| Plan Review Notes For Permit 05041760 |
| Permit Number |
05041760 |
|
| Review Stop |
G |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2008-01-17 12:08:52 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE | | | METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS. | | | TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM | | | DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER. | | | SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM | | | WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.-- | | | INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS, | | | THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 & | | | 3. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|