| Plan Review Notes For Permit 05041760 |
| Permit Number |
05041760 |
|
| Review Stop |
E |
| Sequence Number |
11 |
|
| Notes |
| Date |
Text |
| 2007-08-27 14:37:54 | | | | SOME SHEETS OK, AND STAMPED. | | | | | | | | | | | | | | | | | | *** DENIED*** | | | | | | SHEETS E16 | | | | | | 1) NOTE: PLEASE SEE THE NOTES ON THE ENERGY | | | CALCULATIONS AS NO FURTHER REVISIONS WILL BE ACCEPTED | | | UNTIL THE COMMENTS ARE CORRECTED FOR THE FBC CHAPTER 13 | | | REQUIREMENTS. | | | | | | | | | 2) NOTE: PLEASE SEE THE REVISED SHEET E-16 AS THERE ARE | | | FEEDERS WHICH DO NOT MEET THE MINIMUM SIZE PER THE | | | NEC. | | | PLEASE SEE 240.4 WHEN A CONDUCTOR SIZE DOES NOT | | | COORDINATE WITH THE OVER CURRENT PROTECTION DEVICES, IT | | | IS PERMISSIBLE TO GO THE NEXT STANDARD SIZE OVER | | | CURRENT PROTECTION PER 240.6, HOWEVER YOU MAY NOT | | | EXCEED THAT NEXT STANDARD SIZE. | | | PLEASE SEE THE MINIMUM FEEDERS FOR EEP AND P1A | | | 110.14, 240.4, 310.16 | | | | | | PLEASE REVISE. | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|