Plan Review Notes
Plan Review Notes For Permit 05041807
Permit Number 05041807
Review Stop E
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00** UNSAT **'
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED.
 215.5
  
 2)NOTE: PLEASE SEE SWITCHES SHOWN AND
 NOTED TO SW OUTLETS, HOWEVER THESE ARE
 NOTE SHOWN? PLEASE SHOW.
 215.5
  
 3)NOTE: PLEASE SEE ALL NEW CIRCUTING TO
 BEDRMS SHALL HAVE ARC FAULT PROTECTION
 AS REQUIRED UNDER 2002 NEC 210.12.
 THIS WOULD INCLUDE , RECEPTS, LTS, FANS,
 SD'S.
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 IN 20A #12FOR BATH(S) CIRCUIT(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW