| 2008-01-17 12:06:39 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2001 FUEL GAS |
| | |
| | 1. SHTS P-05A, P-O5B & P-06 PER SECTION 1107.3 THE |
| | CROSS-SECTIONAL AREA OF AN OVERFLOW SCUPPER SHALL BE |
| | THREE TIMES THE CROSS-SECTIONAL AREA OF THE PRIMARY |
| | ROOF DRAIN AND THE SCUPPER SHALL HAVE A MINIMUM OPENING |
| | DIMENSION OF 4 INCHES. |
| | |
| | 2. SHTS P-05A, P-05B & P-06 PER SECTION 1503.4.2 |
| | OVERFLOW SCUPPERS SHALL HAVE A MINIMUM OPENING |
| | DIMENSION OF 4 INCHES IN HEIGHT AND SHALL BE PLACED IN |
| | WALLS OR PARAPETS WITH THE INLET FLOW LINE NOT LESS |
| | THAN 2 INCHES ABOVE THE ROOF SURFACE, EXCLUDING SUMPS, |
| | OR MORE THAN 4 INCHES ABOVE THE ROOF SURFACE AND SHALL |
| | BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| | LEADERS. EACH VERTICAL LEADER SHALL BE SUPPLIED WITH AN |
| | EMERGENCY OVERFLOW SCUPPER SIZED PER SECTION 1107.3 OF |
| | THE PLUMBING CODE. |
| | |
| | 3. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE |
| | METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS. |
| | TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM |
| | DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER. |
| | SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM |
| | WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.-- |
| | INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS, |
| | THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 & |
| | 3. |
| | |
| | 4. SHT P-08 REVISION HISTORY ON STAMPED/REVIEWED SHEET |
| | INDICATES REVISIONS 2 & 3. THESE HAVE BEEN DELETED FROM |
| | THE REVISION HISTORY.--NEW REVISIONS THIS SUBMITTAL |
| | INDICATE REVISIONS 5, 7 & 8, BUT ONLY REVISION 8 HAS |
| | BEEN LOCATED. PLEASE INDICATE WHERE REVISIONS 5 & 7 CAN |
| | BE FOUND. SHOW THE COMPLETE REVISION HISTORY ON THE |
| | REVISION INDEX. SECTION 10104.2.1.3. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.-- THE |
| | MANUF. SHEETS FOR THE POOL HEATER SHALL |
| | BE SUBMITTED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |