2007-07-03 11:15:33REVISION TO MECH. PLANS PAGES M-04, M-05 AND M-06.
  
 *** PROVISO ***
 1) FRESH AIR INTAKE TO COMPLY WITH 2004 FBC/M 401.5.1
 INTAKE OPENINGS.
 MECHANICAL AND GRAVITY OUTSIDE AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE. FRESH AIR INTAKES SHALL NOT BE LOCATED
 CLOSER THAN 10 FEET (3048 MM) FROM ANY CHIMNEY OR VENT
 OUTLET, OR SANITARY SEWER VENT OUTLET.