| Plan Review Notes For Permit 05041760 |
| Permit Number |
05041760 |
|
| Review Stop |
B |
| Sequence Number |
35 |
|
| Notes |
| Date |
Text |
| 2007-09-30 08:27:22 | BUILDING PLAN REVIEW | | | PERMIT: 05041760 | | | ADD: 465 W EXECUTIVE CENTER DR | | | CONT: THE WEITZ CO | | | TEL: (561)719-0102 | | | | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION# 4REVIEW | | | SHEET: A-6.1 | | | ACTION: DENIED | | | | | | SHEET A-6.1,DEETAIL 12 | | | | | | 1)THE HANDICAPPED SUITE KITHEN AREA, THE SINK BASE | | | CABINET INDICATES A 2'-3" WIDTH IN THE OPENING. | | | SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE | | | MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE | | | FINISH FLOOR. | | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH | | | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH | | | SINKS. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | |
|