Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 14
Notes
Date Text
2007-11-27 11:05:34REDLINED, NEUTRAL CONDUCTOR FOR FIRE PUMP SHALL NOT BE
 SMALLER THAN GROUNDING ELECTRODE CONDUCTOR.
 230.42C, 250.24C.