Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop M
Sequence Number 8
Notes
Date Text
2007-07-25 10:46:34** MECHANICAL REVISION TO PLANS PAGES M-03, M-04, AND
 M-05.
 *** PROVISO ***
 1) 2001 FBC/M 504.7 COMMERCIAL CLOTHES DRYERS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING TYPE 2
 CLOTHES DRYERS SHALL COMPLY WITH THE APPLIANCE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. EXHAUST FAN
 MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL BE LOCATED
 OUTSIDE OF THE AIRSTREAM. IN MULTIPLE INSTALLATIONS,
 THE FAN SHALL OPERATE CONTINUOUSLY OR BE INTERLOCKED TO
 OPERATE WHEN ANY INDIVIDUAL UNIT IS OPERATING. DUCTS
 SHALL HAVE A MINIMUM CLEARANCE OF 6 INCHES (152 MM) TO
 COMBUSTIBLE MATERIALS. CLOTHES DRYER TRANSITION DUCTS
 USED TO CONNECT THE APPLIANCE TO THE EXHAUST DUCT
 SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS NOT TO EXCEED
 8 FEET (2438 MM) IN LENGTH AND SHALL BE LISTED AND
 LABELED FOR THE APPLICATION. TRANSITION DUCTS SHALL NOT
 BE CONCEALED WITHIN CONSTRUCTION.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.