| Notes |
| Date |
Text |
| 2007-09-05 12:54:56 | REVISION DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SHT P-08 GAS RISER ISOMETRIC DIAGRAM. THE GAS | | | REGULATORS FOR THE DOMESTIC WATER BOILERS ARE NOT | | | APPROVED. THE MAXIMUM INDIVIDUAL LOAD FOR THE MAXITROL | | | MODEL 325-51 IS ONLY 250,000 BTU'S. THE RISER DIAGRAM | | | INDICATES 400,000 BTU'S FOR EACH BOILER. (SEE ATTACHED | | | SHEET). PLEASE SPECIFY THE CORRECT REGULATORS FOR THE | | | BOILERS. SECTION 410.2(1). (ALSO CORRECT REGULATOR | | | MODEL NUMBER ON DETAIL FOR WATER HEATERS SHEET P-07). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|