Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop G
Sequence Number 8
Notes
Date Text
2008-02-22 14:32:44REVISIONDENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL SHOWS
 2" PIPE UP TO THE BRANCH LINE FOR THE GAS DRYERS. THERE
 WAS NO RESPONSE TO THE RISER DIAGRAM FOR THE POOL/BATH
 RISER NOT REFLECTING THE GASE RISER AT THE METER AND
 ALL CUT SECTIONS WERE NOT PROVIDED.--REGULATOR
 MODELS INDICATED FOR RTU'S 1 & 2 ARE NOT APPROVED.
 MAXIMUM 140 MBH FOR THE MODEL 325-3L, BUT 150 MBH
 INDICATED ON THE RISER DIAGRAM.
  
 ****FROM PREVIOUS PLUMBING REVIEW:
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-- THE
 MANUF. SHEETS FOR THE POOL HEATER SHALL
 BE SUBMITTED.
 ****RESPONSE NOTED, BUT THE DRYER MANUF SHEETS ARE NOT
 APPROVED. THERE IS NO LISTING INDICATED ON THE MANUF.
 SHEETS.NO BTU LOAD INDICATED. COVER SHEET STATES
 "REFER TO PAGE 4 FOR MODEL IDENTIFICATION". PAGE 4 HAS
 NOT BEEN SUBMITTED WITH MANUF. SPECIFICATION SHEETS.
 --NO MANUF. SHEETS FOR RTU UNITS 1 & 2 SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved