Plan Review Notes
Plan Review Notes For Permit 05041811
Permit Number 05041811
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-05-12 00:00:001) DUCT SMOKE DETECTORS SHALL BE WIRED
 TO THE FIRE ALARM PANEL, TO CAUSE A
 GENERAL ALARM PER LOCAL REQUIREMENTS.
  
 2) THE PLANS SHOW WORK ONLY IN CERTAIN
 AREAS OF THE FIRST FLOOR. DOES THIS WORK
 INCLUDE ANY GUEST ROOMS OR SUITES? IF
 SO, SINGLE STATION SMOKE DETECTORS ARE
 REQUIRED. PLANS SHOW GUEST ROOM
 DETECTORS TIED INTO THE FIRE ALARM
 SYSTEM.
  
 3) PLEASE SUBMIT A LETTER TO THE
 FOLLOWING ADDRESS IN REGARDS TO THE
 SCOPE OF YOUR WORK WITH THIS PROJECT.
  
  