2008-01-17 12:06:39DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 FUEL GAS
  
 1. SHTS P-05A, P-O5B & P-06 PER SECTION 1107.3 THE
 CROSS-SECTIONAL AREA OF AN OVERFLOW SCUPPER SHALL BE
 THREE TIMES THE CROSS-SECTIONAL AREA OF THE PRIMARY
 ROOF DRAIN AND THE SCUPPER SHALL HAVE A MINIMUM OPENING
 DIMENSION OF 4 INCHES.
  
 2. SHTS P-05A, P-05B & P-06 PER SECTION 1503.4.2
 OVERFLOW SCUPPERS SHALL HAVE A MINIMUM OPENING
 DIMENSION OF 4 INCHES IN HEIGHT AND SHALL BE PLACED IN
 WALLS OR PARAPETS WITH THE INLET FLOW LINE NOT LESS
 THAN 2 INCHES ABOVE THE ROOF SURFACE, EXCLUDING SUMPS,
 OR MORE THAN 4 INCHES ABOVE THE ROOF SURFACE AND SHALL
 BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS. EACH VERTICAL LEADER SHALL BE SUPPLIED WITH AN
 EMERGENCY OVERFLOW SCUPPER SIZED PER SECTION 1107.3 OF
 THE PLUMBING CODE.
  
 3. SHT P-08 GAS RISER DIAGRAM 2-1/2" REQUIRED FROM THE
 METER AND UP TO THE BRANCH LINE FOR THE GAS DRYERS.
 TABLE 402(8).--POOL/BATH HOUSE GAS RISER DIAGRAM
 DOES NOT REFLECT THE GAS RISER DIAGRAM AT THE METER.
 SHOW ALL CUT LENGTHS FOR THE POOL HEATER GAS LINES FROM
 WHERE IT CONNECTS TO THE MAIN GAS RISER DIAGRAM.--
 INDICATE REGULATOR MODEL NUMBERS FOR THE GAS DRYERS,
 THE HOT WATER BOOSTER, POOL HEATER AND THE RTU'S 1, 2 &
 3.
  
 4. SHT P-08 REVISION HISTORY ON STAMPED/REVIEWED SHEET
 INDICATES REVISIONS 2 & 3. THESE HAVE BEEN DELETED FROM
 THE REVISION HISTORY.--NEW REVISIONS THIS SUBMITTAL
 INDICATE REVISIONS 5, 7 & 8, BUT ONLY REVISION 8 HAS
 BEEN LOCATED. PLEASE INDICATE WHERE REVISIONS 5 & 7 CAN
 BE FOUND. SHOW THE COMPLETE REVISION HISTORY ON THE
 REVISION INDEX. SECTION 10104.2.1.3.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.-- THE
 MANUF. SHEETS FOR THE POOL HEATER SHALL
 BE SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  