Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop B
Sequence Number 2
Notes
Date Text
2005-12-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05041760
 ADD: XXX W. EXECUTIVE CENTER DR.
 (74-43-43-20-00-000-3010)
 CONT: THE WEITZ CO.
 TEL: (561)686-5511
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) COMMENT# 2FROM THE PREVIOUS REVIEW,
 PERMIT APPLICATION CORRECT THE PCN TO
 (74-43-43-20-00-000-3010) OR PROVIDE
 ADDITIONAL INFORMATION.THE CITY GIS
 SYSTEM ONLY INDICATES A SINGLE LOT SEE
 ATTACHED PAGES. OWNER AS COURTNEY LAKES
 APARTMENTS LLC. PALM BEACH COUNTY
 PROPERTY APPRAISERS OFFICE INDICATES
 THIS SINGLE LOT HAS BEEN REPLATED INTO
 (5) LOTS. THE CITY HAS NOT RECEIVED A
 COPY OF THE REPLAT TO UPDATE OUR LAND
 FILE AND TO ADDRESS THE NEWLY FORMED
 LOTS. PROVIDE A COPY OF THE RECORDED
 REPLAT!!!!!
  
 2) COMMENT# 3 FROM THE PREVIOUS REVIEW
 SEE ATTACHMENT,LOW VALUE, CALCULATED
 VALUE IS: $9,907,170.00 SEE ADDITIONAL
 FEES.
  
 3) COMMENT# 5 FROM THE PREVIOUS
 REVIEWDEALS WWITH THE THRESHOLD
 INSPECTOR FORMS TO BE FILLED OUT,WPB
 AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 4) COMMENT# 7FROM THE PEVIOUS REVIW,
 903.8.2 FLOR ST STATUTE 553.895(2)
 ALL RESIDENTIAL BUILD. 3 OR MORE STORIES
 TALL WHETHER DESIGNATED AS TOWNHOUSE,
 CONDOMINIUMS, "APARTMENT HOUSES,
 TENEMENTS, GARDEN APARTMENTS OR BY ANY
 OTHER NAME SHALL BE SUPPLIED BY FIRE
 SPRINKLERS MEETING NFPA 101. SINCE THE
 FIRE SPRINKLERS ARE REQUIRED BY CODE
 THEY MUST BE PART OF THE PERMIT PACKAGE.
  
 5)COMMENT# 10 FROM THE PREVIOUS REVIEW,
 BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) COMMENT# 3A) FROM THE PREVIOUS REVIEW
  
 DEALS WITH CROSSWALKS FOR ACCESSIBLE
 ROUTES, PLEASE INDICATE WHERE THE
 ACCESSIBLE ROUTE IS ON EITHER C-2 OR
 C-3, ALSO INDICATE FLARED CURBING FOR
 SIDEWALKS.11-4.1.2(1) AT LEAST ONE
 ACCESSIBLE ROUTE COMPLYING WITH ?11-4.3
 SHALL BE PROVIDED WITHIN THE BOUNDARY OF
 THE SITE FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING SPACES,
 PASSENGER LOADING ZONES IF PROVIDED, AND
 PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE.
  
 7) PLANS INDICATE THE ACCESSIBLE PARKING
  
 COMMENT# 14 FROM THE PREVIOUS REVIEW,
  
 THE ACCESSIBLE PARKING SPACES ARE TO BE
 ON THE SHORTEST ROUTE OF TRAVEL.
 11-4.6.2 LOCATION. ACCESSIBLE PARKING
 SPACES SERVING A PARTICULAR
 BUILDING SHALL BE LOCATED ON THE
 SHORTEST SAFELY ACCESSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE.IN PARKING
 FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING
 SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN
 ACCESSIBLE PEDESTRIAN ENTRANCE OF THE
 PARKING FACILITY.IN BUILDINGS WITH
 MULTIPLE ACCESSIBLE ENTRANCES WITH
 ADJACENT PARKING, ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED
 CLOSEST TO THE ACCESSIBLE ENTRANCES.
  
 8) COMMENT# 18 FROM THE PREVIOUS REVIEW
 INDICATE COMPLIANCE WITH 11-9.1.4(1) FOR
 SUITE TYPE "C".18) 11-9.1.4(1) IN
 ORDER TO PROVIDE PERSONS WITH
 DISABILITIES A RANGE OF OPTIONS
 EQUIVALENT TO THOSE AVAILABLE TO OTHER
 PERSONS SERVED BY THE FACILITY, SLEEPING
 ROOMS AND SUITES REQUIRED TO BE
 ACCESSIBLE BY11-9.1.2 SHALL BE
 DISPERSED AMONG THE VARIOUS CLASSES OF
 SLEEPINGACCOMMODATIONS AVAILABLE TO
 PATRONS OF THE PLACE OF TRANSIENT
 LODGING.FACTORS TO BE CONSIDERED
 INCLUDE ROOM SIZE, COST, AMENITIES
 PROVIDED, & THE NUMBER OF BEDS PROVIDED.
  
 9) COMMENT FROM# 24 FROM THE PREVIOUS
 REVIEW, THERE SEEMS TO BE CONFUSION ON
 THE LAUNDRY& REFUSE CHUTE ON LOCATION
 SEE A-1.2 & A-1.3 .
  
 10) COMMENT # 26 FROM THE PREVIOUS
 REVIEW, MISSING RATING ON DOORS LEADING
 TO REFUSE & LAUNDRY ROOMS A 3/4HR
 RATING.705.2.4.3 REFUSE AND LAUNDRY
 CHUTE ACCESS ROOMS.ACCESS OPENINGS
 FOR REFUSE AND LAUNDRY CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION AND
 OPENING PROTECTIVES IN ACCORDANCE WITH
 TABLE 705.1.2.ACCESS OPENINGS TO
 REFUSE AND LAUNDRY CHUTES SHALL NOT BE
 LOCATED IN EXIT ACCESS CORRIDORS OR EXIT
 ENCLOSURES.
  
 11) COMMENT# 40 FROM THE PREVIOUS REVIEW
 DEALS WITH CURRIES EXTERIOR DOORS IN END
 ZONE# 5, REPORT GOOD FOR +/- 62 REQUIRES
 A -68.3.
  
 12) COMMENT# 41 FROM THE PREVIOUS REVIEW
  
 DEALS WITH RESAM AES AUTO DOORS, ARCH
 PLANS A4.1 SECTION# 1 INDICATES A NEW
 STEEL MULLION NOT DEPICTED ON STRUCRURAL
 PLANS. 1707.4.5.2 MULLIONS SHALL BE
 DESIGNED TO TRANSFER THE DESIGN PRESSURE
 LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING
 SUBTRATE. INDICATE COMPLIANCE.
  
 13) A-3.0 WINDOW SCHEDULE INDICATES A
 WINDOW TYPE "A" BUT DOESN'T INDICATE IF
 THIS IS A HORIZONTAL SLIDER OR FIXED?
 IF THE WINDOWS ARE SLIDERS THE REPORT
 WAS TESTED WITH A 63" WINDOW WHEREAS THE
 PLANS CALL FOR A 65" WINDOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026