Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 20
Notes
Date Text
2008-05-04 12:59:32** DENIED REVISIONS**
  
 ** REVIEW BASED ON NEW PLANS NOW SUBMITTED WHICH WERE
 NOT PREVIOUSLY SUBMITTED SHOWING THE ENCLOSURE.
  
 1) NOTE: PLEASE KNOW THE PLANS NOW SHOW AN ENCLOSURE
 BUILT RIGHT UP NEXT TO THE GENERATOR. PLEASE PROVIDE
 THE MINIMUM CLEARANCES PER THE GENERATOR MANUFACTURE.
 THIS OFFICE IS NOT AWARE OF ANY GENERATOR MANUFACTURE
 WHO ALLOWS ONLY 6 INCHES OF CLEARANCE ON THE SIDES. IN
 FACT THIS MANUFACTURE AS SUBMITTED REQUIRED AS MUCH AS
 5FT ON PREVIOUS PROJECTS/DOCUMENTS SUBMITTED TO THIS
 OFFICE ON PREVIOUS REVIEWS.
 PLEASE ALSO KNOW THAT REMOVABLE PANELS ARE NOT
 ACCEPTABLE AS THESE ARE NOT READILY ACCESSIBLE OR
 ACCESSIBLE AS REQUIRED BY CODE.
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND THIS FENCING
 SHALL BE REMOVED IMMEDIATELY UNTIL SUCH TIME AS MINIMUM
 CODE COMPLIANCE IS DETERMINED.BASED ON INFORMATION TO
 THIS OFFICE THIS IS A CURRENT HAZARD. THIS INFORMATION
 HAS BEEN FORWARDED TO INSPECTION SERVICES AS OF THIS
 REVIEW.
 PLEASE SEE THE LIMITATIONS AS SHOWN ON PLANS WITH ONLY
 6 INCHES ON TWO SIDES AND ONLY 1.5 AND 2FT ON THE OTHER
 IS NOT PERMITTED.
 MUST SUPPLY *MINIMUM* PER CODE AND MANUFACTURE.
 90.7, 110.3, 110.26, 100, 700.12B6, 701.10B5, 702.11
 PLEASE ALSO SEE SECTION 7 OF NFPA-110.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]