2007-09-05 12:53:05REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SHT P-02C REVISION #5 TO BE INDICATED ON ALL
 REVISIONS ON SHEET. CLOUDS INDICATED, BUT WITHOUT THE
 REVISION NUMBERS. SECTION 104.2.1.3.
  
 2. SHT P-03A DRAWING NOTES (14) & (15). ICE MACHINE AND
 FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL
 SHOWN. DELETE NOTES ALSO. SECTION 104.2.1.
  
 3. SHT P-04A DRAWING NOTES (14) & (15). ICE MACHINE AND
 FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL
 SHOWN. DELETE NOTES ALSO. SECTION 104.2.1.-- REVISION
 #5 HAS NOT BEEN LOCATED. MANY REVISIONS INDICATED
 WITHOUT REVISION NUMBERS. ALL REVISIONS TO BE CLOUDED
 AND NUMBERED. SECTION 104.2.1.3.--REVISION #4 CLOUD
 VERY FAINT AND NOT VERY LEGIBLE. DARKEN CLOUDS TO MAKE
 REVISIONS NOTICIBLE. SECTION 104.2.1.3.-- REVISION #4
 SHOWS WATER LINES UP TO A SHOWER, A TUB & LAV, BUT SHT
 P-05A SHOWS NOT UNIT ABOVE. PLEASE CLARIFY. SECTION
 104.2.1.
  
 4. SHT P-05A REVISION INDICATED FOR THE GAS RISER WITH
 A CLOUD, BUT NO REVISION NUMBER INDICATED. PLEASE CLOUD
 AND NUMBER ALL REVISIONS. SECTION 104.2.1.3.
  
 5. SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO
 BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR
 THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. --
 SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF
 DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE
 FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE
 CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE
 STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.--
 SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR
 EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON
 PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH.
 DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL
 DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1.
  
 6. SHT P-08 GAS RISER ISOMETRIC DIAGRAM. THE GAS
 REGULATORS FOR THE DOMESTIC WATER BOILERS ARE NOT
 APPROVED. THE MAXIMUM INDIVIDUAL LOAD FOR THE MAXITROL
 MODEL 325-51 IS ONLY 250,000 BTU'S. THE RISER DIAGRAM
 INDICATES 400,000 BTU'S FOR EACH BOILER. (SEE ATTACHED
 SHEET). PLEASE SPECIFY THE CORRECT REGULATORS FOR THE
 BOILERS. SECTION 410.2(1). (ALSO CORRECT REGULATOR
 MODEL NUMBER ON DETAIL FOR WATER HEATERS SHEET P-07).
  
 7. SHT P-16 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. RISER SHOWS 2 TUBS, WHEREAS THE FLOOR PLAN
 SHOWS ONE TUB. ALSO SEE SHT P-04A THE WATER SUPPLY IS
 SHOWN IN UNIT 214 WHICH IS RISER W2, BUT THE WATER
 SUPPLY FOR UNIT ON THE 6TH FLOOR IS SHOWN ON RISER W4
 ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
  
 8. NOTE: WHEN SUBMITTING REVISIONS, PLEASE TURN OFF ALL
 PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION
 NUMBERS. LEAVING THE PREVIOUS CLOUDS AND REVISION
 NUMBERS CAUSES CONFUSION AND INCREASES THE TURN AROUND
 TIME FOR THE REVIEWS. THANK YOU.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  