Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop E
Sequence Number 12
Notes
Date Text
2007-10-05 12:29:05*** DENIED REVISION ***
  
  
 1) NOTE:PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS
 WHICH COORDINATE ALL LIGHTING ON PLANS AND FIXTURE
 LEGEND. PLEASE SEE THE INPUT DATA REPORT NEEDS ALL
 ITEMS ON PLANS WHICH CONSUME ENERGY AND PROVIDES
 EFFICIENCY TO BE ON THE IDR.
 PLEASE SEE THE LIGHTING FIXTURE WATTAGES AS SHOWN DO
 NOT MATCH WITH THE LIGHTING FIXTURES WATTAGES AS SHOWN
 AND LISTED ON PLANS.
 PLEASE SEE THAT NO EXTERIOR LIGHTING COULD BE FOUND ON
 THE IDR SO NO REVIEW OF THESE COULD BE DONE. CHAPTER
 13, 400.2, 400.3.A, 415.1.AB.1, 415.1.A, TABLE 4-15,
 415.2 ETC.
 PLEASE CLARIFY HOW 13-415.1.ABCD.1.1.4 IS MET?
  
 CALCULATIONS WILL BE ROUTED TO OTHER TRADES.
  
 IF THERE ARE ANY QUESTIONS AS STATED ON PREVIOUS
 REVIEW
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  