Date Text
2008-01-17 12:08:52DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  