| 2005-06-22 00:00:00 | ********** PROVISO/REVISION REQ'D ***** |
| | |
| | PLEASE SEE NOW THAT CIRCUITING IS SHOWN |
| | ON PLANS AND PANEL SCHEDULE IS |
| | SUBMITTED, PLEASE SEE THE FOLLOWING CODE |
| | COMMENTS FOR CORRECTION NEEDED. |
| | |
| | 1)NOTE: PLEASE SEE ALL SD'S WHICH ARE |
| | REQUIRED TO BE WIRED "INLINE" ARE ALL |
| | SHOWN ON SEPARATE CIRCUITS??? THIS IS |
| | NOT POSSIBLE . PLEASE ADJUST CIRCUITING, |
| | ALL SD'S ON SAME CIRCUIT AND THIS |
| | CIRCUIT SHALL BE ARC FAULT PROTECTED. |
| | SD'S MAY BE PLACED ON ONE OF THE BEDRM |
| | CIRCUITS. |
| | NFPA-72 8-1.4.1.6.2, 210.12 |
| | |
| | 2)NOTE: PLEASE SEE CIRCUITING REQ'D FOR |
| | "DINING RM". PLEASE SEE DIN RM RECEPTS |
| | ARE SHOWN ON WITH LIV RM CIRCUITS. |
| | 210.52B1 |
| | |
| | 3)NOTE: PLEASE SEE GFI RECEPT PLACEMENT |
| | FOR WHAT APPEARS TO BE A KITCHEN |
| | PENINSULAR IS TO BE VERIFIED AND SHOWN |
| | TO MEET 210.52C3,5 |
| | |
| | PLEASE MAKE THE ABOVE CORRECTIONS AND |
| | SUBMIT REVISED PLANS BEFORE ROUGH |
| | ELECTRICAL INSPECTION IS CALLED IN. |
| | |
| | PLEASE NOTE: IF PLANS COME BACK WITH AMY |
| | OTHER CORRECTIONS NEEDED BEFORE PERMIT |
| | IS ISSUED, PLEASE MAKE CORRECTIONS AT |
| | THATTIME. THIS WILL ALSO ALLEVIATE A |
| | REVSION FEE AT A LATER DATE. |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |