2005-11-14 00:00:00*** UNSAT ***
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 INFORMATION NOW SUBMITTED AND/OR CHANGES
 IN DESIGN.
  
 1)NOTE: PLEASE SEE NO INFORMATION WAS
 SUBMITTED FOR FIRE PUMP WITH FIRE PUMP
 CONTROLLER. PLEASE SEE RISER DIAGRAM
 DOES NOT INCLUDE HP RATING OF PUMP IN
 ORDER TO VERIFY FEEDERS/SEC'S ETC.
 SPECS NOT SPECIFIC TO ANY ONE SIZE.
 PLEASE ALSO SUBMIT SPECS FOR PUMP, THE
 MANUFACTURE CUT SHEETS.
  
 2)NOTE: PLEASE SEE NEC NFPA-70,
 701.11(B)3, WHICH REQUIRES ADDITIONAL
 "ON-SITE" FUEL SOURCE WHEN RELYING ON
 THE UTILITY COMPANY ONLY FOR FUEL.
 PLEASE SUBMIT SPECS/ CUT SHEETS FOR
 "ON-SITE" TANK, LP). PLEASE SEE FIRE
 REVIEW COMMENTS FOR SIZING OF THE TANK
 AND WHETHER OR NOT THE SIZE MAY REQUIRE
 TANK TO BE DIRECTLY BURIED IN THE
 GROUND.
  
 3)NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS CORRECTIONS MADE TO PLANS FOR
 GFI PROTECTION FOR ALL KITCHEN CIRCUITS
 15AND 20A AND 120V. PER 2002 NEC 210.8B3
 COULD NOT LOCATE THIS.
  
 4)NOTE: PLEASE SEE EEP AND ELP WILL BE
 REQUIRED TO HAVE MCB'S AS SPECS FOR ATS
 SWITCH SUBMITTED FOR BOTH UNITS DOES NOT
 CONTAIN AN MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF THE ATS FOR
 DISCONNECTING FEEDERS COMING INTO
 BUILDING FROM GEN.
 225.31,225.34.
 PLEASE ALSO VERIFY IF THE SPECS FOR
 ATS'S SUBMITTED IS FOR BOTH.
 ** PLEASE KNOW, IT IS KNOW THAT SPEC
 BOOKS SUBMITTED DOES CONTAIN A NOTE FOR
 MANUAL MEANS OF DISCONNECT, HOWEVER THE
 MANUFACTURE SPECS/CUT SHEETS DID NOT
 MATHC WITH THIS.
  
 5)NOTEL PLEASE SEE P1B AS THIS IS A 225A
 MLO WITH 300A OCP FEEDING THIS PANEL.
  
 6)NOTE: PLEASE SEE SOME CIRCUITS STILL
 SHOWN AS 30A OCP ON #12 AWG, PLEASE SEE
 MOST WERE CORRECTED ON PREVIOUS REVIEW.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  