Notes
Date Text
2006-04-18 00:00:00*** UNSAT ***
  
 1) NOTE: PELASE SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER. THIS WAS REQUESTED ON
 THE TWO PREVIOUS REVIEWS AND THE
 RESPONSE LTR MENTIONS THESE ARE TO BE
 SUBMITTED, HOWEVER THESE COULD NOT BE
 LOCATED ON PACKAGE.
 THESE ARE NEED TO VERIFY COMPLIANCE FOR
 LOCKED ROTOR SETTING FOR MAX OCP , THE
 MEANS OF DISCONNECT REQUIRED PER NFPA-20
 CHAPTERS 6 AND 7, (1999)7-3.6, 7-4.2 AND
 NFPA-70.695.5, 230.76,230.79
  
 2) NOTE: PLEASE SEE THAT ALL ELECTRICAL
 SHEETS ARE SIGNED, DATED AND SEALED AS
 REQUIRED PER FS 471.025
 PLEASE SEE NEW SHEETS ARE SIGNED, DATED
 AND SEALED AND MANY OF THE OTHER SHEETS
 ARE NOT DATED.
 PLEASE SEE PLANS MUST BE RE-SEALED AS
 THE SEAL AS SHOWN IS NO LONGER
 ACCEPTABLE AS PUBLIC RECORD FOR THE
 FLORIDA BOARD OF PROFESSINAL ENGINEER'S.
 PLEASE SEE FAC 61G15-23.001 WHICH IN FEB
 04 CHANGED TO NOW REQUIRE ALL SEALS TO
 CONTAIN THE WORDING OF "LICENSE" AND
 COULD NO LONGER USE "CERTIFICATE".
 PLEASE KNOW, AN EXTENSION WAS GRANTED TO
 THE DATE OF 12/31/05 TO GIVE ALL
 ENGINEERS 2 YRS TO OBTAIN NEW SEALS. WE
 CAN NO LONGER ACCEPT OLD SEALS.
 PLEASE SEE PREVIOUS SHEETS WERE NOT
 DATED.
  
 ** PLEASE SEE THE FOLLOWING IS A NEW
 COMMENT AND CAN BE SET UP AS A "PROVISO"
 WHICH WOULD REQUIRE REVISIONS BEFORE
 ROUGH OR MAY BE ADDRESSED AT THIS TIME
 SINCE PLANS ARE COMING BACK FOR COMMENTS
 AND COMMENTS FROM OTHER TRADES.
  
 1) NOTE: PLEASE SEE NFPA-101 (2003)
 7.8.1.3 AND 7.9.2.2 WHICH REQUIRES AMIN
 OF 10FT CANDLE (108LUX) IN STAIR TOWERS.
  
 PLEASE ALSO KNOW A MIN OF ONE BATTERY
 BACK UP FIXTURE ON EVERY OTHER LEVEL
 MEETING THE MIN OF 1FT CANDLE UNDER
 EMERGENCY CONDITIONS WILL BE REQUIRED.
 PLEASE PROVIDE PHOTO-METRICS FOR STAIRS
 WALKING SURFACE. PLEASE KNOW, THIS CAN
 BE A TYPICAL DETAIL AS EACH STAIR TOWER
 AND FLOOR LEVEL IS THE SAME.
 PLEASE KNOW, THE BATTERY BACK UP FIXTURE
 ON EVERY OTHER LEVEL AT A MIN IS
 REQUIRED DUE THE POSSIBLE TRIPPING IS
 DISCONNECTING OF A SINGLE MEANS OF OCP
 AND WOULD LEAVE STAIR TOWERS IN TOTAL
 DARKNESS.
 PLEASE SEE THE CORRIDORS ARE ONLY
 REQUIRED TO MEET 1 FT CANDLE UNDER
 NORMAL AND EMERGENCY CONDITIONS.
 A BATTERY BACK UP FIXTURE MEETING THE
 MIN FT CANDLES WILL BE REQUIRED IN THE
 EGRESS PATH.
 ** PLEASE KNOW, THIS WAS NOT IN PREVIOUS
 COMMENTS FROM ELECTRICAL REVIEW, HOWEVER
 THE NEW REQUIREMENTS OF THE 2003 LS101
 WAS ADOPTED BY THE STATE OF FLORIDA ON
 JAN 1ST, 2005.
 ** AS MENTIONED ABOVE THIS CAN BE DONE
 AT THIS TIME OR A "PROVISO" BEFORE FIRST
 ROUGH INSPECTION CAN BE SET UP.
 IF THERE ARE ANY QUESTIONS ON THIS,
 PLEASE CALL.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]