Plan Review Notes
Plan Review Notes For Permit 05041760
Permit Number 05041760
Review Stop P
Sequence Number 10
Notes
Date Text
2007-10-15 14:44:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. SHT P-02C REVISION #5 DATED 07/11/07 & REVISION #6
 DATED 07/22/07 WERE APPROVED PREVIOUSLY. NO
 CHANGE/REVISION NOTED. SHEET NOT APPROVED.
  
 B. SHT P-06 THE ROOF DRAINAGE AREA SHOWN DOES NOT
 APPEAR TO BE CORRECT. SEE PREVIOUS REVISION COMMENTS
 FOR THIS SHEET. NO CALCULATIONS WERE SUBMITTED, AND NO
 INFORMATION FOR THE SCUPPERS AS REQUESTED. (SEE
 FOLLOWING FROM PREVIOUS REVIEW DATED 09/05/07):
  
 (5). SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO
 BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR
 THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. --
 SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF
 DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 &
 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE
 FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE
 CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE
 STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.--
 SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR
 EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON
 PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH.
 DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL
 DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1.--
 PLEASE RESPOND TO ALL OF THIS AFTER AND INCLUDING
 "SUBMIT CALCULATIONS.....
  
 C. SHT P-08 SEE THE FOLLOWING COMMENTS FROM 10/13/07
 FOR THE GAS ISOMETRIC RISER DIAGRAM:
  
 DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED.
 SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE
 POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND
 CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH
 REGULATOR ON THE ISOMETRIC.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--NOT
 INDICATED FOR POOL HOUSE WATER HEATER.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE
 RESPONSE FOR COMMENT IS REVIEWED.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER
 HEATER MANUF. SHEETS REQUIRED.
  
 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL
 REGULATORS. INDICATED MODEL NUMBER USED FOR EACH
 REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL
 BE USED TO VERIFY CAPACITY.
  
 ****END OF GAS COMMENTS FROM 10-13-07****
  
 D. SHT P-11 NO CHANGE FROM REVISION #4 ON SHEET SEALED
 07/06/07. SHEET NOT APPROVED AS THERE ARE NO NEW
 REVISIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]