| 2007-06-09 17:28:25 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE PERMIT 07050818 FOR LV DATA AND |
| | VOICE HAS BEEN PLACED ON HOLD FOR NO INSPECTIONS AS |
| | THESE SYSTEMS WERE NOT ON PRIMARY PLANS AND THE |
| | REVISION HAVE FAILED WITH COMMENTS FOR THESE ITEMS. |
| | |
| | 2) NOTE: PLEASE SEE THAT NO LOW VOLTAGE PERMIT HAS BEEN |
| | APPLIED FOR ALL OTHER LOW VOLTAGE SYSTEMS FOR |
| | CATV/PHONE SYSTEMS WHICH ARE ONE MASTER/PRIME PLANS. |
| | PLEASE SE FBC ADMIN SECTION 105.1 WHICH REQUIRES |
| | PERMITS. THE VALUE IS BASED ON THESE SEPARATELY AS THE |
| | FBC VALUATION TABLES FOR PERMIT DOES NOT INCLUDE LV. |
| | |
| | 3) NOTE: PLEASE SEE THE VOICE/DATA OUTLETS ARE NO ADDED |
| | TO PLANS AS *HAND-DRAWN* WHICH IS NOT PERMITTED UNDER |
| | FS 471.025. NO CHANGES ARE TO BE MADE TO THE ENGINEERS |
| | PLANS. |
| | PLEASE KNOW AS THESE ITEMS WERE NOT PART OF THE |
| | ORIGINAL PLANS, SEPARATE PLANS ARE TO BE SUBMITTED |
| | WHICH WILL BE PLACED UNDER PERMIT WHICH IS NOTED ABOVE |
| | BEING PLACED ON HOLD. |
| | |
| | |
| | 4) NOTE: PLEASE SEE AS IT APPEARS SOME LIGHTING HAS |
| | BEEN REVISED, PLEASE SUBMIT REVISED ENERGY CALCULATIONS |
| | PER FBC CHAPTER 13. |
| | |
| | 5) NOTE: PLEASE SEE THAT THE PARCEL CONTAINS SEVERAL |
| | HOLDS FROM THE ASSISTANT BUILDING OFFICIAL, LICENSE |
| | SUPERVISOR AND ADDRESSING REVIEWER. PLEASE SEE HOLDS |
| | STATES ADDRESS IS TO BE CHANGED AND NO PERMITS CAN BE |
| | ISSUED UNTIL THESE ITEMS ARE DONE. |
| | PLEASE CONTACT THE ADDRESSING REVIEWER AND THE ABOVE |
| | MENTIONED PERSON FOR NEW ADDRESS AS THE TITLE BLOCKS ON |
| | PLANS WILL BE REQUIRED TO COORDINATE FOR THESE. PLEASE |
| | ISSUE ALL NEW REVISED SHEETS FOR ELECTRICAL ONCE THIS |
| | IS DONE. |
| | |
| | 6) NOTE: PLEASE SEE REDLINED PLANS WHICH REQUESTED UPON |
| | ISSUANCE OF PERMIT FOR NOTES FOR SIGNAGE ON STORAGE |
| | ROOM DOORS AND OTHER REDLINED NOTES. PLEASE SEE THE |
| | PREVIOUS REVIEW ON 7/15/2006 AND NOTES BELOW WHICH ARE |
| | FROM REDLINED PLANS AND REVIEW OF THAT DATE. |
| | |
| | |
| | **** NOTES REDLINED **** |
| | |
| | |
| | 1) EM BATTERY BACK LT FIXTURE OF SOME |
| | SORT WILL BE REQUIRED IN THE FIRE PUMP |
| | RM. LS 101 7.8,7.9, NEC 700.16. |
| | |
| | |
| | 2) SIGNAGE REQUIRED AT ALL DOORS FOR ENTRANCE THROUGH |
| | STORAGE RMS TO ELECTRICAL ROOMS. SIGNAGE SHALL INCLUDE |
| | WORDING. "CLEAR PATH OF EGRESS TO ALL ELECTRICAL ROOMS |
| | SHALL BE MAINTAINED AT ALL TIMES" OR WORDS TO THAT |
| | EFFECT. |
| | MIN 1" LTRS ON CONTRASTING BACK AND SIGNAGE SHALL BE |
| | PERMANENTLY AFFIXED. |
| | |
| | 3) SIGNAGE REQUIRED FOR ALL MAINS AND DISCONNECTING |
| | MEANS. |
| | 230.2E,700.8,701.9 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |