| 2007-10-15 14:44:50 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | A. SHT P-02C REVISION #5 DATED 07/11/07 & REVISION #6 |
| | DATED 07/22/07 WERE APPROVED PREVIOUSLY. NO |
| | CHANGE/REVISION NOTED. SHEET NOT APPROVED. |
| | |
| | B. SHT P-06 THE ROOF DRAINAGE AREA SHOWN DOES NOT |
| | APPEAR TO BE CORRECT. SEE PREVIOUS REVISION COMMENTS |
| | FOR THIS SHEET. NO CALCULATIONS WERE SUBMITTED, AND NO |
| | INFORMATION FOR THE SCUPPERS AS REQUESTED. (SEE |
| | FOLLOWING FROM PREVIOUS REVIEW DATED 09/05/07): |
| | |
| | (5). SHT P-06 INDICATES A ROOF DRAIN ON WHAT APPEARS TO |
| | BE A HIP ROOF. PLEASE CLARIFY.--SUBMIT A DETAIL FOR |
| | THE ROOF DRAIN CONNECTION TO THE PEAK OF THE ROOF. -- |
| | SUBMIT CALCULATIONS FOR THE PRIMARY AND SECONDARY ROOF |
| | DRAINS, (IF ROOF HAS A PARAPET) PER SECTIONS 1106 & |
| | 1107 WITH ALL SUBSECTIONS & TABLES. SHOW THE SQUARE |
| | FOOTAGE OF THE ROOF AND 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS ADDED TO THE ROOF AREA IN THE |
| | CALCULATIONS.--ROOF DRAIN IS NOT SHOWN ON THE |
| | STORM DRAIN TABLE. PLEASE CLARIFY. SECTION 104.2.1.-- |
| | SHOW THE LOCATION OF ALL SECONDARY ROOF DRAINS OR |
| | EMERGENCY ROOF SCUPPERS. SECTION 104.2.1.--NOTE ON |
| | PLANS STATES "FOR RELIEF SCUPPER DRAINS SEE ARCH. |
| | DRAWINGS". PLEASE INDICATE WHERE IN THE ARCHITECTURAL |
| | DRAWINGS THESE CAN BE FOUND. SECTION 104.2.1.-- |
| | PLEASE RESPOND TO ALL OF THIS AFTER AND INCLUDING |
| | "SUBMIT CALCULATIONS..... |
| | |
| | C. SHT P-08 SEE THE FOLLOWING COMMENTS FROM 10/13/07 |
| | FOR THE GAS ISOMETRIC RISER DIAGRAM: |
| | |
| | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE.--COMPLETE ISOMETRIC NOT SUBMITTED. |
| | SUBMIT A COMPLETE ISOMETRIC WITH THE PIPING FOR THE |
| | POOL HOUSE WATER HEATER SHOWN WITH ALL CUT SECTIONS AND |
| | CORRESPONDING LENGHTS.--INDICATE THE MODEL OF EACH |
| | REGULATOR ON THE ISOMETRIC. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED.--NOT |
| | INDICATED FOR POOL HOUSE WATER HEATER. |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33).--POOL HOUSE WATER HEATER NOT INDICATED. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4).--TO BE VERIFIED ONCE |
| | RESPONSE FOR COMMENT IS REVIEWED. |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--POOL HOUSE WATER |
| | HEATER MANUF. SHEETS REQUIRED. |
| | |
| | 6. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR ALL |
| | REGULATORS. INDICATED MODEL NUMBER USED FOR EACH |
| | REGULATOR AND INDICATE WHERE EACH REGULATOR MODEL WILL |
| | BE USED TO VERIFY CAPACITY. |
| | |
| | ****END OF GAS COMMENTS FROM 10-13-07**** |
| | |
| | D. SHT P-11 NO CHANGE FROM REVISION #4 ON SHEET SEALED |
| | 07/06/07. SHEET NOT APPROVED AS THERE ARE NO NEW |
| | REVISIONS. |
| | |
| | REVIEW BY KEN STEVENS |