2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
 1. PLANS SHALL BE ROUTED TO DBPR
 DIVISION OF HOTEL AND RESTURANTS FOR
 REVIEW. MINIMUM OF 2 STAMPED SETS OF
 PLANS SHALL BE SUBMITTED TO THE CITY FOR
 REVIEW WITH 2 PAGE "WORK SHEETS"
 ATTACHED TO EACH SET. SECTION 101.4.7. -
 PER RESPONSE SHEET CONTRACTOR WAS
 SUPPOSED TO DO THIS. NO STAMPED SETS OF
 PLANS OR WORKSHEETS SUBMITTED.
 3. GREASE INTERCEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE.
 (561) 837-4074, E-MAIL [email protected],
 OR FAX (561) 659-7458. THE DETERMINATION
 WORKSHEET FROM MR. COMPO SHALL BE
 ATTACHED TO PLANS WHEN RESUBMITTING FOR
 REVIEW. - NO INFORMATION FROM MR. COMPO
 AS OF YET. I WILL CHECK TO SEE IF HE HAS
 A DETERMINATION FOR THIS JOB.
 4. SHT C-8 CIVIL WATER AND SEWER PLANS.
 NO WATER SERVICE TO THE BUILDING IS
 SHOWN. PLEASE INDICATE WATER SERVICE ON
 PLANS INCLUDING PIPE SIZE, VALVES,
 BACKFLOW ECT. - SHT C-9 INDICATES A 3"
 DIP WATER SERVICE, BUT NO BACKFLOW SHOWN
 FOR WATER SERVICE TO BUILDING.
 5. SHTS A-1.0, & A-6.1,(DETAILS 10 & 11)
 LOUNGE SINK SHALL COMPLY WITH 11-4.24
 AND ALL SUBSECTIONS. SHOW THE FOLLOWING:
 B. KNEE CLEARANCE 11-4.24.3 - KNEE
 CLEARANCE NOT SHOWN.
 C. SINK DEPTH 11-4.24.4 - SINK DEPTH
 NOT SHOWN.
 D. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE
 FORWARD APPROACH, AND SHALL EXTEND A
 MAXIMUM 19" UNDERNEATH THE SINK. CABINET
 DOORS ARE NOT APPROVED, MUST BE "CLEAR"
 FLOOR SPACE. - CLEAR FLOOR SPACE SHALL
 BE SHOWN ON THE FLOOR PLAN.
 E. EXPOSED PIPES & SURFACES 11-4.24.6 -
 NO RESPONSE TO THIS REQUIREMENT.
 F. FAUCETS 11-4.24.7 - NO RESPONSE TO
 THIS REQUIREMENT.
 6. SHOW COMPLIANCE WITH SECTION 11-9.1.4
 INDICATE ROOM NUMBERS FOR EACH
 REQUIREMENT. - THERE ARE 6 DIFFERENT
 TYPES OF UNITS SHOWN, BUT ONLY SUITES 1,
 2, AND A SHOW ACCESSIBLE UNITS. PLEASE
 INDICATE WHY SUITES B, C, AND D HAVE NO
 ACCESSIBLE UNITS AS REQUIRED BY SECTION
 11-9.1.4.
 9. SHT A-6.2 SHOW THE ACCESSIBLE W/C'S
 TO BE 18" OFF THE WALL TO THE CENTERLINE
 OF THE FIXTURE, AS REQUIRED IN FIG. 28.
 - NOT ADDRESSED, ALSO SEE FIG 30E.
 10) SHT A-6.2 SHOW THE FOLLOWING FOR THE
 ACCESSIBLE FIXTURES:
 FOR W/C'S
 A. CLEAR FLOOR SPACE. 11-4.16.2 -
 SUPERIMPOSE CLEAR FLOOR SPACE ON PLANS.
 SEE FIG'S 28 & 30E.
 D. FLUSH CONTROLS 11-4.16.5 - NOT
 INDICATED TO WIDE SIDE OF W/C.
 E. DISPENSERS 11-4.16.6 - INDICATE
 HEIGHT AS REQUIRED.
 FOR URINAL
 B. CLEAR FLOOR SPACE 11-4.18.3 - NOT
 SHOWN.
 FOR LAVS
 A. HEIGHT & CLEARANCES 11-4.19.2 -
 CLEARANCE MEASUREMENT NOT SHOWN.
 B. CLEAR FLOOR SPACE 11-4.19.3 - SHOW
 ON PLANS.
 C. EXPOSED PIPES & SURFACES 11-4.19.4 -
 INDICATE METHOD.
 D. FAUCETS 11-4.19.5 - NOT ADDRESSED.
 12. ALL MECH., ELECT., & PLMB. SHEETS.
 EACH SHEET OF PLANS WHICH MUST BE SEALED
 UNDER THE PROVISIONS OF CHAPTER 471
 SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER. 61G15-23.002(1).
 NO DATE AFFIXED TO SEAL/SIGNATURE. -
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS THE
 NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. 61G15-23.002(2)
 FAC, & FS 471.025. - THE DATE SEAL AND
 SIGNATURE SHALL BE PLACED ON SEAL.
 13. SHT P-01 DOMESTIC PUMPS SHALL BE
 LISTED. SUBMIT MANUF. SPECIFICATION
 SHEETS. SECTION 303.4. - NO LISTING
 SHOWN ON SHEETS.
 19. SHT P-02C KITCHEN EQUIPMENT
 CONNECTION NOTES 1 & 4. THE AIR GAP
 SHALL BE TWICE THE DIAMETER OF THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1. - NOTE #1 3" AIR
 GAP REQUIRED. 1-1/2" SHOWN.
 30. THE FOLLOWING INFORMATION IS RQUIRED
 FOR GAS PERMIT:
 A. SHT P-08 SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF
 PIPE AND CORRESPONDING LENGTHS PER
 FBC-2001 FUEL GAS CODE. - NOT ALL
 SECTIONS SHOW THE LENGTH OF THE PIPES.
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - WILL CHECK
 WHEN ALL LENGTHS ARE SHOWN.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 DELEVERY PRESSURE IS USUALLY 11 TO 14
 INCHES OF WATER COLUMN OR 56 INCHES OF
 WATER COLUMN, AND PLANS SHOW 7". PLEASE
 CHECK WITH GAS PROVIDER AND VERIFY THE
 DELIVERY PRESSURE. -RESPONSE NOTED,
 BUT PLANS STILL SHOW 7" WATER COLUMN.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - GAS
 DRYER AND RTU'S MANUF. SHEETS NOT FOUND.
 ***************NEW COMMENT**************
 1B. GREASE INTERCEPTOR SHOWN IN STORAGE
 ROOM NOT APPROVED. GREASE INTERCEPTOR
 SHALL BE LOCATED OUTSIDE OF THE BUILDING
 FOR SERVICING. MISSED LOCATION ON FIRST
 REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS