| Plan Review Notes For Permit 05041807 |
| Permit Number |
05041807 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-03 00:00:00 | ** UNSAT **' | | | | | | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH A PANEL SCHEDULE TO | | | BE SUBMITTED. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE SWITCHES SHOWN AND | | | NOTED TO SW OUTLETS, HOWEVER THESE ARE | | | NOTE SHOWN? PLEASE SHOW. | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE ALL NEW CIRCUTING TO | | | BEDRMS SHALL HAVE ARC FAULT PROTECTION | | | AS REQUIRED UNDER 2002 NEC 210.12. | | | THIS WOULD INCLUDE , RECEPTS, LTS, FANS, | | | SD'S. | | | | | | 4)NOTE: PLEASE SEE 210.52D,210.11C3 FOR | | | IN 20A #12FOR BATH(S) CIRCUIT(S). | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|