Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop P
Sequence Number 3
Notes
Date Text
2006-05-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7. -
 PER RESPONSE SHEET CONTRACTOR WAS
 SUPPOSED TO DO THIS. NO STAMPED SETS OF
 PLANS OR WORKSHEETS SUBMITTED.
 ***RESPONSE NOTED, BUT "SULLIVAN HAS NOT
 DONE THIS.
  
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT. - SHT C-9 INDICATES A 3"
 DIP WATER SERVICE, BUT NO BACKFLOW SHOWN
 FOR WATER SERVICE TO BUILDING.
 ***RESPONSE NOTED, BUT I CONTACTED MR.
 DEAN LAUDERMILK FROM WPB ENGINEERING,
 AND HE ADVISED ME THAT NEW SHEETS, DATED
 4-4-06, SHOWING A SEPARATE 8" LINE FOR
 FIRE AND 4" LINE FOR DOMESTIC WATER WITH
 A 3" METER ARE SHOWN. PLEASE SUBMIT NEW
 SHEETS FOR CIVIL WITH NEXT RESUBMITTAL.
 SECTION 106.1.1.
  
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 - NOT ADDRESSED, ALSO SEE FIG 30E.
 ***RESPONSE NOTED, MEASUREMENTS FOUND ON
 SHEETS A-1.1, A-1.4 & A-6.0,BUT THIS IS
 NOT SHOWN ON ANY OF THE ELEVATIONS ON
 SHEET A-6.2 AS INDICATED.
  
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 E. DISPENSERS 11-4.16.6 INDICATE HEIGHT
 AS REQUIRED. (PLANS SHOW WITHIN REACH)
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2 -
 CLEARANCE MEASUREMENT NOT SHOWN. NO
 CLEARANCE SHOWN AS OF YET.
 ***RESPONSE NOTED, BUT RESPONSE NOT
 ADEQUATE. W/C 'C' INDICATES GRAB BARS TO
 BE 36" MIN. WHEN THEY ARE TO BE 33" TO
 36". DETAIL FOR ACCESSIBLETOILET
 ACCESSORIES INDICATE THAT THE LIP OF THE
 URINAL TO BE 20". IT IS SUPPOSED TO BE
 17" MAX. PLUS SEE NOTES "C" FOR W/C AND
 "A" FOR LAVS.
  
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025. - THE DATE SEAL AND
 SIGNATURE SHALL BE PLACED ON SEAL.
 ***RESPONSE NOTED, BUT THE SEAL IS NOT
 DATED YET ON MANY SHEETS. ALSO SHEETS
 SEALED AFTER JAN. 1, 2006 SHALL BE
 SEALED WITH THE NEW "LICENCE" SEAL PER
 ATTACHED LETER FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGENEERS.
  
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - WILL CHECK
 WHEN ALL LENGTHS ARE SHOWN. ***RESPONSE
 NOTED, BUT THE TOTAL DEVELOPED LENGTH
 ADDS UP TO 232FT TO R.T.U #2, NOT 244
 FT. AS SHOWN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE. -RESPONSE NOTED,
 BUT PLANS STILL SHOW 7" WATER COLUMN.
 ***RESPONSE NOTED, BUT THE PLANS STILL
 SHOW 7"WC PRESSURE. PLEASE CALL MR.
 ROLAND PARKER, SERVICE MANAGER FLORIDA
 PUBLIC UTILITIES AT (561) 838-1818 AS HE
 HAS INDICATED TO ME THAT FPU DELIVERS
 12" TO 14" WATER COLUMN MINIMUM
 PRESSURE.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - GAS
 DRYER AND RTU'S MANUF. SHEETS NOT FOUND.
 ***RESPONSE NOTED, BUT MANUF. SHEETS FOR
 THE RTU-2 UNITS HAVE NOT BEEN SUBMITTED.
 ALSO DRYER MANUF. SPECIFICATION SHEET
 INDICATES THE BTU'SARE 165,000 WHERE
 AS THE RISER DIAGRAM INDICATES 215,000
 BTU'S. PLEASE CLARIFY AND CORRELATE THE
 MANUF. INFORMATION WITH THE RISER
 DIAGRAM.
  
 ***************NEW COMMENT**************
 1C. SHT P-08 THE FOLLOWING INFORMATION
 HAS BEEN DELETED FROM PREVIOUS SUBMITTED
 SHEETS:
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 2C. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]