| Date |
Text |
| 2007-09-05 12:53:05 | REVISION DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | |
| | 1. SHT P-02C REVISION #5 TO BE INDICATED ON ALL |
| | REVISIONS ON SHEET. CLOUDS INDICATED, BUT WITHOUT THE |
| | REVISION NUMBERS. SECTION 104.2.1.3. |
| | |
| | 2. SHT P-03A DRAWING NOTES (14) & (15). ICE MACHINE AND |
| | FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL |
| | SHOWN. DELETE NOTES ALSO. SECTION 104.2.1. |
| | |
| | 3. SHT P-04A DRAWING NOTES (14) & (15). ICE MACHINE AND |
| | FLOOR SINK DELETED FROM THE FLOOR PLAN, BUT NOTES STILL |
| | SHOWN. DELETE NOTES ALSO. SECTION 104.2.1.-- REVISION |
| | #5 HAS NOT BEEN LOCATED. MANY REVISIONS INDICATED |
| | WITHOUT REVISION NUMBERS. ALL REVISIONS TO BE CLOUDED |
| | AND NUMBERED. SECTION 104.2.1.3.--REVISION #4 CLOUD |
| | VERY FAINT AND NOT VERY LEGIBLE. DARKEN CLOUDS TO MAKE |
| | REVISIONS NOTICIBLE. SECTION 104.2.1.3.-- REVISION #4 |
| | SHOWS WATER LINES UP TO A SHOWER, A TUB & LAV, BUT SHT |
| | P-05A SHOWS NOT UNIT ABOVE. PLEASE CLARIFY. SECTION |
| | 104.2.1. |
| | |
| | 4. SHT P-05A REVISION INDICATED FOR THE GAS RISER WITH |
| | A CLOUD, BUT NO REVISION NUMBER INDICATED. PLEASE CLOUD |
| | AND NUMBER ALL REVISIONS. SECTION 104.2.1.3. |
| | |
| | 5. SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO |
| | BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR |
| | THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. -- |
| | SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF |
| | DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 & |
| | 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE |
| | FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE |
| | CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE |
| | STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.-- |
| | SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| | EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON |
| | PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH. |
| | DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL |
| | DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1. |
| | |
| | 6. SHT P-08 GAS RISER ISOMETRIC DIAGRAM. THE GAS |
| | REGULATORS FOR THE DOMESTIC WATER BOILERS ARE NOT |
| | APPROVED. THE MAXIMUM INDIVIDUAL LOAD FOR THE MAXITROL |
| | MODEL 325-51 IS ONLY 250,000 BTU'S. THE RISER DIAGRAM |
| | INDICATES 400,000 BTU'S FOR EACH BOILER. (SEE ATTACHED |
| | SHEET). PLEASE SPECIFY THE CORRECT REGULATORS FOR THE |
| | BOILERS. SECTION 410.2(1). (ALSO CORRECT REGULATOR |
| | MODEL NUMBER ON DETAIL FOR WATER HEATERS SHEET P-07). |
| | |
| | 7. SHT P-16 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. RISER SHOWS 2 TUBS, WHEREAS THE FLOOR PLAN |
| | SHOWS ONE TUB. ALSO SEE SHT P-04A THE WATER SUPPLY IS |
| | SHOWN IN UNIT 214 WHICH IS RISER W2, BUT THE WATER |
| | SUPPLY FOR UNIT ON THE 6TH FLOOR IS SHOWN ON RISER W4 |
| | ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 104.2.1. |
| | |
| | 8. NOTE: WHEN SUBMITTING REVISIONS, PLEASE TURN OFF ALL |
| | PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION |
| | NUMBERS. LEAVING THE PREVIOUS CLOUDS AND REVISION |
| | NUMBERS CAUSES CONFUSION AND INCREASES THE TURN AROUND |
| | TIME FOR THE REVIEWS. THANK YOU. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |