Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 5
Notes
Date Text
2007-06-09 17:28:25** UNSAT **
  
 1) NOTE: PLEASE SEE PERMIT 07050818 FOR LV DATA AND
 VOICE HAS BEEN PLACED ON HOLD FOR NO INSPECTIONS AS
 THESE SYSTEMS WERE NOT ON PRIMARY PLANS AND THE
 REVISION HAVE FAILED WITH COMMENTS FOR THESE ITEMS.
  
 2) NOTE: PLEASE SEE THAT NO LOW VOLTAGE PERMIT HAS BEEN
 APPLIED FOR ALL OTHER LOW VOLTAGE SYSTEMS FOR
 CATV/PHONE SYSTEMS WHICH ARE ONE MASTER/PRIME PLANS.
 PLEASE SE FBC ADMIN SECTION 105.1 WHICH REQUIRES
 PERMITS. THE VALUE IS BASED ON THESE SEPARATELY AS THE
 FBC VALUATION TABLES FOR PERMIT DOES NOT INCLUDE LV.
  
 3) NOTE: PLEASE SEE THE VOICE/DATA OUTLETS ARE NO ADDED
 TO PLANS AS *HAND-DRAWN* WHICH IS NOT PERMITTED UNDER
 FS 471.025. NO CHANGES ARE TO BE MADE TO THE ENGINEERS
 PLANS.
 PLEASE KNOW AS THESE ITEMS WERE NOT PART OF THE
 ORIGINAL PLANS, SEPARATE PLANS ARE TO BE SUBMITTED
 WHICH WILL BE PLACED UNDER PERMIT WHICH IS NOTED ABOVE
 BEING PLACED ON HOLD.
  
  
 4) NOTE: PLEASE SEE AS IT APPEARS SOME LIGHTING HAS
 BEEN REVISED, PLEASE SUBMIT REVISED ENERGY CALCULATIONS
 PER FBC CHAPTER 13.
  
 5) NOTE: PLEASE SEE THAT THE PARCEL CONTAINS SEVERAL
 HOLDS FROM THE ASSISTANT BUILDING OFFICIAL, LICENSE
 SUPERVISOR AND ADDRESSING REVIEWER. PLEASE SEE HOLDS
 STATES ADDRESS IS TO BE CHANGED AND NO PERMITS CAN BE
 ISSUED UNTIL THESE ITEMS ARE DONE.
 PLEASE CONTACT THE ADDRESSING REVIEWER AND THE ABOVE
 MENTIONED PERSON FOR NEW ADDRESS AS THE TITLE BLOCKS ON
 PLANS WILL BE REQUIRED TO COORDINATE FOR THESE. PLEASE
 ISSUE ALL NEW REVISED SHEETS FOR ELECTRICAL ONCE THIS
 IS DONE.
  
 6) NOTE: PLEASE SEE REDLINED PLANS WHICH REQUESTED UPON
 ISSUANCE OF PERMIT FOR NOTES FOR SIGNAGE ON STORAGE
 ROOM DOORS AND OTHER REDLINED NOTES. PLEASE SEE THE
 PREVIOUS REVIEW ON 7/15/2006 AND NOTES BELOW WHICH ARE
 FROM REDLINED PLANS AND REVIEW OF THAT DATE.
  
  
 **** NOTES REDLINED ****
  
  
 1) EM BATTERY BACK LT FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE FIRE PUMP
 RM. LS 101 7.8,7.9, NEC 700.16.
  
  
 2) SIGNAGE REQUIRED AT ALL DOORS FOR ENTRANCE THROUGH
 STORAGE RMS TO ELECTRICAL ROOMS. SIGNAGE SHALL INCLUDE
 WORDING. "CLEAR PATH OF EGRESS TO ALL ELECTRICAL ROOMS
 SHALL BE MAINTAINED AT ALL TIMES" OR WORDS TO THAT
 EFFECT.
 MIN 1" LTRS ON CONTRASTING BACK AND SIGNAGE SHALL BE
 PERMANENTLY AFFIXED.
  
 3) SIGNAGE REQUIRED FOR ALL MAINS AND DISCONNECTING
 MEANS.
 230.2E,700.8,701.9
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]