Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop G
Sequence Number 5
Notes
Date Text
2007-10-15 14:33:13SEE COMMENTS FROM REVIEW FOR SHT P-08 DATED 10-13-07:
  
  
 DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED.
 SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE
 POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND
 CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH
 REGULATOR ON THE ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--NOT
 INDICATED FOR POOL HOUSE WATER HEATER.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE
 RESPONSE FOR COMMENT IS REVIEWED.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER
 HEATER MANUF. SHEETS REQUIRED.
  
 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL
 REGULATORS. INDICATED MODEL NUMBER USED FOR EACH
 REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL
 BE USED TO VERIFY CAPACITY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]