Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 4
Notes
Date Text
2006-07-15 00:00:00**** NOTES REDLINED ****
  
  
 1) EM BATTERY BACK LT FIXTURE OF SOME
 SORT WILL BE REQUIRED IN THE FIRE PUMP
 RM. LS 101 7.8,7.9, NEC 700.16.
  
  
 2) SIGNAGE REQUIRED AT ALL DOORS FOR
 ENTRANCE THROUGH STORAGE RMS TO
 ELECTRICAL ROOMS. SIGNAGE SHALL INCLUDE
 WORDING. "CLEAR PATH OF EGRESS TO ALL
 ELECTRICAL ROOMS SHALL BE MAINTAINED AT
 ALL TIMES" OR WORDS TO THAT EFFECT.
 MIN 1" LTRS ON CONTRASTING BACK AND
 SIGNAGE SHALL BE PERMANANTLY AFFIXED.
  
 3) SIGNAGE REQUIRED FOR ALL MAINS AND DISCONNECTING
 MEANS.
 230.2E,700.8,701.9
  
  
 ***********************************
  
 FIRE PUMP SUBMITTIALS STAMPED AND
 INSERTED INTO SPEC BOOKS.