| 2008-02-22 14:30:47 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 FUEL GAS |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE |
| | METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS. |
| | TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM |
| | DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER. |
| | SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM |
| | WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.-- |
| | INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS, |
| | THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 & |
| | 3. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM STILL SHOWS |
| | 2" PIPE UP TO THE BRANCH LINE FOR THE GAS DRYERS. THERE |
| | WAS NO RESPONSE TO THE RISER DIAGRAM FOR THE POOL/BATH |
| | RISER NOT REFLECTING THE GAS RISER AT THE METER AND ALL |
| | CUT SECTIONS WERE NOT PROVIDED.--REGULATOR MODELS |
| | INDICATED FOR RTU'S 1 & 2 ARE NOT APPROVED. MAXIMUM 140 |
| | MBH FOR THE MODEL 325-3L, BUT 150 MBH INDICATED ON THE |
| | RISER DIAGRAM. |
| | |
| | 4. SHT P-08 REVISION HISTORY ON STAMPED/REVIEWED SHEET |
| | INDICATES REVISIONS 2 & 3. THESE HAVE BEEN DELETED FROM |
| | THE REVISION HISTORY.--NEW REVISIONS THIS SUBMITTAL |
| | INDICATE REVISIONS 5, 7 & 8, BUT ONLY REVISION 8 HAS |
| | BEEN LOCATED. PLEASE INDICATE WHERE REVISIONS 5 & 7 CAN |
| | BE FOUND. SHOW THE COMPLETE REVISION HISTORY ON THE |
| | REVISION INDEX. SECTION 104.2.1.3. |
| | ****RESPONSE NOTED, BUT THE SHEET ON FILE AND REVIEWED |
| | SHOWS REVISION 2, DATED 1-13-06, AND REVISION 3, DATED |
| | 6-12-06. PLEASE SHOW COMPLETE REVISION HISTORY ON THE |
| | REVISION INDEX. SECTION 104.2.1.3. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.-- THE |
| | MANUF. SHEETS FOR THE POOL HEATER SHALL |
| | BE SUBMITTED. |
| | ****RESPONSE NOTED, BUT THE DRYER MANUF SHEETS ARE NOT |
| | APPROVED. THERE IS NO LISTING INDICATED ON THE MANUF. |
| | SHEETS.NO BTU LOAD INDICATED. COVER SHEET STATES |
| | "REFER TO PAGE 4 FOR MODEL IDENTIFICATION". PAGE 4 HAS |
| | NOT BEEN SUBMITTED WITH MANUF. SPECIFICATION SHEETS. -- |
| | NO MANUF. SHEETS FOR THE RTU UNITS1 & 2 SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |