| Plan Review Notes For Permit 05041903 |
| Permit Number |
05041903 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-09 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} A DISCONNECT MUST BE INSTALLED PRIOR | | | TO CONDUCTORS ENTERING THE BUILDING PER | | | 225.31 & 225.32. | | | | | | 2} THE SITE PLAN DOES NOT SHOW THE | | | LOCATION OF THE NEW 125 AMP PANEL. | | | | | | 3} THE RISER DOES NOT SHOW THE UTILITY | | | SOURCE CONNECTION. IF BEING ROUTED TO | | | THE ATS THAT EQUIPMENT MUST BE LISTED | | | PER 225.36 AND 230.66. | | | | | | 4} DISCONNECTS MUST BE GROUPED PER | | | 230.72. | | | | | | 5} IDENTIFICATION MUST BE INSTALLED PER | | | 225.37. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | PLEASE NOTE THAT A GAS APPLICATION MUST | | | BE SUBMITTED FOR REVIEW PRIOR TO PERMIT | | | BEING ISSUED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|