| Plan Review Notes For Permit 05041811 |
| Permit Number |
05041811 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-12 00:00:00 | 1) DUCT SMOKE DETECTORS SHALL BE WIRED | | | TO THE FIRE ALARM PANEL, TO CAUSE A | | | GENERAL ALARM PER LOCAL REQUIREMENTS. | | | | | | 2) THE PLANS SHOW WORK ONLY IN CERTAIN | | | AREAS OF THE FIRST FLOOR. DOES THIS WORK | | | INCLUDE ANY GUEST ROOMS OR SUITES? IF | | | SO, SINGLE STATION SMOKE DETECTORS ARE | | | REQUIRED. PLANS SHOW GUEST ROOM | | | DETECTORS TIED INTO THE FIRE ALARM | | | SYSTEM. | | | | | | 3) PLEASE SUBMIT A LETTER TO THE | | | FOLLOWING ADDRESS IN REGARDS TO THE | | | SCOPE OF YOUR WORK WITH THIS PROJECT. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | BUREAU OF FIRE PREVENTION | | | 500 N. DIXIE HIGHWAY | | | WEST PALM BEACH, FLORIDA 33401 | | | T- (561) 835-2910 OR 805-6722 | | | F- (561) 835-2936 |
|