Plan Review Notes
Plan Review Notes For Permit 05041903
Permit Number 05041903
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-09 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} A DISCONNECT MUST BE INSTALLED PRIOR
 TO CONDUCTORS ENTERING THE BUILDING PER
 225.31 & 225.32.
  
 2} THE SITE PLAN DOES NOT SHOW THE
 LOCATION OF THE NEW 125 AMP PANEL.
  
 3} THE RISER DOES NOT SHOW THE UTILITY
 SOURCE CONNECTION. IF BEING ROUTED TO
 THE ATS THAT EQUIPMENT MUST BE LISTED
 PER 225.36 AND 230.66.
  
 4} DISCONNECTS MUST BE GROUPED PER
 230.72.
  
 5} IDENTIFICATION MUST BE INSTALLED PER
 225.37.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 PLEASE NOTE THAT A GAS APPLICATION MUST
 BE SUBMITTED FOR REVIEW PRIOR TO PERMIT
 BEING ISSUED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718