| Plan Review Notes For Permit 05041760 |
| Permit Number |
05041760 |
|
| Review Stop |
M |
| Sequence Number |
14 |
|
| Notes |
| Date |
Text |
| 2008-06-02 15:03:29 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE FUEL | | | STORAGE TANK FOR THE GENERATOR IS 550 GAL. DIESEL FUEL. | | | PER NFPA 30 TABLE 4.3.2.1.1 (B), THE STORAGE TANK MUST | | | BE 10 FEET FROM THE PROPERTY LINE. PLEASE SUBMIT | | | DOCUMENTATION SHOWING THE DISTANCE BETWEEN THE FUEL | | | STORAGE TANK AND THE PROPERTY LINE. | | | | | | 2) PLEASE SUBMIT DOCUMENTATION STATING THE SIZE OF THE | | | GENERATOR'S FUEL STORAGE TANK AND TYPE OF FUEL. PER | | | 2004 FBC 106.3, 106.4, AND 106.5. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|