| 2005-05-10 00:00:00 | IN ELECTRIC FOR REVIEW. |
| | ************* UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SUBMIT WIND LOADING |
| | CALCULATIONS/ WIND LOADING FOR LT POLES |
| | AND FIXTURES PER FBC 140 MPH. |
| | THIS IS REQUIRED AT THIS TIME. |
| | |
| | 2)NOTE: PLEASE INCLUDE REQUIRED LICENSE |
| | # INFORMATION ON TITLE BLOCKS PER FAC |
| | 61G15-23.002 AND FS 471.023. |
| | PLEASE SEE THIS IS REQUIRED OF ALL |
| | TRADES SHEETS WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE CORRELATE RISER DIAGRAMS |
| | AND PANEL SCHEDULES. |
| | PLEASE SEE ONE RISER SHOWS "NEW" PANEL |
| | SS IN BOLD AND PANELS K AND EK AS |
| | EXSITING? HOWEVER, SOME OF THESE ARE |
| | ALSO SHOWN AS NEW ON PANEL SCHEDULE(S) |
| | AND OTHER RISER? |
| | PLEASE ALSO SEE TRANSFORMER DETAIL SHOWS |
| | DISC('S) WHICH ARE NOT SHOWN ON RISER ? |
| | PLEASE SEE THERE ARE MANY ITEMS THAT DO |
| | NOT CORRELATE AND HAVE BEEN REDLINED. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE 250.30 FOR GROUNDING OF |
| | TRANSFORMER TO BE SHOWN. |
| | PLEASE PROVIDE ATTACHMENT DETAIL. |
| | |
| | 5)NOTE: PLEASE INCLUDE LOAD CALCULATIONS |
| | FOR ADDED LOAD TO ENTIRE SERVICE. PANEL |
| | HU2 IS FED FROM TWO OTHER ELECTRICAL |
| | PANELS/MAINS. |
| | PLEASE ALOS SHOW ALL CONTINUOUS LOADS AT |
| | 125%, ALONG WITH LARGEST MOTORS LOADS. |
| | 220,215.5 |
| | |
| | 6)NOTE: PLEASE SEE TRANSFOMER DETAIL |
| | SHOWN, SHOWS ONLY FEEDERS ETC FOR NEW |
| | PANEL "SS", HOWEVER OTHER PANELS ARE |
| | INDICATED AS NEW ALSO?? |
| | |
| | 7)NOTE: PLEASE SEE NOTE ON RISER |
| | MENTIONS; REFER TO ORIGINAL PLANS" |
| | PLEASE SEE THIS PROJECT/OTHER PERMITS/ |
| | WERE COMPLETED SOME TIME AGO AND THOSE |
| | PLANS ARE NOT READILY AVAILABLE FOR |
| | VIEWING. |
| | ANY REFERENCES AND /OR INFORMATION |
| | NEEDED TO BE NOTED FROM PREVIOUS |
| | PLANS/DRAWINGS, NEEDS TO BE DONE ON |
| | PLANS SUBMITTED. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | ALL GFI PROTECTION REQUIRED IN |
| | KITCHENS.SECTION 210.8(B)(3) IS NEW FOR |
| | THE 2002 CODE AND REQUIRES ALL 15- AND |
| | 20-AMPERE, 125-VOLT RECEPTACLES IN |
| | NONDWELLING-TYPE KITCHENS TO BE GFCI |
| | PROTECTED. THIS REQUIREMENT APPLIES TO |
| | EACH AND EVERY 15- AND 20-AMPERE, |
| | 125-VOLT KITCHEN RECEPTACLE, WHETHER OR |
| | NOT THE RECEPTACLE SERVES COUNTERTOP |
| | APPLIANCES. |
| | |
| | 9)NOTE: PLEASE SEE NUMEROUS LOCATIONS ON |
| | RISER APPEARS TO A "NUMBERING" FOR |
| | NOTES, HOWEVER NO NOTES CORRELATING TO |
| | THESE COULD BE LOCATED ON PLANS?? |
| | PLEASE SEE REDLINED PLANS FOR THESE. |
| | |
| | 10)NOTE: PLEASE SEE 450.3 FOR MAX OPC |
| | FOR TRANSFORMERS> (125%). |
| | PLEASE SEE 125A,60A ETC SHOWN. |
| | |
| | 11)NOTE: PLEASE SEE CONDUCTOR SIZE SHOWN |
| | @ #0?? |
| | PLEASE SEE NEC 310.16, THIS IS NOT A |
| | CONDUCTOR SIZE RECOGNIZED UNDER THE AWG. |
| | |
| | PLEASE BE SURE TO SEE POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY HAVE AN |
| | AFFECT ON ELECTRICAL PLANS. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO COMPLETE SETS FOR |
| | REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHALL BE SUBMITTED |
| | FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |