Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop M
Sequence Number 4
Notes
Date Text
2006-09-06 00:00:00PROVISO:
 PER RESPONSE LETTER DATED JUNE 19, 2006
 THE FOLLOWING ITEMS WILL BE REVISED
 AFTER PERMIT IS ISSUED.
  
 PLAN SHEET M-04 8 X 4 DUCT PENETRATING
 STORAGE ROOM 213 & 228, DUCT SHALL
 COMPLY WITH 2001 FMC 607.1.3 #3 ITEMS 1
 THROUGH 4.
  
 PER 2001 FBC 705.2.4.6, AUTOMATIC
 SPRINKLERS - AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM SHALL BE INSTALLED AT
 THE TOP AND AT ALTERNATE FLOOR LEVELS IN
 REFUSE AND LAUNDRY CHUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].