Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 16
Notes
Date Text
2008-01-22 09:14:51REDLINED NEUTRAL SHOWN FOR FIRE PUMP. THIS CONDUCTOR
 MAY NOT BE SMALLER THAN THE GROUNDING ELECTRODE.
 250.24C, 230.42C