| 2006-04-18 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PELASE SUBMIT THE MANUFACTURES |
| | SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE |
| | PUMP CONTROLLER. THIS WAS REQUESTED ON |
| | THE TWO PREVIOUS REVIEWS AND THE |
| | RESPONSE LTR MENTIONS THESE ARE TO BE |
| | SUBMITTED, HOWEVER THESE COULD NOT BE |
| | LOCATED ON PACKAGE. |
| | THESE ARE NEED TO VERIFY COMPLIANCE FOR |
| | LOCKED ROTOR SETTING FOR MAX OCP , THE |
| | MEANS OF DISCONNECT REQUIRED PER NFPA-20 |
| | CHAPTERS 6 AND 7, (1999)7-3.6, 7-4.2 AND |
| | NFPA-70.695.5, 230.76,230.79 |
| | |
| | 2) NOTE: PLEASE SEE THAT ALL ELECTRICAL |
| | SHEETS ARE SIGNED, DATED AND SEALED AS |
| | REQUIRED PER FS 471.025 |
| | PLEASE SEE NEW SHEETS ARE SIGNED, DATED |
| | AND SEALED AND MANY OF THE OTHER SHEETS |
| | ARE NOT DATED. |
| | PLEASE SEE PLANS MUST BE RE-SEALED AS |
| | THE SEAL AS SHOWN IS NO LONGER |
| | ACCEPTABLE AS PUBLIC RECORD FOR THE |
| | FLORIDA BOARD OF PROFESSINAL ENGINEER'S. |
| | PLEASE SEE FAC 61G15-23.001 WHICH IN FEB |
| | 04 CHANGED TO NOW REQUIRE ALL SEALS TO |
| | CONTAIN THE WORDING OF "LICENSE" AND |
| | COULD NO LONGER USE "CERTIFICATE". |
| | PLEASE KNOW, AN EXTENSION WAS GRANTED TO |
| | THE DATE OF 12/31/05 TO GIVE ALL |
| | ENGINEERS 2 YRS TO OBTAIN NEW SEALS. WE |
| | CAN NO LONGER ACCEPT OLD SEALS. |
| | PLEASE SEE PREVIOUS SHEETS WERE NOT |
| | DATED. |
| | |
| | ** PLEASE SEE THE FOLLOWING IS A NEW |
| | COMMENT AND CAN BE SET UP AS A "PROVISO" |
| | WHICH WOULD REQUIRE REVISIONS BEFORE |
| | ROUGH OR MAY BE ADDRESSED AT THIS TIME |
| | SINCE PLANS ARE COMING BACK FOR COMMENTS |
| | AND COMMENTS FROM OTHER TRADES. |
| | |
| | 1) NOTE: PLEASE SEE NFPA-101 (2003) |
| | 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES AMIN |
| | OF 10FT CANDLE (108LUX) IN STAIR TOWERS. |
| | |
| | PLEASE ALSO KNOW A MIN OF ONE BATTERY |
| | BACK UP FIXTURE ON EVERY OTHER LEVEL |
| | MEETING THE MIN OF 1FT CANDLE UNDER |
| | EMERGENCY CONDITIONS WILL BE REQUIRED. |
| | PLEASE PROVIDE PHOTO-METRICS FOR STAIRS |
| | WALKING SURFACE. PLEASE KNOW, THIS CAN |
| | BE A TYPICAL DETAIL AS EACH STAIR TOWER |
| | AND FLOOR LEVEL IS THE SAME. |
| | PLEASE KNOW, THE BATTERY BACK UP FIXTURE |
| | ON EVERY OTHER LEVEL AT A MIN IS |
| | REQUIRED DUE THE POSSIBLE TRIPPING IS |
| | DISCONNECTING OF A SINGLE MEANS OF OCP |
| | AND WOULD LEAVE STAIR TOWERS IN TOTAL |
| | DARKNESS. |
| | PLEASE SEE THE CORRIDORS ARE ONLY |
| | REQUIRED TO MEET 1 FT CANDLE UNDER |
| | NORMAL AND EMERGENCY CONDITIONS. |
| | A BATTERY BACK UP FIXTURE MEETING THE |
| | MIN FT CANDLES WILL BE REQUIRED IN THE |
| | EGRESS PATH. |
| | ** PLEASE KNOW, THIS WAS NOT IN PREVIOUS |
| | COMMENTS FROM ELECTRICAL REVIEW, HOWEVER |
| | THE NEW REQUIREMENTS OF THE 2003 LS101 |
| | WAS ADOPTED BY THE STATE OF FLORIDA ON |
| | JAN 1ST, 2005. |
| | ** AS MENTIONED ABOVE THIS CAN BE DONE |
| | AT THIS TIME OR A "PROVISO" BEFORE FIRST |
| | ROUGH INSPECTION CAN BE SET UP. |
| | IF THERE ARE ANY QUESTIONS ON THIS, |
| | PLEASE CALL. |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |