| 2007-10-27 10:09:02 | ** DENIED REVISION ** |
| | |
| | 1) NOTE: PLEASE SEE COMMENTS FROM TWO PREVIOUS REVIEWS |
| | AS THE COMMENTS WITH RESPECT THE ENERGY CALCULATIONS |
| | HAS NOT YET BEEN ADDRESSED. AS PREVIOUSLY MENTIONED NO |
| | FURTHER ELECTRICAL REVISIONS WILL BE GRANTED UNTIL THE |
| | CALCULATIONS HAVE BEEN CORRECTED, SUBMITTED AND ARE |
| | CODE COMPLIANT FOR BUILDING BEING CONSTRUCTED. |
| | FBC 2001 CHAPTER 13. |
| | |
| | 2) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE |
| | FIRST MEANS OF DISCONNECT AT THE FIRE PUMP CONTROLLER. |
| | PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO INDICATE |
| | AN INCREASE IN FIRE PUMP FROM 20HP TO 60HP. |
| | PLEASE PROVIDE NEW LOCK ROTOR OVER CURRENT PROTECTION. |
| | PLEASE SUBMIT NEW MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | NEW FIRE PUMP CONTROLLER, AND FIRE PUMP. |
| | PLEASE SEE THE FIRE SPRINKLER PLANS ON FILE DO NOT |
| | CORRELATE WITH SIZE AND WILL BE REQUIRED TO BE REVISED |
| | ALSO. |
| | PLEASE SEE 250.20, 250.24, ETC FOR GROUNDED NEUTRAL. IS |
| | THE #2 AS SHOWN ON #27 NOTE FROM FPL THE NEUTRAL? IF SO |
| | PLEASE COORDINATE THIS WITH NOTE #3. |
| | OTHER ADDITIONAL INFORMATION AND COORDINATION PER |
| | 104.1.2, OF 2001 FBC AND NEC 695.4, NFPA-20, NEC 110.3, |
| | 90.7 ETC. |
| | |
| | 3) NOTE: PLEASE SEE UNIT B MISSING BEDROOM #2 |
| | RECEPTACLE PER 210.62, 210.52 |
| | |
| | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | PLEASE ADDRESS COMMENT NUMBER #1. |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |