Plan Review Notes
Plan Review Notes For Permit 05041896
Permit Number 05041896
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-10 00:00:00IN ELECTRIC FOR REVIEW.
 ************* UNSAT ************
  
 1)NOTE: PLEASE SUBMIT WIND LOADING
 CALCULATIONS/ WIND LOADING FOR LT POLES
 AND FIXTURES PER FBC 140 MPH.
 THIS IS REQUIRED AT THIS TIME.
  
 2)NOTE: PLEASE INCLUDE REQUIRED LICENSE
 # INFORMATION ON TITLE BLOCKS PER FAC
 61G15-23.002 AND FS 471.023.
 PLEASE SEE THIS IS REQUIRED OF ALL
 TRADES SHEETS WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAMS
 AND PANEL SCHEDULES.
 PLEASE SEE ONE RISER SHOWS "NEW" PANEL
 SS IN BOLD AND PANELS K AND EK AS
 EXSITING? HOWEVER, SOME OF THESE ARE
 ALSO SHOWN AS NEW ON PANEL SCHEDULE(S)
 AND OTHER RISER?
 PLEASE ALSO SEE TRANSFORMER DETAIL SHOWS
 DISC('S) WHICH ARE NOT SHOWN ON RISER ?
 PLEASE SEE THERE ARE MANY ITEMS THAT DO
 NOT CORRELATE AND HAVE BEEN REDLINED.
 215.5
  
 4)NOTE: PLEASE 250.30 FOR GROUNDING OF
 TRANSFORMER TO BE SHOWN.
 PLEASE PROVIDE ATTACHMENT DETAIL.
  
 5)NOTE: PLEASE INCLUDE LOAD CALCULATIONS
 FOR ADDED LOAD TO ENTIRE SERVICE. PANEL
 HU2 IS FED FROM TWO OTHER ELECTRICAL
 PANELS/MAINS.
 PLEASE ALOS SHOW ALL CONTINUOUS LOADS AT
 125%, ALONG WITH LARGEST MOTORS LOADS.
 220,215.5
  
 6)NOTE: PLEASE SEE TRANSFOMER DETAIL
 SHOWN, SHOWS ONLY FEEDERS ETC FOR NEW
 PANEL "SS", HOWEVER OTHER PANELS ARE
 INDICATED AS NEW ALSO??
  
 7)NOTE: PLEASE SEE NOTE ON RISER
 MENTIONS; REFER TO ORIGINAL PLANS"
 PLEASE SEE THIS PROJECT/OTHER PERMITS/
 WERE COMPLETED SOME TIME AGO AND THOSE
 PLANS ARE NOT READILY AVAILABLE FOR
 VIEWING.
 ANY REFERENCES AND /OR INFORMATION
 NEEDED TO BE NOTED FROM PREVIOUS
 PLANS/DRAWINGS, NEEDS TO BE DONE ON
 PLANS SUBMITTED.
 215.5
  
 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 ALL GFI PROTECTION REQUIRED IN
 KITCHENS.SECTION 210.8(B)(3) IS NEW FOR
 THE 2002 CODE AND REQUIRES ALL 15- AND
 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS TO BE GFCI
 PROTECTED. THIS REQUIREMENT APPLIES TO
 EACH AND EVERY 15- AND 20-AMPERE,
 125-VOLT KITCHEN RECEPTACLE, WHETHER OR
 NOT THE RECEPTACLE SERVES COUNTERTOP
 APPLIANCES.
  
 9)NOTE: PLEASE SEE NUMEROUS LOCATIONS ON
 RISER APPEARS TO A "NUMBERING" FOR
 NOTES, HOWEVER NO NOTES CORRELATING TO
 THESE COULD BE LOCATED ON PLANS??
 PLEASE SEE REDLINED PLANS FOR THESE.
  
 10)NOTE: PLEASE SEE 450.3 FOR MAX OPC
 FOR TRANSFORMERS> (125%).
 PLEASE SEE 125A,60A ETC SHOWN.
  
 11)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN
 @ #0??
 PLEASE SEE NEC 310.16, THIS IS NOT A
 CONDUCTOR SIZE RECOGNIZED UNDER THE AWG.
  
 PLEASE BE SURE TO SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHALL BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  