| 2008-02-22 14:32:44 | REVISIONDENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE |
| | METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS. |
| | TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM |
| | DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER. |
| | SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM |
| | WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.-- |
| | INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS, |
| | THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 & |
| | 3. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL SHOWS |
| | 2" PIPE UP TO THE BRANCH LINE FOR THE GAS DRYERS. THERE |
| | WAS NO RESPONSE TO THE RISER DIAGRAM FOR THE POOL/BATH |
| | RISER NOT REFLECTING THE GASE RISER AT THE METER AND |
| | ALL CUT SECTIONS WERE NOT PROVIDED.--REGULATOR |
| | MODELS INDICATED FOR RTU'S 1 & 2 ARE NOT APPROVED. |
| | MAXIMUM 140 MBH FOR THE MODEL 325-3L, BUT 150 MBH |
| | INDICATED ON THE RISER DIAGRAM. |
| | |
| | ****FROM PREVIOUS PLUMBING REVIEW: |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.-- THE |
| | MANUF. SHEETS FOR THE POOL HEATER SHALL |
| | BE SUBMITTED. |
| | ****RESPONSE NOTED, BUT THE DRYER MANUF SHEETS ARE NOT |
| | APPROVED. THERE IS NO LISTING INDICATED ON THE MANUF. |
| | SHEETS.NO BTU LOAD INDICATED. COVER SHEET STATES |
| | "REFER TO PAGE 4 FOR MODEL IDENTIFICATION". PAGE 4 HAS |
| | NOT BEEN SUBMITTED WITH MANUF. SPECIFICATION SHEETS. |
| | --NO MANUF. SHEETS FOR RTU UNITS 1 & 2 SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |