2005-06-22 00:00:00********** PROVISO/REVISION REQ'D *****
  
 PLEASE SEE NOW THAT CIRCUITING IS SHOWN
 ON PLANS AND PANEL SCHEDULE IS
 SUBMITTED, PLEASE SEE THE FOLLOWING CODE
 COMMENTS FOR CORRECTION NEEDED.
  
 1)NOTE: PLEASE SEE ALL SD'S WHICH ARE
 REQUIRED TO BE WIRED "INLINE" ARE ALL
 SHOWN ON SEPARATE CIRCUITS??? THIS IS
 NOT POSSIBLE . PLEASE ADJUST CIRCUITING,
 ALL SD'S ON SAME CIRCUIT AND THIS
 CIRCUIT SHALL BE ARC FAULT PROTECTED.
 SD'S MAY BE PLACED ON ONE OF THE BEDRM
 CIRCUITS.
 NFPA-72 8-1.4.1.6.2, 210.12
  
 2)NOTE: PLEASE SEE CIRCUITING REQ'D FOR
 "DINING RM". PLEASE SEE DIN RM RECEPTS
 ARE SHOWN ON WITH LIV RM CIRCUITS.
 210.52B1
  
 3)NOTE: PLEASE SEE GFI RECEPT PLACEMENT
 FOR WHAT APPEARS TO BE A KITCHEN
 PENINSULAR IS TO BE VERIFIED AND SHOWN
 TO MEET 210.52C3,5
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT REVISED PLANS BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
  
 PLEASE NOTE: IF PLANS COME BACK WITH AMY
 OTHER CORRECTIONS NEEDED BEFORE PERMIT
 IS ISSUED, PLEASE MAKE CORRECTIONS AT
 THATTIME. THIS WILL ALSO ALLEVIATE A
 REVSION FEE AT A LATER DATE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW