBC*TABLE 2306.1. |
| | |
| | 18.)PROVIDE A WALL SECTION CONTINUOUS |
| | FOUNDATION THROUGH ROOF, INCLUDING GRADE |
| | IN RELATION TO FINISH FLOOR AND BOTTOM |
| | OF FOOTER, FBC*104.3.1.1, FBC*1804.1.7. |
| | |
| | 19.)WATERSTOP REQUIRED FBC2111.1.9, |
| | FIRST AND SECOND FLOOR. |
| | |
| | 20.)WHAT IS THE CONSTRUCTION OF THE |
| | CABANA WALLS?IT DOES NOT APPEAR TO BE |
| | BLOCK.PROVIDE A DETAIL. |
| | |
| | 21.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE BAY WINDOWS. |
| | |
| | 22.)PROVIDE CALCULATIONS TO JUSTIFY |
| | THE 16X16 FOOTER WITH TWO #5S FOR THE |
| | TWO STORY BLOCK STRUCTURE.A3, TYP CBS |
| | EDGE DETAIL AND CONCRETE WORK ITEM 3 |
| | SHOWS 16X16, PLAN STATES 16X24. |
| | STRUCTURAL DETAILS SHOULD BE CONSISTENT. |
| | |
| | 23.) PROVIDE CALCULATIONS FOR THE FILLED |
| | CELLS SET AT EVERY 10?. |
| | |
| | 24.)VERTICAL FILLED CELLS SHOWN AND |
| | SPECIFIED ON ONE SIDE OF EACH OPENING |
| | ONLY.WINDOW AND DOOR TEST REPORTS |
| | GENERALLY HAVE A MINIMUM FASTENER |
| | EMBEDMENT REQUIREMENT, HOW WILL THIS BE |
| | ADDRESSED? |
| | |
| | 25.)PROVIDE WINDOW AND DOOR BUCK |
| | DETAILS. |
| | |
| | 26.) A4.0 WALL BETWEEN GARAGE AND ENTRY |
| | HALLWAY SHOWS A 6" CBS SOLID.WHAT DOES |
| | THIS MEAN?PROVIDE A DETAIL. |
| | |
| | 27.)SPECIFY INSULATION FOR THE |
| | ADJACENT WALL (BETWEEN GARAGE AND ENTRY |
| | HALL). |
| | |
| | 28.)ADJACENT DOORS SHALL BE BE EITHER |
| | SOLID CORE, INSULATED OR WOOD PANEL, |
| | CANNOT BE HOLLOW CORE (DOOR 7). |
| | |
| | 29.)PROVIDE AREA CALCULATIONS ON THE |
| | PLAN - AREAS UNDER AIR, 1ST AND 2ND |
| | FLOORS, AND UNCONDITIONED SPACE. |
| | |
| | 30.)CASEMENT WINDOWS ARE SPECIFIED IN |
| | THE WINDOW SCHEDULE, SINGLE HUNG ARE |
| | SHOWN.THE MASONRY OPENING SIZES DO NOT |
| | LEAVE ROOM FOR A WINDOW BUCK ON THE |
| | SIDES. |
| | |
| | 31.)PROVIDE BEAM HEIGHTS ON THE PLAN. |
| | |
| | 32.)DETAILS SHOWN ON A6.0 ARE NOT |
| | CLEAR.COMPLETE DIMENSIONS AND |
| | MATERIALS ARE NOT SHOWN. |
| | |
| | 31.)PROVIDE A STRUCTURAL DETAIL FOR |
| | THE STAIRS, WITH ALL DIMENSIONS, |
| | INCLUDING THE LANDING AND FIREBLOCKING |
| | FBC2305.1.4(3). |
| | |
| | 32.)SHOW ATTIC ACCESS LOCATIONS AND |
| | SIZE FBC2309. |
| | |
| | 33.)SAFETY GLASS REQUIRED AT TUBS AND |
| | SHOWER, FBC2405.1. |
| | |
| | 34.)THE CANTILEVERED BALCONY DETAIL A6 |
| | DOES NOT HAVE A SLAB DIMENSION. |
| | |
| | 35.)SPECIFY SOFFIT VENTING AND SHOW |
| | COMPLIANCE FBC2309.7. |
| | |
| | 36.)SPECIFY REACTION LOADS ON THE ROOF |
| | FRAMING PLAN A7.0. |
| | |
| | 37.)PROVIDE CALCULATIONS FOR THE BOND |
| | BEAM, ONE 8X8 WITH TWO #4S. |
| | |
| | 38.)PROVIDE DESIGN CRITERIA FOR |
| | HANDRAILS AND GUARDRAILS, FBC1608.2, |
| | FBC1007, FBC1015.STAIR DETAIL |
| | DIFFICULT TO READ.THE RAILING CANNOT |
| | BE 34", FBC1015, FBC1026.5. |
| | |
| | 39.)PROPERTY APPRAISER'S WEBSITE SHOW |
| | TWO LOTS WITH THIS ADDRESS, EACH WITH A |
| | STRUCTURE ON IT.PLEASE CLARIFY. |
| | |
| | 40.) REINFORCEMENT ABOVE OPENINGS HAS |
| | NOT BEEN SPECIFIED.PROVIDE A SCHEDULE. |
| | |
| | 41.) A COPY OF THE PLANS HAS BEEN |
| | RETAINED. |