2005-06-14 00:00:00DENIED:
 1.PLEASE INDICATE WHAT WILL BE STORED
 IN THE "STORAGE" AREA.
  
 2.PLAN SHEET A.01 INDICATES EXISTING
 RAMP.FRESH AIR INTAKES SHALL BE A
 MINIMUMOF 10 FT FROM LOADING DOCKS,
 PARKING LOSTS, ALLEYS, ETC. PER 2001
 FBC(M)401.5.1 & 401.5.
  
 3.EXHAUST OPENINGS SHALL NOT BE
 DIRECTED ONTO WALKWAYS PER 2001 FBC(M)
 401.5.2.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE PER
 2001 FBC(M) 606.2.1 & 606.4.1.
  
 HOOD/SUPRESSION REVIEW:
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPPRESSION, GAS AND WALK-IN
 COOLERS.
 1.PROVIDED ELEVATION OF THE KITCHEN
 EXHAUST FAN INDICATED ON PLAN SHEET
 M.04.SHALL COMPLY WITH 2001 FBC(M)
 506.3.14.2 & 506.3.14.3.
  
 2.PROVIDE CLEARANCE TO COMBUSTIBLES.
 INDICATE CLEARANCE REDUCTION METHODS ON
 PLAN.
  
 3.INDICATE DUCT & HOOD MATERIAL IN
 ACCORDANCE WITH 2001 FBC(M) 506.3.3 &
 507.4 RESPECTIVELY.
  
 4.AIR VELOCITY WITHIN THE GREASE DUCT
 SHALL NOT LESS THAN 1,500 FPM & NOT
 GREATER THAN 2,500 FPM.
  