Plan Review Notes
Plan Review Notes For Permit 05041896
Permit Number 05041896
Review Stop B
Sequence Number 1
Notes
Date Text
2005-06-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.PLEASE CALL 233-5025 FOR
 MORE INFORMATION.
  
 3.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 4.)PROVIDE INFORMATION IN REGARDS TO
 THE MATERIALS TO BE STORED IN THIS AREA.
  
 5.)HOW HAVE YOU DETERMINED A TYPE IV
 BUILDING, SHEET T.01?SHOW COMPLIANCE
 WITH FBC TABLE 500 AND FBC CHAPTER 5
 AREA INCREASES.PRINCIPAL USE IS A1,
 FBC304.2.1.1.
  
 6.)T.01 AND S.06 SHOWS A 3 HOUR
 REQUIRED FIRE SEPARATION BETWEEN A AND
 S1 OCCUPANCY.SHEET A.08 DOES NOT SHOW
 ANY 3 HOUR FIRE RATED WALLS (SHOWS THAT
 WALL AS 1 HR), LS1 SHOWS A 1 HR.SHOW
 FIRE SEPARATION AS REQUIRED BY FBC TABLE
 704.1 AND OPENING PROTECTIVES TABLE
 705.1.2.A 3 HR IS REQUIRED FOR THE
 DOORS 06 AND 05 BUT A 45 MIN IS SHOWN ON
 A.08 DOOR SCHEDULE.
  
 7.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.PLEASE
 PROVIDE PRODUCT APPROVALS ALONG WITH
 SUPPORTING DOCUMENTATION (EVALUATION,
 NOA OR TEST REPORT, INSTALLATION
 INSTRUCTIONS).WWW.FLORIDABUILDING.ORG
  
 EXTERIOR DOORS (DOUBLE AND SINGLE)
 OVERHEAD DOORS
 LOUVERS
  
 7.)SHOW EXITING FROM THE KITCHEN LS01;
 SHOULD NOT GO THROUGH A MORE HAZARDOUS
 CONDITION, FBC1001.1.4.
  
 8.)THERE ARE SOME FILLED CELLS LACKING
 FROM THE PLAN A.01; BUILDING CORNERS,
 BOTH SIDES OF OPENINGS.ACI530,
 FBC2103, PRODUCT APPROVAL ATTACHMENT
 REQUIREMENTS.
  
 9.)A.02 SHOWS THE VERTICAL
 ACCESSIBILITY AS A RAMP, 2-A.07.ACCESS
 TO THIS RAMP IS ON EXISTING RAMPS.ARE
 THESE PEDESTRIAN RAMPS OR VEHICULAR?
 YOU CANNOT USE A VEHICULAR RAMP TO
 CONNECT ACCESSIBLE ELEMENTS.WHAT IS
 THE EXISTING RAMP SLOPE?
  
 10.) 9-A.06 IS TO COMPLY WITH FBC11
 FIGURE 19; MISSING THE EXTENSION AT
 BOTTOM OF RUN.
  
 11.)A-A.07, C-A.07, FBC11-4.16.4, GRAB
 BAR BEHIND WATER CLOSET IS TO BE 36
 INCHES MINIMUM.SHOW SIDE GRAB BAR
 DIMENSION IN COMPLIANCE WITH FBC11
 FIGURE 29.
  
 12.)A.07, SHOW SIDE DIMENSIONS OF
 ACCESSIBLE LAV, FBC11 FIGURE 31.
  
 13.)SHOW CLEARANCE AT BOTTOM OF RAMPS,
 FBC11-4.8.4(2).SHOW DIRECTION CHANGE
 DIMENSION FBC11-4.8.4(2).
  
 14.) THE SERVING AREA SHOWN A.09 IS TO
 COMPLY WITH FBC11-5.5.SHOW TURNING
 SPACE FBC11-4.2.3.
  
 15.)WHAT IS THE USE OF THE KITCHEN
 COUNTER, 51 SHEET A.09?IS THIS A
 SERVING AREA?
  
 16.)THE SPACE BETWEEN THE BOTTOM RAIL
 OF THE GUARDRAIL AND THE DECK SCALES TO
 OVER 3?.THE GUARDRAILS ARE TO COMPLY
 WITH FBC1015.3.ALSO SPECIFY DESIGN
 CRITERIA FBC1608.2.1 (HANDRAILS) AND
 FBC1608.2.2 (GUARDRAILS).
  
 17.)THE HANDRAIL 3-A.10 IS TO BE
 COMPLIANT WITH FBC11 FIGURE 19.
  
 18.)S.01, C1, ACI318 STANDARD SHOULD
 BE 02, FBC3502.
  
 19.)SPECIFY SLOPE ON S.02.
  