| 2007-10-15 14:33:13 | SEE COMMENTS FROM REVIEW FOR SHT P-08 DATED 10-13-07: |
| | |
| | |
| | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED. |
| | SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE |
| | POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND |
| | CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH |
| | REGULATOR ON THE ISOMETRIC. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED.--NOT |
| | INDICATED FOR POOL HOUSE WATER HEATER. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE |
| | RESPONSE FOR COMMENT IS REVIEWED. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER |
| | HEATER MANUF. SHEETS REQUIRED. |
| | |
| | 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL |
| | REGULATORS. INDICATED MODEL NUMBER USED FOR EACH |
| | REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL |
| | BE USED TO VERIFY CAPACITY. |
| | |