| Date |
Text |
| 2005-11-14 00:00:00 | *** UNSAT *** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW AND SOME NEW COMMENTS DUE TO |
| | INFORMATION NOW SUBMITTED AND/OR CHANGES |
| | IN DESIGN. |
| | |
| | 1)NOTE: PLEASE SEE NO INFORMATION WAS |
| | SUBMITTED FOR FIRE PUMP WITH FIRE PUMP |
| | CONTROLLER. PLEASE SEE RISER DIAGRAM |
| | DOES NOT INCLUDE HP RATING OF PUMP IN |
| | ORDER TO VERIFY FEEDERS/SEC'S ETC. |
| | SPECS NOT SPECIFIC TO ANY ONE SIZE. |
| | PLEASE ALSO SUBMIT SPECS FOR PUMP, THE |
| | MANUFACTURE CUT SHEETS. |
| | |
| | 2)NOTE: PLEASE SEE NEC NFPA-70, |
| | 701.11(B)3, WHICH REQUIRES ADDITIONAL |
| | "ON-SITE" FUEL SOURCE WHEN RELYING ON |
| | THE UTILITY COMPANY ONLY FOR FUEL. |
| | PLEASE SUBMIT SPECS/ CUT SHEETS FOR |
| | "ON-SITE" TANK, LP). PLEASE SEE FIRE |
| | REVIEW COMMENTS FOR SIZING OF THE TANK |
| | AND WHETHER OR NOT THE SIZE MAY REQUIRE |
| | TANK TO BE DIRECTLY BURIED IN THE |
| | GROUND. |
| | |
| | 3)NOTE: PLEASE SEE RESPONSE LETTER |
| | MENTIONS CORRECTIONS MADE TO PLANS FOR |
| | GFI PROTECTION FOR ALL KITCHEN CIRCUITS |
| | 15AND 20A AND 120V. PER 2002 NEC 210.8B3 |
| | COULD NOT LOCATE THIS. |
| | |
| | 4)NOTE: PLEASE SEE EEP AND ELP WILL BE |
| | REQUIRED TO HAVE MCB'S AS SPECS FOR ATS |
| | SWITCH SUBMITTED FOR BOTH UNITS DOES NOT |
| | CONTAIN AN MANUAL MEANS OF DISCONNECT |
| | LOCATED ON THE OUTSIDE OF THE ATS FOR |
| | DISCONNECTING FEEDERS COMING INTO |
| | BUILDING FROM GEN. |
| | 225.31,225.34. |
| | PLEASE ALSO VERIFY IF THE SPECS FOR |
| | ATS'S SUBMITTED IS FOR BOTH. |
| | ** PLEASE KNOW, IT IS KNOW THAT SPEC |
| | BOOKS SUBMITTED DOES CONTAIN A NOTE FOR |
| | MANUAL MEANS OF DISCONNECT, HOWEVER THE |
| | MANUFACTURE SPECS/CUT SHEETS DID NOT |
| | MATHC WITH THIS. |
| | |
| | 5)NOTEL PLEASE SEE P1B AS THIS IS A 225A |
| | MLO WITH 300A OCP FEEDING THIS PANEL. |
| | |
| | 6)NOTE: PLEASE SEE SOME CIRCUITS STILL |
| | SHOWN AS 30A OCP ON #12 AWG, PLEASE SEE |
| | MOST WERE CORRECTED ON PREVIOUS REVIEW. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |