Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 13
Notes
Date Text
2007-10-27 10:09:02** DENIED REVISION **
  
 1) NOTE: PLEASE SEE COMMENTS FROM TWO PREVIOUS REVIEWS
 AS THE COMMENTS WITH RESPECT THE ENERGY CALCULATIONS
 HAS NOT YET BEEN ADDRESSED. AS PREVIOUSLY MENTIONED NO
 FURTHER ELECTRICAL REVISIONS WILL BE GRANTED UNTIL THE
 CALCULATIONS HAVE BEEN CORRECTED, SUBMITTED AND ARE
 CODE COMPLIANT FOR BUILDING BEING CONSTRUCTED.
 FBC 2001 CHAPTER 13.
  
 2) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRST MEANS OF DISCONNECT AT THE FIRE PUMP CONTROLLER.
 PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO INDICATE
 AN INCREASE IN FIRE PUMP FROM 20HP TO 60HP.
 PLEASE PROVIDE NEW LOCK ROTOR OVER CURRENT PROTECTION.
 PLEASE SUBMIT NEW MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW FIRE PUMP CONTROLLER, AND FIRE PUMP.
 PLEASE SEE THE FIRE SPRINKLER PLANS ON FILE DO NOT
 CORRELATE WITH SIZE AND WILL BE REQUIRED TO BE REVISED
 ALSO.
 PLEASE SEE 250.20, 250.24, ETC FOR GROUNDED NEUTRAL. IS
 THE #2 AS SHOWN ON #27 NOTE FROM FPL THE NEUTRAL? IF SO
 PLEASE COORDINATE THIS WITH NOTE #3.
 OTHER ADDITIONAL INFORMATION AND COORDINATION PER
 104.1.2, OF 2001 FBC AND NEC 695.4, NFPA-20, NEC 110.3,
 90.7 ETC.
  
 3) NOTE: PLEASE SEE UNIT B MISSING BEDROOM #2
 RECEPTACLE PER 210.62, 210.52
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 PLEASE ADDRESS COMMENT NUMBER #1.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]