| Plan Review Notes For Permit 05041760 |
| Permit Number |
05041760 |
|
| Review Stop |
M |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2007-07-25 10:46:34 | ** MECHANICAL REVISION TO PLANS PAGES M-03, M-04, AND | | | M-05. | | | *** PROVISO *** | | | 1) 2001 FBC/M 504.7 COMMERCIAL CLOTHES DRYERS. | | | THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING TYPE 2 | | | CLOTHES DRYERS SHALL COMPLY WITH THE APPLIANCE | | | MANUFACTURER?S INSTALLATION INSTRUCTIONS. EXHAUST FAN | | | MOTORS INSTALLED IN EXHAUST SYSTEMS SHALL BE LOCATED | | | OUTSIDE OF THE AIRSTREAM. IN MULTIPLE INSTALLATIONS, | | | THE FAN SHALL OPERATE CONTINUOUSLY OR BE INTERLOCKED TO | | | OPERATE WHEN ANY INDIVIDUAL UNIT IS OPERATING. DUCTS | | | SHALL HAVE A MINIMUM CLEARANCE OF 6 INCHES (152 MM) TO | | | COMBUSTIBLE MATERIALS. CLOTHES DRYER TRANSITION DUCTS | | | USED TO CONNECT THE APPLIANCE TO THE EXHAUST DUCT | | | SYSTEM SHALL BE LIMITED TO SINGLE LENGTHS NOT TO EXCEED | | | 8 FEET (2438 MM) IN LENGTH AND SHALL BE LISTED AND | | | LABELED FOR THE APPLICATION. TRANSITION DUCTS SHALL NOT | | | BE CONCEALED WITHIN CONSTRUCTION. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|