| 2007-09-26 11:05:10 | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE & |
| | REFERENCED CODES, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | *** DENIED *** |
| | THE FOLLOWING COMMENTS MAY HAVE BEEN PROVISO-ED IN |
| | PREVIOUS REVIEWS BUT REVISED MECHANICAL PLANS STILL DO |
| | NOT SHOW COMPLIANCE WITH 2001 FBC/M 607.1.2 OR |
| | EXCEPTIONS 607.1.3. |
| | |
| | 1) REVISED MECHANICAL PLAN PAGE M-03 SHOWS A 22" X 10" |
| | SUPPLY AIR DUCT PENETRATING TWO 1 HOUR FIRE RATED WALLS |
| | TO THE ELECTRICAL ROOM #120, THE DUCTS WILL NEED FIRE |
| | DAMPERS, SEE 2001 FBC/M 607.1.2. |
| | |
| | 2) REVISED MECHANICAL PLAN PAGE M-04 SHOWS A 12" X 8" |
| | SUPPLY AIR DUCT PENETRATING A ONE HOUR FIRE RATED WALL |
| | FROM STORAGE ROOM #228 TO CORRIDOR #223, AND A 8" X 6" |
| | DUCT FROM STORAGE ROOM #213 TO CORRIDOR #223, THE DUCTS |
| | WILL NEED A FIRE DAMPERS, SEE 2001 FBC/M 607.1.2. |
| | |
| | 3) REVISED MECHANICAL PLAN PAGE M-05 SHOWS A 12" X 15" |
| | SUPPLY AIR DUCT PENETRATING A ONE HOUR FIRE RATED WALL |
| | FROM STORAGE ROOM #623 TO MULTIPURPOSE ROOM #621, THE |
| | DUCT WILL NEED A FIRE DAMPER, SEE 2001 FBC/M 607.1.2. |
| | |
| | 4) REVISED MECHANICAL PLAN PAGE M-02 PASSED REVIEW AND |
| | WAS STAMPED. |
| | |