| Date |
Text |
| 2006-05-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW: |
| | 1. PLANS SHALL BE ROUTED TO DBPR |
| | DIVISION OF HOTEL AND RESTURANTS FOR |
| | REVIEW. MINIMUM OF 2 STAMPED SETS OF |
| | PLANS SHALL BE SUBMITTED TO THE CITY FOR |
| | REVIEW WITH 2 PAGE "WORK SHEETS" |
| | ATTACHED TO EACH SET. SECTION 101.4.7. - |
| | PER RESPONSE SHEET CONTRACTOR WAS |
| | SUPPOSED TO DO THIS. NO STAMPED SETS OF |
| | PLANS OR WORKSHEETS SUBMITTED. |
| | ***RESPONSE NOTED, BUT "SULLIVAN HAS NOT |
| | DONE THIS. |
| | |
| | 4. SHT C-8 CIVIL WATER AND SEWER PLANS. |
| | NO WATER SERVICE TO THE BUILDING IS |
| | SHOWN. PLEASE INDICATE WATER SERVICE ON |
| | PLANS INCLUDING PIPE SIZE, VALVES, |
| | BACKFLOW ECT. - SHT C-9 INDICATES A 3" |
| | DIP WATER SERVICE, BUT NO BACKFLOW SHOWN |
| | FOR WATER SERVICE TO BUILDING. |
| | ***RESPONSE NOTED, BUT I CONTACTED MR. |
| | DEAN LAUDERMILK FROM WPB ENGINEERING, |
| | AND HE ADVISED ME THAT NEW SHEETS, DATED |
| | 4-4-06, SHOWING A SEPARATE 8" LINE FOR |
| | FIRE AND 4" LINE FOR DOMESTIC WATER WITH |
| | A 3" METER ARE SHOWN. PLEASE SUBMIT NEW |
| | SHEETS FOR CIVIL WITH NEXT RESUBMITTAL. |
| | SECTION 106.1.1. |
| | |
| | 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S |
| | TO BE 18" OFF THE WALL TO THE CENTERLINE |
| | OF THE FIXTURE, AS REQUIRED IN FIG. 28. |
| | - NOT ADDRESSED, ALSO SEE FIG 30E. |
| | ***RESPONSE NOTED, MEASUREMENTS FOUND ON |
| | SHEETS A-1.1, A-1.4 & A-6.0,BUT THIS IS |
| | NOT SHOWN ON ANY OF THE ELEVATIONS ON |
| | SHEET A-6.2 AS INDICATED. |
| | |
| | 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE |
| | ACCESSIBLE FIXTURES: |
| | FOR W/C'S |
| | E. DISPENSERS 11-4.16.6 INDICATE HEIGHT |
| | AS REQUIRED. (PLANS SHOW WITHIN REACH) |
| | FOR LAVS |
| | A. HEIGHT & CLEARANCES 11-4.19.2 - |
| | CLEARANCE MEASUREMENT NOT SHOWN. NO |
| | CLEARANCE SHOWN AS OF YET. |
| | ***RESPONSE NOTED, BUT RESPONSE NOT |
| | ADEQUATE. W/C 'C' INDICATES GRAB BARS TO |
| | BE 36" MIN. WHEN THEY ARE TO BE 33" TO |
| | 36". DETAIL FOR ACCESSIBLETOILET |
| | ACCESSORIES INDICATE THAT THE LIP OF THE |
| | URINAL TO BE 20". IT IS SUPPOSED TO BE |
| | 17" MAX. PLUS SEE NOTES "C" FOR W/C AND |
| | "A" FOR LAVS. |
| | |
| | 12. ALL MECH., ELECT., & PLMB. SHEETS. |
| | EACH SHEET OF PLANS WHICH MUST BE SEALED |
| | UNDER THE PROVISIONS OF CHAPTER 471 |
| | SHALL BE SEALED, SIGNED AND DATED BY THE |
| | PROFESSIONAL ENGINEER. 61G15-23.002(1). |
| | NO DATE AFFIXED TO SEAL/SIGNATURE. - |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME AND LICENSE NUMBER, AS WELL AS THE |
| | NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. 61G15-23.002(2) |
| | FAC, & FS 471.025. - THE DATE SEAL AND |
| | SIGNATURE SHALL BE PLACED ON SEAL. |
| | ***RESPONSE NOTED, BUT THE SEAL IS NOT |
| | DATED YET ON MANY SHEETS. ALSO SHEETS |
| | SEALED AFTER JAN. 1, 2006 SHALL BE |
| | SEALED WITH THE NEW "LICENCE" SEAL PER |
| | ATTACHED LETER FROM THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGENEERS. |
| | |
| | 30. THE FOLLOWING INFORMATION IS RQUIRED |
| | FOR GAS PERMIT: |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). - WILL CHECK |
| | WHEN ALL LENGTHS ARE SHOWN. ***RESPONSE |
| | NOTED, BUT THE TOTAL DEVELOPED LENGTH |
| | ADDS UP TO 232FT TO R.T.U #2, NOT 244 |
| | FT. AS SHOWN. |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - |
| | DELEVERY PRESSURE IS USUALLY 11 TO 14 |
| | INCHES OF WATER COLUMN OR 56 INCHES OF |
| | WATER COLUMN, AND PLANS SHOW 7". PLEASE |
| | CHECK WITH GAS PROVIDER AND VERIFY THE |
| | DELIVERY PRESSURE. -RESPONSE NOTED, |
| | BUT PLANS STILL SHOW 7" WATER COLUMN. |
| | ***RESPONSE NOTED, BUT THE PLANS STILL |
| | SHOW 7"WC PRESSURE. PLEASE CALL MR. |
| | ROLAND PARKER, SERVICE MANAGER FLORIDA |
| | PUBLIC UTILITIES AT (561) 838-1818 AS HE |
| | HAS INDICATED TO ME THAT FPU DELIVERS |
| | 12" TO 14" WATER COLUMN MINIMUM |
| | PRESSURE. |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. - GAS |
| | DRYER AND RTU'S MANUF. SHEETS NOT FOUND. |
| | ***RESPONSE NOTED, BUT MANUF. SHEETS FOR |
| | THE RTU-2 UNITS HAVE NOT BEEN SUBMITTED. |
| | ALSO DRYER MANUF. SPECIFICATION SHEET |
| | INDICATES THE BTU'SARE 165,000 WHERE |
| | AS THE RISER DIAGRAM INDICATES 215,000 |
| | BTU'S. PLEASE CLARIFY AND CORRELATE THE |
| | MANUF. INFORMATION WITH THE RISER |
| | DIAGRAM. |
| | |
| | ***************NEW COMMENT************** |
| | 1C. SHT P-08 THE FOLLOWING INFORMATION |
| | HAS BEEN DELETED FROM PREVIOUS SUBMITTED |
| | SHEETS: |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | |
| | 2C. SEE ATTACHED SHEET CONCERNING THE |
| | DESIGN PROFESSIONAL AND FS 553.80(2)(B). |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |