Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 19
Notes
Date Text
2008-04-24 16:05:15** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE NOTES DATED 4/7/08 WHICH REQUESTED
 SUBMISSION OF UPDATED SHEETS FOR OTHER TRADES SUCH AS
 ARCHITECTURAL, SITE ETC.
 STILL NEED UPDATE SLAB DETAILS, ELEVATION, TIE DOWN,
 OVER TURN DETAILS AS REQUIRE DIN FBC AND NFPA-110
 CHAPTER 7.
 PLEASE KNOW ONCE THE OTHER DETAILS AND PLANS ARE
 REVIEWED AND MEET THE REQUIREMENTS OF THE FBC AND OTHER
 ADOPTED CODES ELECTRICAL REVIEW WILL BE OK.
  
 2) NOTE: PLEASE SEE THAT THREE SETS OF THE MANUFACTURES
 SPECS/CUT SHEETS ARE SUBMITTED.
 FBC106.1.2 THIS IS A THRESHOLD PROJECT.
 ONE COMPLETE SET REMAINS ON FILE THE OTHER TWO ARE FOR
 JOB-SITE.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717