2008-06-02 15:03:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE FUEL
 STORAGE TANK FOR THE GENERATOR IS 550 GAL. DIESEL FUEL.
 PER NFPA 30 TABLE 4.3.2.1.1 (B), THE STORAGE TANK MUST
 BE 10 FEET FROM THE PROPERTY LINE. PLEASE SUBMIT
 DOCUMENTATION SHOWING THE DISTANCE BETWEEN THE FUEL
 STORAGE TANK AND THE PROPERTY LINE.
  
 2) PLEASE SUBMIT DOCUMENTATION STATING THE SIZE OF THE
 GENERATOR'S FUEL STORAGE TANK AND TYPE OF FUEL. PER
 2004 FBC 106.3, 106.4, AND 106.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]