Notes
Date Text
2005-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS, AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
 2) WATER RISER DIAGRAMS APPEAR TO HAVE
 AIR CHAMBERS AT THE LAV AND AT THE
 SHOWER VALVE. AIR CHAMBERS ARE NOT
 APPROVED. IF THESE ARE AIR HAMMER
 ARRESTORS, PLEASE INDICATE AS MUCH ON
 THE PLANS. IF THESE ARE AIR CHAMBERS,
 THEY SHALL BE DELETED. SECTION 604.9 AND
 PDI-WH 201.
  