Plan Review Notes
Plan Review Notes For Permit 05041896
Permit Number 05041896
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ROUTE PLANS TO DBPR HOTEL & RESTURANT
 DIVISION FOR PLAN REVIEW. MINIMUM 2 SETS
 OF PLANS, REVIEWED BY DEBR SHALL BE
 RESUBMITTED FOR REVIEW, WITH DBPR STAMPS
 AND 2 PAGE "WORK SHEETS" ATTACHED SHALL
 BE RESUBMITTED FOR REVIEW. SECTION
 101.4.7.
 2. GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 MANAGER. PLEASE CONTACT MR. COMPO BY
 E-MAIL AT [email protected], OR FAX HIM AT
 (561) 659-7458. - PLEASE ATTACH THE
 DETERMINATION SHEET FROM MR. COMPO WITH
 PLANS WHEN RESUBMITTING.
 3. PLEASE INDICATE HOW THE STORM WATER
 WILL BE KEPT FROM DRAINING INTO THE
 DUMPSTER PAD DRAIN. AND THE CAN WASH
 SINK SECTION 104.2.1.
 4. SHTS A.01, A.07 & A.08 SHOW CLEAR
 FLOOR SPACE FOR THE FOLLOWING FIXTURES.
 ALL ACCESSIBLE WATER CLOSETS. LAVS,
 SHOWERS ECT. FOR EACH TOILET ROOM. ALSO
 SHOW THE 5' TURNING AREA IN EACH TOILET
 ROOM. SECTIONS 11-4.16.2, 11-4.19.3,
 11-4.21.2.
 5. SHOW THE FOLLOWING ACCESSIBLE FIXTURE
 REQUIREMENTS:
 FOR W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.3 HEIGHT & CLAEARANCES
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.19.5 FAUCETS
 FOR SHOWERS
 A. 11-4.21.3 SEAT
 B. 11-4.21.4 GRAB BARS
 C. 11-4.21.5 CONTROLS
 D. 11-4.21.6 SHOWER UNITS
 E. 11-4.21.7 CURBS
 6. SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ALL AREAS OF ROOFS THAT
 DRAIN ONTO THE ROOF FROM ABOVE ADDED TO
 THE SQUARE FOOTAGE OF THE ROOF AREAS.
 SHOW THE LOCATION OF ALL SECONDARY ROOF
 DRAINS.
 7. ALL P,M,E & FS SHEETS. ENGINEER SHALL
 INDICATE THE CERTIFICATION OF
 AUTHORIZATION REQUIRED BY
 61G15-23.002(2) ON EACH SHEET IN THE
 TITLE BLOCK. FS 471.025.
 8. ALL ARCHITECTURAL SHEETS. ENGINEER
 SHALL INDICATE THE CERTIFICATION OF
 AUTHORIZATION REQUIRED BY FAC
 61G15-23.002(2) ON EACH SHEET IN THE
 TITLE BLOCK. FS 471.025.
 9. SHT P.02 STORM DRAINAGE ISOMETRIC
 DOES NOT REFLECT THE ROOF DRAINAGE PLAN.
 4" DD @ 391SF SHOWN ON THE ROOF PLAN IS
 NOT SHOWN ON THE STORM RISER DIAGRAM.
 ALSO PLEASE INDICATE WHERE "ACO DECK
 DRAIN" DRAINS TO. DOES THE 4" RWL 652SF
 AND THE 4" DD 652SF TIE INTO THE SAME
 "ACO DECK DRAIN" OR IS THE 6" "ACO DECK
 DRAIN SEPARATE? SUBMIT DETAIL. SECTION
 104.2.1.
 10. SHT P.03 SANITARY & GREASE WASTE
 PIPING PLAN, AND WASTE PIPING ISOMETRICS
 SAFE WASTE NOT APPROVED. SEPARATE TRAPS
 REQUIRED FOR EACH FIXTURE. SECTION
 1002.1. - FLOOR SINKS WITH INDIRECT
 WASTE PIPES SHALL NOT BE LOCATED WHERE
 THEY CAN BE A TRIPPING HAZARD. LOCATE
 ALL FLOOR SINKS UNDER THE FIXTURES. -
 FLOOR DRAINS ARE NOT APPROVED FOR
 INDIRECT WASTE. EITHER A FLOOR SINK OR A
 HUB DRAIN IS APPROVED. SECTIONS 802.3 &
 802.3.2. - DISHWASHER SHALL DRAIN TO
 SANITARY WASTE NOT GREASE WASTE PER
 UTILITY DEPT. REQUIREMENT. - CLEANOUTS
 ARE REQUIRED NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 SECTION 708.3.5.
 11. SHT P.04 WATER PIPING ISOMETRIC. AIR
 CHAMBERS ARE NOT APPROVED AND SHALL BE
 DELETED. ALSO WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9 SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 12. SHT P.04 WATER PIPING ISOMETRIC.
 FULL OPEN VALVES REQUIRED ON ALL WATER
 DOWN FEED LINES. (SEE CAN WASH) SECTION
 606.1(4) - SHUT OFF VALVES ARE REQUIRED
 AT THE HOSE BIBB. SECTION 606.2(2) - NO
 OUTLET FOR WATER FEEDING "FIAT #830-AA
 FAUCET. PLEASE INDICATE WHAT TYPE OF
 FAUCET THIS IS, WHAT ITS WHAT IS THE
 PURPOSE OF THE FLOOR DRAIN IT SERVES.
 13. SHT P.05 SAFE WASTE IS NOT APPROVED.
 DELETE DETAIL. SECTION 1002.1.
 14. SHT P.05 WATER HEATER DETAIL,
 THERMAL EXPANSION CONTROL IS REQUIRED.
 SECTION 607.3.2. - P&T DISCHARGE LINE
 SHALL DRAIN TO A FLOOR SINK OR HUB DRAIN
 FLOOR DRAINS ARE NOT APPROVED INDIRECT
 WASTE RECEPTORS. SECTIONS 802.3 AND
 802.3.2.
 15. THE FOLLOWING INFORMATION IS
 REQUIRED FOR GAS PERMIT.
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -
 SHOW ON ISOMETRIC.
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - INDICATE
 THE TOTAL DEVELOPED LENGTH OF EACH
 SYSTEM. (2LB FROM METER & 1/2LB
 DOWNSTREAM OF REGULATOR.)
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. - MANUAL
 VALVE SHALL BE UPSTREAM OF GAS REGULATOR
 ALSO.
 G. SUBMIT MANUF. SPECIFICATION SHEET FOR
 REGULATOR. PLEASE INDICATE MANUF., MAKE,
 AND MODEL. SECTION 303.8
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]